DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
BUREAU OF FIRE SERVICES  
ADULT FOSTER CARE FACILITIES  
(By authority conferred on the bureau of fire services in cooperation with the department  
of human services and the state fire safety board by section 10 of 1979 PA 218, MCL  
400.710.  
PART 1. GENERAL PROVISIONS  
R 400.18101 Applicability.  
Rule 101. (1) These rules apply to all adult foster care facilities licensed for 7 or  
more adults pursuant to the provisions of 1979 PA 218, MCL 400.701 to 400.737  
(2) These rules supersede all local regulations applicable specifically to adult foster  
care facilities. Local ordinances, regulations, or construction codes regulating institutions  
shall not be applied to adult foster care facilities licensed for 7 or more adults including  
existing adult foster care congregate facilities. This subrule shall not be construed to  
exempt adult foster care facilities from local construction codes that are applicable to  
private residences. This provision is in compliance with section 33 of the adult foster care  
facility licensing act, 1979 PA 218, MCL 400.733.  
History: 1994 AACS; 2012 AACS.  
R 400.18102 Life safety code; adoption by reference; access to Michigan rules as  
referenced.  
Rule 102. (1) The provisions of chapters 1 to 10, 32 and 33 of national fire protection  
association (NFPA) standard 101, 2006 edition, entitled "Life Safety Code," referred to  
in these rules as “code” are adopted by reference in these rules.  
(2) Copies of the adopted provisions in subrules (1) and (3) of this rule are available  
for inspection and from the National Fire Protection Association, 1 Batterymarch Park, P.  
otherwise specified in subrule (3) of this rule. The cost as of the time of adoption of  
these rules is $75.00. The costs of the adopted provisions in subrule (3) of this rule are  
specified in subrule (3) of this rule. Copies of adopted standards are available for  
inspection at the offices of the Bureau of Fire Services, 4th Floor, 525 West Allegan, P. O.  
Box 30700, Lansing, Michigan 48909. Copies of the adopted provisions may be  
purchased from the bureau of fire services at the same cost as from the national source  
identified in subrules (1) and (3) of this rule plus $30.00 for shipping and handling as of  
the time of the adoption of these rules.  
(3) Chapter 2 of the code is amended to read as follows:  
2.1 General.  
Page 1  
The documents or portions thereof listed in this chapter are referenced within this  
code and are adopted by reference in these rules. The cost of each standard at the time of  
the adoption of these rules is indicated after the title.  
2.2 NFPA Publications. www.nfpa.org  
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.  
NFPA 1. “Uniform Fire Code ,” 2006 edition.  
NFPA 10. “Standard for Portable Fire Extinguishers,” 2002 edition.  
$38.00/each  
$72.00/each  
NFPA 11. “Standard for Low-, Medium-, and High-Expansion Foam,” 2005 edition.  
$38.00/each  
NFPA 12. “Standard on Carbon Dioxide Extinguishing Systems, 2005 edition.”  
$38.00/each  
NFPA 12A. “Standard on Halon 1301 Fire Extinguishing Systems, 2004 edition.”  
$38.00/each  
NFPA 13. “Standard for the Installation of Sprinkler Systems, 2002 edition”  
$72.00/each  
NFPA 13D. “Standard for the Installation of Sprinkler Systems in One- and Two-  
Family Dwellings and Manufactured Homes, 2002 edition.”  
$34.50/each  
NFPA 13R. “Standard for the Installation of Sprinkler Systems in Residential  
Occupancies up to and Including Four Stories in Height,” 2002 edition.  
$34.50/each  
NFPA 14. “Standard for the Installation of Standpipe and Hose Systems,” 2003  
edition.  
$34.50/each  
NFPA 15. “Standard for Water Spray Fixed Systems for Fire Protection,” 2001  
edition.  
$38.00/each  
NFPA 16. “Standard for the Installation of Foam-Water Sprinkler and Foam-Water  
Spray Systems,” 2003 edition.  
$34.50/each  
NFPA 17. “Standard for Dry Chemical Extinguishing Systems,” 2002 edition.  
$34.50/each  
NFPA 17A. “Standard for Wet Chemical Extinguishing Systems,” 2002 edition.  
$29.00/each  
NFPA 25. “Standard for the Inspection, Testing, and Maintenance of Water-Based  
Fire Protection Systems,” 2002 edition.  
$44.00/each  
Page 2  
NFPA 30B. “Code for the Manufacture and Storage of Aerosol Products, 2002  
edition.”  
$38.00/each  
NFPA 31. “Standard for the Installation of Oil-Burning Equipment,” 2001  
edition. References to this standard mean the Michigan administrative rules R 29.5401 to  
R 5419, promulgated by the Michigan department of natural resources and environment.  
NFPA 40. “Standard for the Storage and Handling of Cellulose Nitrate Film,” 2001  
edition.  
$29.00/each  
NFPA 45. “Standard on Fire Protection for Laboratories Using Chemicals,” 2004  
edition.  
$38.00/each  
NFPA 54. “National Fuel Gas Code,” 2006 edition.  
