separation between the basement and the first floor. If the heating plant is on the same
level with the residents, the furnace room shall be separated from the remainder of
the building with materials that will afford a minimum 1 hour protected enclosure.
A permanent outside vent which cannot be closed shall be incorporated in the
design of heating plant rooms so that adequate air for proper combustion is assured.
Space heaters are prohibited.
(2) Factory mutual and underwriters' laboratories approved permanent, fixed-
type electrical heating, such as recognized panel or baseboard fixed-type may be
utilized in any location. In existing homes where an American gas association
approved sealed combustion wall heater has been installed in accordance with both
the AGA and the manufacturer's recommendations, approval will be given if the
unit is located on an outside wall, obtains combustion air directly from the outside
and vents products of combustion directly to the outside.
(3) Flame-producing water heaters or incinerators shall be installed with the
same protection as a heating plant.
(4) Storage of combustible materials is prohibited in rooms containing the
heating plant, water heater, or incinerator.
History: 1979 AC.
R 400.2245 Fire extinguishers.
Rule 245. A minimum of one 5-pound multi-purpose fire extinguisher or
equivalent shall be provided for use in a family home on each occupied floor and in
the basement.
History: 1979 AC.
R 400.2246 Electrical service.
Rule 246. Electrical service shall be maintained in
a
safe condition.Where
conditions indicate a need for inspection, and on all new or remodeled projects,
the electrical service shall be inspected by a qualified electrical inspection service
and a copy of the inspection report shall be submitted to the department.
History: 1979 AC.
R 400.2247 Safety generally.
Rule 247. (1) Stairways shall have sturdy and securely fastened handrails,
not less than 30 inches nor more than 34 inches above the upper surface of the tread.
Exterior stairways and porches shall have handrails on the open sides.
(2) Scatter or throw rugs on hard finished floors shall have a nonskid backing.
(3) Handrails and nonskid surfacing or strips shall be installed in showers and
bath areas.
(4) Sidewalks, fire escape routes, and entrances shall be kept free of any hazards
such as ice, snow and debris.
Page 3