$44.00/each  
NFPA 58. “Liquefied Petroleum Gas Code,” 2004 edition. References to this code  
mean the Michigan administrative rules relating to storage and handling of liquefied  
petroleum gases, R 29.6001 to R 29.6097, promulgated by the Michigan department of  
natural resources and environment pursuant to the act.  
NFPA 70. “National Electrical Code®,” 2005 edition with amendments as provided  
in the Michigan electrical code, R 408.30801 to 408.30873, promulgated by the Michigan  
department of energy, labor, and economic growth, bureau of construction codes.  
NFPA 72. “National Fire Alarm Code,” 2002 edition.  
NFPA 80. “Standard for Fire Doors and Fire Windows,” 1999 edition.  
$38.00/each  
$54.00/each  
NFPA 82. “Standard on Incinerators and Waste and Linen Handling Systems and  
Equipment, 2004 edition.”  
$34.50/each  
NFPA 88A. “Standard for Parking Structures, 2002 edition.”  
$29.00/each  
NFPA 90A. “Standard for the Installation of Air-Conditioning and Ventilating  
Systems, 2002 edition.”  
$34.50/each  
NFPA 90B. “Standard for the Installation of Warm Air Heating and Air-Conditioning  
Systems,” 2006 edition.  
$29.00/each  
NFPA 91. “Standard for Exhaust Systems for Air Conveying of Vapors, Gases. Mists,  
and Noncombustible Particulate Solids,” 2004 edition.  
$29.00/each  
NFPA 92B. “Standard for Smoke Management Systems in Malls, Atria, and Large  
Spaces,” 2005 edition.  
$38.00/each  
NFPA 96. “Standard for Ventilation Control and Fire Protection of Commercial  
Cooking Operations,” 2004 edition.  
$34.50/each  
Page 3  
NFPA 99. “Standard for Health Care Facilities,” 2005 edition.  
$54.00/each  
NFPA 101A. “Guide on Alternative Approaches to Life Safety,” 2004 edition.  
$38.00/each  
NFPA 105. “Standard for the Installation of Smoke Door Assemblies,” 2003 edition.  
$29.00/each  
NFPA 110. “Standard for Emergency and Standby Power Systems,” 2005 edition.  
$34.50/each  
NFPA 111. “Standard on Stored Electrical Energy Emergency and Standby Power  
Systems,” 2005 edition.  
$29.00/each  
NFPA 160. “Standard for the Use of Flame Effects Before an Audience,” 2006  
edition.  
$34.50/each  
NFPA 211. “Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning  
Appliances,” 2003 edition.  
$38.00/each  
NFPA 220. “Standard on Types of Building Construction,” 2006 edition.  
$29.00/each  
NFPA 221. “Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier  
Walls,” 2006 edition.  
$34.50/each  
NFPA 241. “Standard for Safeguarding Construction, Alteration, and Demolition  
Operations,” 2004 edition.  
$34.50/each  
NFPA 251. “Standard Methods of Tests of Fire Resistance of Building Construction  
and Materials,” 2006 edition.  
$34.50/each  
NFPA 252. “Standard Methods of Fire Tests of Door Assemblies, 2003 edition.”  
$29.00/each  
NFPA 253. “Standard Method of Test for Critical Radiant Flux of Floor Covering  
Systems Using a Radiant Heat Energy Source,” 2006 edition.  
$29.00/each  
NFPA 255. “Standard Method of Test of Surface Burning Characteristics of Building  
Materials,” 2006 edition.  
$29.00/each  
NFPA 256. “Standard Methods of Fire Tests of Roof Coverings,” 2003 edition.  
$29.00/each  
NFPA 257. “Standard on Fire Test for Window and Glass Block Assemblies,” 2000  
edition.  
$29.00/each  
Page 4  
NFPA 259. “Standard Test Method for Potential Heat of Building Materials,” 2003  
edition.  
$29.00/each  
NFPA 260. “Standard Methods of Tests and Classification System for Cigarette  
Ignition Resistance of Components of Upholstered Furniture,” 2003 edition.  
$29.00/each  
NFPA 261. “Standard Method of Test for Determining Resistance of Mock-Up  
Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes,” 2003  
edition.  
$29.00/each  
NFPA 265. “Standard Methods of Fire Tests for Evaluating Room Fire Growth  
Contribution of Textile Coverings on Full Height Panels and Walls,” 2002 edition.  
$34.50/each  
NFPA 286. “Standard Methods of Fire Tests for Evaluating Contribution of Wall and  
Ceiling Interior Finish to Room Fire Growth,” 2006 edition.  
$34.50/each  
NFPA 288. “Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance–Rated Floor Systems,” 2001 edition.  
$29.00/each  
NFPA 415. “Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and  
Loading Walkways,” 2002 edition.  
$29.00/each  
NFPA 418. “Standard for Heliports,” 2001 edition.  
$29.00/each  
NFPA 430. “Code for the Storage of Liquid and Solid Oxidizers,” 2004 edition.  
$34.50/each  
NFPA 432. “Code for the Storage of Organic Peroxide Formulations,” 2002 edition.  
$34.50/each  
NFPA 434. “Code for the Storage of Pesticides,” 2002 edition.  
$29.00/each  
NFPA 701. “Standard Methods of Fire Tests for Flame Propagation of Textiles and  
Films,” 2004 edition.  
$29.00/each  
NFPA 703. “Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings  
for Building Materials,” 2006 edition.  
$29.00/each  
NFPA 750. “Standard on Water Mist Fire Protection Systems, 2003 edition.”  
$38.00/each  
Page 5  
NFPA 914. “Code for Fire Protection of Historic Structures,” 2001 edition.  
$54.00/each  
NFPA 1124. “Code for the Manufacture, Transportation, Storage, and Retail Sales of  
Fireworks and Pyrotechnic Articles,” 2006 edition.  
$38.00/each  
NFPA 1126. “Standard for the Use of Pyrotechnics Before a Proximate Audience,”  
2006 edition.  
$29.00/each  
NFPA 2001. “Standard on Clean Agent Fire Extinguishing Systems,” 2004 edition.  
$44.00/each  
NFPA 5000. “Building Construction and Safety Code,” 2006 edition. References to  
this code mean the Michigan residential code, R 408.30501 to 408.30547, promulgated  
by the Michigan department of energy, labor, and economic growth, bureau of  
construction codes.  
2.3 Other Publications.  
2.3.1 ACI Publication. www.concrete.org American Concrete Institute, P.O. Box  
9094, Farmington Hills, MI 48333. ACI 216.1/TMS 0216.1. “Standard Method for  
Determining Fire Resistance of Concrete and Masonry Construction Assemblies,” 1997.  
$70.50/each  
2.3.2 ANSI Publications.  
American National Standards Institute, Inc., 25 West 43rd Street, 14th floor, New  
York, NY 10036. ANSI A14.3. “Safety Requirements for Fixed Ladders,” 2002.  
$219.00/each  
ICC/ANSI A117.1. “American National Standard for Accessible and Usable  
$35.00/each  
BHMA/ANSI A156.19. “American National Standard for Power Assist and Low  
$40.00/each  
2.3.3 Deleted.  
2.3.4 ASME Publications. www.asme.org  
American Society of Mechanical Engineers  
Three Park Avenue, New York, NY 10016-5990.  
2.3.5 ASTM Publications. www.astm.org  
American Society for Testing and Materials, 100 Barr Harbor Drive, West  
Conshohocken, PA 19428-2959.  
ASTM D 1929. “Standard Test Method for Determining Ignition Temperatures of  
Plastic,” 2001.  
$36.00/each  
ASTM D 2859. “Standard Test Method for Ignition Characteristics of Finished  
Textile Floor Covering Materials,” 2004.  
$37.20/each  
Page 6  
ASTM D 2898. “Standard Test Methods for Accelerated Weathering of Fire-  
Retardant-Treated Wood for Fire Testing,” 1994 (1999).  
$37.20/each  
ASTM E 136. “Standard Test Method for Behavior of Materials in a Vertical Tube  
Furnace at 750°C,” 2004.  
$36.00/each  
ASTM E 814. “Standard Test Method for Fire Tests of Through Penetration Fire  
Stops,” 2002.  
$43.20/each  
ASTM E 1966. “Standard Test Method for Fire-Resistive Joint Systems,” 2001.  
$50.40/each  
ASTM E 2074. “Standard Test Method for Fire Tests of Door Assemblies, Including  
Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies,”  
2000e1.  
$50.40/each  
2.3.6 FMGR Publication.  
FM Global Research, FM Global, 1301 Atwood Avenue, P.O. Box 7500, Johnston,  
RI 02919.  
FM 4880. “Approval Standard for Class I Insulated Wall or Wall and Roof/Ceiling  
Panels; Plastic Interior Finish Materials; Plastic Exterior Building Panels; Wall/Ceiling  
Coating Systems; Interior or Exterior Finish Systems,” 1994. Free PDF download online  
200.com per UL website. (All revisions included in purchase of standard) Underwriters  
Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.  
UL 555. “Standard for Fire Dampers,” 1999, Revised 2002.  
$974.00 per  
hard copy/$779.00 per PDF copy  
UL 555S. “Standard for Smoke Dampers,” 1999, Revised 2003.  
$248.00/each  
UL 924. “Standard for Emergency Lighting and Power Equipment,” 1995, Revised  
2001.  
$974.00 per hard copy/$779.00 per PDF copy  
UL 1040. “Standard for Fire Test of Insulated Wall Construction,” 1996.  
$490.00 per  
hard copy / $392.00 PDF copy  
UL 1715. “Standard for Fire Test of Interior Finish Material,” 1997.  
$875.00 per hard copy / $699.00 per  
PDF copy  
UL 1975. “Standard for Fire Tests for Foamed Plastics Used for Decorative  
Purposes,” 1996.  
$974.00 per hard  
copy/$779.00 per PDF copy  
2.3.8 U.S. Government publication. www.gpoaccess.gov/CFR  
U.S. Government Printing Office, Washington, DC 20402.  
Page 7  
Title 16. “Code of Federal Regulations, Part 1632, Standard for the Flammability of  
Mattresses and Mattress Pads.”  
$63.00/each  
2.3.9 Other Publication.  
“Merriam-Webster's Collegiate Dictionary,” 11th edition, Merriam-Webster, Inc.,  
2.4 References for rxtracts in mandatory sections.  
NFPA 1. “Uniform Fire Code ,” 2006 edition.  
NFPA 72®. “National Fire Alarm Code®,” 2002 edition.  
$54.00/each  
$26.95/each  
$72.00/each  
NFPA 80. “Standard for Fire Doors and Fire Windows,” 1999 edition.  
$38.00/each  
NFPA 88A. “Standard for Parking Structures,” 2002 edition.  
$29.00/each  
NFPA 101B. “Code for Means of Egress for Buildings and Structures,” 2002 edition.  
$44.00/each  
NFPA 102. “Standard for Grandstands, Folding and Telescopic Seating, Tents, and  
Membrane Structures,” 1995 edition.  
$29.00/each  
NFPA 288. “Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance–Rated Floor Systems,” 2001 edition.  
$29.00/each  
NFPA 301. “Code for Safety to Life from Fire on Merchant Vessels,” 2001 edition.  
$8.00/each  
NFPA 415. “Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and  
Loading Walkways,” 2002 edition.  
$29.00/each  
NFPA 914. “Code for Fire Protection of Historic Structures,” 2001 edition.  
$54.00/each  
NFPA 921. “Guide for Fire and Explosion Investigations,” 2004 edition.  
$72.00/each  
(4) Rules pertaining to flammable and combustible liquid handing referenced in  
8.7.3.1. of the code are available for inspection from the bureau of fire services as  
identified in subrule (2) of this rule, and are promulgated by and also available from the  
Michigan department of environmental quality storage tank unit by calling (517) 335-  
code.”  
(5) Rules pertaining to the Michigan elevator code, Michigan mechanical code, the  
Michigan building code, Michigan electrical code, and Michigan plumbing code are  
available for inspection at the Okemos office of the bureau of construction codes. Copies  
of these rules are available from the Michigan government website,  
Page 8  
Michigan Department of Energy, Labor, & Economic Growth, Bureau of Construction  
Codes, 2501 Woodlake Circle, Okemos, Michigan 48864.  
mm) from the building, between the building and a point 6 feet (1,829 mm) from  
the building.  
(j) "Interconnected" means that the entire fire detection system is connected  
together so that, when 1 detection device is activated, a general alarm will sound  
which shall be audible in all habitable areas.  
(k) "Licensee" means the agency, association, corporation, organization, person, or  
department or agency of the state, county, city, or other political subdivision that  
has been issued a license to operate an adult foster care facility.  
(l) "Listed" means the material listed by an approved independent nationally  
recognized testing laboratory acceptable to the state fire marshal.  
(m) "New" means a facility licensed after the effective date of these rules.  
(n) "Story above grade" means any story that has its finished floor surface  
entirely above grade, except that a basement shall be considered as a story above grade  
when the distance from grade to the finished surface of the floor above the  
basement is more than 6 feet (1,829 mm) for more than 50% of the total perimeter or  
more than 12 feet (3,658 mm) at any point.  
(o) "Twin-twenty" means 2 20-bed facilities that are attached or located inside the  
same building, separated from each other by not less than a 2-hour fire wall.  
(p) "Usable floor space" means floor space under a ceiling not less than 6 feet 6  
inches in height, excluding closets.  
History: 1994 AACS; 2012 AACS.  
R 400.18103 Definitions.  
Rule 103. As used in these rules for new and existing adult foster care facilities and  
congregate facilities licensed for 7 or more adults:  
(a) "Act" means 1979 PA 218, MCL 400.701 to 400.737  
(b) "Adult foster care facility" has the same meaning as defined in the act.  
(c) "Approved" means acceptable to the bureau of fire services, unless specifically  
indicated otherwise in these rules.  
(d) "Authority having jurisdiction" means the bureau of fire services, an employee of the  
bureau of fire services, or an employee of a city, village, or township delegated to enforce  
the code under section 2b of the act.  
(e) "Code" means national fire protection association standard no. 101, 2006 edition,  
entitled “life safety code.”  
(f) “Congregate facility” means an adult foster care facility with the approved capacity  
to receive more than 20 adults for foster care.  
(g) "Conversion" means either of the following:  
(i) To change the license category for an existing facility.  
(ii) To change the purpose for which a building, a room, or an area is designed.  
(h) “Cosmetic remodeling” means surface changes made solely to the wall, floor, or  
ceiling, that do not decrease the fire rating of the wall, floor, or ceiling, including the  
replacement of windows and doors.  
(i) "Department" means the Michigan department of licensing and regulatory affairs.  
Page 9  
(j) “Evacuation capability” means the ability of residents, occupants, and staff, as a  
group, to evacuate the adult foster care facility. Evacuation capability may be classified  
as “prompt,” “slow,” or “impractical.”  
(k) "Existing facility" means a facility that was licensed before the effective date of  
these rules or a change in facility ownership without a conversion of the facility.  
(l) "Grade" means a reference plane that represents the average of finished ground level  
adjoining the building at all exterior walls. When the finished ground level slopes away  
from the exterior walls, the reference plane shall be established by the lowest points  
within the area between the building and the lot line or, when the lot line is more than 6  
feet (1,829 mm) from the building, between the building and a point 6 feet (1,829 mm)  
from the building.  
(m) “Impractical” means that a facility’s evacuation capability is such that the facility  
cannot be evacuated in less than 8 minutes.  
(n) "Interconnected" means that the entire fire alarm system is connected together so  
that, when 1 alarm device is activated, a general alarm will sound which shall be audible  
in all habitable areas.  
(o) "Licensee" means the agency, association, corporation, company, organization,  
person or persons, or department or agency of the state, county, city, or other political  
subdivision that has been issued a license to operate an adult foster care facility.  
(p) "Listed" means the material listed by an approved independent nationally recognized  
testing laboratory acceptable to the bureau of fire services.  
(q) “Large facility” means an adult foster care facility with the approved capacity to  
receive at least 13 but not more than 20 adults for foster care.  
(r) “Maintenance” means repair that is required to keep the building and its component  
parts in an operative condition at all times. “Maintenance” includes the replacement of a  
building’s components when, for any reason, they become undependable or inoperable,  
but does not include remodeling.  
(s) "New" means a facility licensed after the effective date of these rules or a facility  
licensed before the effective date of the rules that changes license category.  
(t) “Prompt” means that a facility’s evacuation capability is such that the facility can be  
evacuated in 3 minutes or less.  
(u) “Remodeling” means an alteration or change of fire-rated assembly, or the  
installation of new equipment required by these rules.  
(v) "Resident" means a person who is receiving adult foster care and resides in an adult  
foster care facility.  
(w) “Slow” means that a facility’s evacuation capability is such that the facility can be  
evacuated in less than 8 minutes, but more than 3 minutes.  
(x) “Small facility” means an adult foster care facility with the approved capacity to  
receive at least 7 but not more than 12 adults for foster care.  
(y) "Story above grade" means any story that has its finished floor surface entirely  
above grade, except that a basement shall be considered as a story above grade when the  
distance from grade to the finished surface of the floor above the basement is more than 6  
feet (1,829 mm) for more than 50% of the total perimeter.  
(z) "Twin-twenty" means 2 20-bed facilities that are attached or located inside the same  
building, separated from each other by not less than a 2-hour fire wall.  
Page 10  
(aa) "Usable floor space" means floor space under a ceiling not less than 6 feet 6 inches  
in height, excluding closets.  
History: 1994 AACS; 2012 AACS.  
R 400.18104 Plans and specifications.  
Rule 104. (1) A registered architect or engineer shall submit plans and specifications to  
the bureau of fire services for all projects that involve construction, additions,  
remodeling, or conversions.  
(2) An adult foster care facility is not required to submit plans and specifications for  
routine maintenance functions or cosmetic remodeling, subject to both of the following:  
(a) An adult foster care facility shall ensure that all work is in compliance with these  
rules.  
(b) Cosmetic remodeling shall not diminish the fire safety of any features being  
replaced.  
(3) Plans and specifications for construction, remodeling, or an addition that involves  
the practices of architecture or engineering, as defined by the provisions of PA 299, MCL  
339.101 to 339.2919, known as the occupational code, shall bear the seal of an architect  
or engineer who is registered pursuant to 1980 PA 299, MCL 339.101 to 339.2919.  
(4) Plans and specifications shall contain all of the following information, as applicable:  
(a) Complete floor plan and layout of the building drawn accurately to scale.  
(b) Use of each room.  
(c) Dimensions of each room.  
(d) Size, location, direction of swing, and fire rating of each door and frame assembly.  
(e) Size and location of windows.  
(f) Wall construction, including fire-resistance rating.  
(g) Type of construction as identified in the “Standards on types of building  
construction,” referenced in Chapter 2 of the life safety code which is adopted by  
reference in R 400.18102.  
(h) Number of stories, including basement and attic areas.  
(i) Interior finish classification.  
(j) Location of fuel-fired equipment.  
(k) Type of furnace and water heater.  
(l) Air-handling system specifications.  
(m) Fire detection and alarm system plans and specifications that are in compliance with  
the fire prevention code, 1941 PA 207, MCL 29.1. to 29.34.  
(n) Sprinkler or other suppression system plans and specifications that are in compliance  
with the fire prevention code, 1941 PA 207, MCL 29.1 to 29.34.  
(o) Type, size, and location of fire extinguishers.  
(p) Other pertinent information that is required to determine compliance with these  
rules.  
(5) Plan approval that is given before the effective date of these rules shall terminate 6  
months after the effective date of these rules if construction has not started.  
History: 1994 AACS; 2012 AACS.  
Page 11  
R 400.18105 Inspections during construction; approval for occupancy.  
Rule 105. (1) During construction, additions, remodeling, or conversions: the architect,  
professional engineer, or construction manager shall notify the bureau of fire services, in  
writing, that the building is ready for inspection at both of the following times:  
(a) When the building is framed and mechanical systems are substantially complete, but  
before concealment.  
(b) When construction is completed.  
(2) A person shall not occupy a newly constructed facility or a facility that is being  
remodeled or added to, in whole or in part, unless approved by the bureau of fire services  
and unless licensed by the department of human services, bureau of children and adult  
licensing  
History: 1994 AACS; 2012 AACS.  
R 400.18106 Projects affecting outside configuration of building, site plan and  
specifications; bureau of fire services or local fire authority specifications; fire  
safety measures during construction.  
Rule 106. (1) Before construction begins for projects that involve construction, addition,  
or remodeling that affects the outside configuration of a building, and as part of the  
building plans and specifications otherwise required by these rules, the licensee’s or  
licensee applicant’s designated architect, engineer or construction manager shall provide  
the bureau of fire services and the local fire authority with a site plan and specifications  
that detail all of the following:  
(a) The available water supply.  
(b) Hydrant locations.  
(c) Vehicle access routes.  
(d) Fire lanes.  
(2) The bureau of fire services or local fire authority may specify any of the following:  
(a) The size of the water mains that supply the hydrants.  
(b) The location of hydrants.  
(c) The locations and dimensions of fire department vehicle access routes.  
(d) The posting of fire lanes.  
(3) As soon as possible during construction, the adult foster care facility shall ensure  
that appropriate fire safety measures shall be taken, including the provision of fire  
extinguishers and fire suppression systems and the establishment of access routes to the  
building that can be traveled by fire department vehicles.  
History: 1994 AACS; 2012 AACS.  
R 400.18107 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 12  
R 400.18108 Universal amendments to code.  
Rule 108. Sections 4.6.10.1, 7.1.10.1, 8.7.3.1, 3.3.65.1, 9.1.1, 9.1.2, 9.4.2.1, and section  
10.2.6.1 of the code, which is adopted by reference in rule 102 of these rules, are  
amended; sections 7.1.7.2.5, 7.2.1.8.1.1, 9.1.1.1, 9.1.1.2, 9.1.1.3, 9.1.1.4, 9.1.2.1, and  
9.1.2.2 are added, and 3.2.1, 3.2.2, 3.2.3, 3.2.5, 9.4.2.2, 9.4.3, 9.4.4, 9.4.5, 9.4.6, and 9.4.7  
are deleted to read as follows:  
3.2.1 Deleted.  
3.2.2 Deleted.  
3.2.3 Deleted.  
3.2.5 Deleted.  
4.6.10.1 A person may occupy a building or portions of a building during construction,  
repair, alterations, or additions only if all means of egress and all fire protection features  
in the building and on site are in place and continuously maintained for the part occupied  
and if the occupied portion is separated from the part under construction by a wall that  
has a 1-hour-fire-resistance rating. The temporary 1-hour fire-resistive rated wall that is  
used for this purpose may be constructed of combustible material. Instead of having all  
means of egress and fire protection features in place, the adult foster care facility may  
take other measures that would provide equivalent safety if approved by the bureau of  
fire services. An adult foster care facility or any of its parts shall not be occupied, in  
whole or in part, without approval from the bureau of fire services, and the Michigan  
department of human services, bureau of children and adult licensing.  
7.1.7.2.5. Facilities housing residents, who regularly require wheelchairs, shall be  
equipped with ramps located at the required means of escape. Ramps shall be in  
compliance with section 7.2.5 of the code.  
7.1.10.1 Means of egress shall be continuously maintained free of all obstructions or  
impediments to full instant use in the case of fire or other emergency. Seasonal  
obstructions such as ice and snow shall not impede safe passage away from the facility to  
a point of safety.  
7.2.1.8.1.1 A door required to be equipped with a self-closing device shall be positive-  
latching upon closure.  
8.2.1.3 Where the building or facility includes additions or connected structures of  
different construction types, all of the following shall apply:  
(a) The rating and classification of the structure shall be based on 1 of the following:  
(i) Separate buildings, if a 2-hour or greater vertically aligned fire barrier wall in  
accordance with NFPA 221, Standard for Fire Walls and Fire Barrier Walls, exists  
between the portions of the building.  
(ii) Separate buildings, if provided with previously approved separations.  
(iii) Least fire-resistive type of construction of the connected portions, if separation as  
specified in paragraph (i) or (ii) of this subdivision is not provided.  
(b) Each proposed facility shall be inspected and licensed independently.  
(c) Each facility shall have a distinct living area, dining area, sleeping area and  
multipurpose area, sized accordingly.  
(d) Each facility may share common services such as laundry, kitchen and heating  
plants.  
Page 13  
8.7.3.1 The adult foster care facility shall store flammable and combustible liquids in  
compliance with R 29.5101 to R 29.5516 promulgated by the Michigan department of  
environmental quality under the act.  
9.1.1 Gas. Equipment using gas and related gas piping shall be in accordance with the  
following requirements:  
9.1.1.3 The installation, use, and maintenance of a gas appliance and gas piping shall be  
in accordance with the provisions of NFPA 54, national fuel gas code, which is adopted  
by reference in R 400.18102.  
9.1.1.4 A liquefied petroleum gas installation shall be in compliance with R_29.6001 to  
R_29.6097 promulgated under the act. When a gas supply line is placed in a tunnel, it  
shall be installed without joints and the tunnel shall have forced ventilation.  
9.1.2 Electrical systems.  
9.1.2.1 The adult foster care facility or designated representative shall ensure that the  
electrical wiring and equipment, including an emergency electrical supply if installed, is  
installed in compliance with the provisions of the NFPA 70, as adopted in Chapter 2.2, as  
amended by and available as specified in R 400.18102.  
9.1.2.2 Electrical inspection shall be made by an electrical inspection authority  
acceptable to the bureau of fire services. The authority shall issue a final approval  
certificate of compliance covering the installation.  
9.4.2.1 The adult foster care facility shall ensure that new and existing elevators,  
escalators, dumbwaiters, and moving walks shall be installed in compliance with R  
408.7001 to R 408.8695.  
9.4.2.2 Deleted.  
9.4.3 Deleted.  
9.4.4 Deleted  
9.4.5 Deleted.  
9.4.6 Deleted.  
9.4.7 Deleted.  
10.2.6.1 The required flame spread or smoke developed classification of surfaces of  
walls, partitions, columns, and ceilings shall not be attained by applying approved fire  
retardant coatings to surfaces that have a higher flame spread rating than permitted.  
Applications approved prior to the effective date of these rules shall be maintained in  
accordance with section 10.2.6.2.  
History: 1994 AACS; 2012 AACS.  
R 400.18109 Fire reporting.  
Rule 109. After the occurrence of a fire, the adult foster care licensee shall immediately  
notify the local fire department and the bureau of fire services with all details of the fire.  
History: 1994 AACS; 2012 AACS.  
R 400.18110 Fire alarm system requirements.  
Rule 110. The adult foster care licensee or designated representative shall ensure that  
the installation, modification, testing, servicing, inspection, or maintenance of a fire  
Page 14  
alarm or fire suppression system required by these rules shall be in compliance with 1941  
PA 207, MCL 29.1 to MCL 29.34.  
History: 1994 AACS; 2012 AACS.  
R 400.18111 Aid for emergency services.  
Rule 111. Every facility shall have the address number displayed in a position easily  
observed and readable from the public right-of-way. All numbers shall be in Arabic  
numerals at least 3 inches (76 mm) high and ½ inch (13 mm) stroke minimum  
History: 1994 AACS; 2012 AACS.  
PART 2. NEW SMALL AND LARGE ADULT FOSTER CARE FACILITIES  
R 400.18201 Application; amendments to chapter 32 of the code.  
Rule 201. Sections 32.1.1.3, 32.1.1.6.3, 32.1.3, 32.2.1.1.1, 32.2.1.1.2, 32.2.1.2,  
32.2.2.5.1, 32.2.2.5.2, 32.2.2.5.5.1, 32.2.3.1.2, 32.2.3.2, 32.2.3.4.3, 32.2.3.4.3.1,  
32.2.3.4.3.2, 32.2.3.4.3.3, 32.2.3.4.3.4, 32.2.3.5.1, 32.3.1.1.1, 32.3.1.1.2, 32.3.1.3,  
32.3.2.2.2, 32.3.2.11.2, 32.3.3.4.2, 32.3.3.4.8, 32.3.3.4.8.1, 32.3.3.4.8.2, 32.3.3.4.8.3,  
3.2.4, 32.7.1.1, 32.7.1.2, 32.7.3.1, and 32.7.6 of the code are amended, sections  
32.2.2.6.4, 32.2.3.2.3.1, 32.2.3.2.6, 32.2.3.2.7, 32.2.5.2.4, 32.3.2.2.3.1, 32.3.3.2.3,  
32.3.3.2.4, 32.3.3.4.8.4, 32.3.6.2.4, 32.3.6.2.5, 32.5, 32.6, 32.6.1, 32.6.2, 32.7.1.1.1,  
32.7.4.1, 32.7.5, and 32.7.5.3, 32.7.4.1.1, 32.7.4.3, 32.7.5.1.1, 32.7.5.2.2, 32.7.5.3, and  
32.7.5.3.2 are added, and sections 32.1.1.4, 32.2.2.5.1.2, 32.2.2.6.2, 32.2.3.1.5,  
32.2.3.2.1, 32.2.3.2.2, 32.2.3.5.2, 32.3.2.2.10, 32.3.3.4.7, 32.4.1, 32.4.1.1, 32.4.1.1.2,  
32.4.1.1.3, 32.4.1.1.4, 32.4.1.2, 32.4.1.3, 32.4.1.4, 32.4.1.4.1, 32.4.1.4.2, 32.4.2.1,  
32.4.2.2, 32.4.3, 32.4.3.1, 32.4.3.1.1, 32.4.3.1.2, 32.4.3.2, 32.4.3.2.1, 32.4.3.2.2, 32.4.3,  
32.4.3.1, 32.4.3.1.1, 32.4.3.1.2, 32.4.3.2, 32.4.3.2.1, 32.4.3.2.2, 32.4.3.3, 32.7.2.4,  
32.7.3.5, and 32.7.3.6 are deleted to read as follows:  
General Requirements  
32.1.1.3 Chapter Sections. This chapter is divided into 7 sections as follows:  
(1) Section 32.1 — General Requirements  
(2) Section 32.2 — Small facilities (7-12 residents)  
(3) Section 32.3 — Large facilities (13 to 20 residents)  
(4) Section 32.4 — Apartments  
(5) Section 32.5 — Miscellaneous  
(6) Section 32.6 — Basements  
(7) Section 32.7 — Operating features  
(1) General Requirements  
Page 15  
32.1.1.4 Conversions. For the purposes of this chapter, exceptions for conversions shall  
apply only for a change of occupancy from an existing residential or health care  
occupancy to an adult foster care facility. A change of licensee does not change the  
status of an existing facility to “new” if the new license application is made not later than  
60 days of the previous license expiration date and the license category has not been  
changed, except as provided in MCL 400.721.  
32.1.3 Definitions. The following are terms used in this chapter:  
(1) Personal care. See 3.3.181.  
(2) Point of safety. See 3.3.186.  
(3) Residential board and care facility means an adult foster facility licensed by the  
Michigan department of human services.  
(4) Residential board and care occupancy means a building or portion thereof that is  
used for lodging and boarding of 7 to 20 residents for the purpose of providing personal  
care services. See R 400.18103 for definitions of small and large facilities.  
(5) Residential board and care resident means a person who is receiving adult foster care  
and resides in an adult foster care facility.  
(6) Staff (residential board and care). See 3.3.232.  
(7) Thermal barrier. See 3.3.24.3.  
(2) Small Facilities  
32.2.1.1.1 Section 32.2 applies to adult foster care facilities that provide adult foster care  
for small facilities that house 7 to 12 residents.  
32.2.1.1.2 Where there are sleeping accommodations for 13 to 20 residents, the  
occupancy shall be classified as a large adult foster care facility in accordance with  
section 32.3.  
32.2.1.2 Requirements based upon evacuation capabilities shall comply with  
“impractical,” “prompt,” and “slow,” as defined in Rule 103 of these rules.  
32.2.2.5.1 A door opening to a means of escape shall not be less than 32 inches (81 cm)  
clear width.  
32.2.2.5.1.2 Deleted.  
32.2.2.5.2 Means of escape doors shall be swinging.  
32.2.2.5.5.1 Delayed-egress locks complying with 7.2.1.6.1 shall be permitted for exit  
doors only.  
32.2.2.6.2 Deleted.  
32.2.2.6.4 Exterior stairs used as a means of escape, that exceed a vertical distance from  
grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with 1-hour rated fire barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
32.2.3.1.2 Vertical openings shall be separated by smoke partitions in accordance with  
section 8.4 that resist the passage of smoke from 1 story to another story.  
32.2.3.1.5 Deleted.  
32.2.3.2 Protection from hazards.  
_______________________________________________________________________  
Page 16  
Hazardous Area Description  
Separation/Protection____________  
Boiler and fuel-fired heater rooms 1 hour  
Central/bulk laundries larger than 100 ft2 (9.3 m2) 1 hour  
paint shops employing hazardous substances and 1 hour  
materials in quantities less than those that would  
be classified as a severe hazard  
Physical plant maintenance shops  
Soiled linen rooms  
1 hour  
1 hour  
Storage rooms larger than 50 ft2 (4.6 m2), but not  
exceeding 100 ft2 (9.3 m2), storing combustible  
material  
Smoke partition  
Trash collection rooms  
1 hour  
32.2.3.2.1 Deleted.  
32.2.3.2.2 Deleted.  
32.2.3.2.6 Oxygen storage  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, which is adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
32.2.3.2.7 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive-rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
32.2.3.4.3 Smoke detectors.  
32.2.3.4.3.1 Approved smoke detectors shall be provided in accordance with 9.6.1.3.  
32.2.3.4.3.2 Smoke detectors shall be installed on all levels, including basements but  
excluding crawl spaces and unfinished attics.  
32.2.3.4.3.3 Additional smoke detectors shall be installed in all living areas, as defined  
in 3.3.17.5.  
32.2.3.4.3.4 Each sleeping room shall be provided with an approved smoke detector.  
Page 17  
32.2.3.5.1 All facilities shall be protected throughout by an approved automatic  
sprinkler system, installed in accordance with 32.2.3.5.3, using quick-response or  
residential sprinklers.  
32.2.3.5.2 Deleted.  
32.2.5.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
32.2.5.2.5 Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA  
pamphlet # 211, which is adopted by reference in 2.1 of the code, as amended by R  
400.18102.  
(3) Large Facilities  
32.3.1.1.1 Section 32.3 applies to adult foster care facilities that provide adult foster care  
for large facilities that house 13 to 20 residents.  
32.3.1.1.2 Where there are sleeping accommodations for 7 to 12 residents, the  
occupancy shall be classified as a small adult foster care facility in accordance with  
Section 32.2.  
32.3.1.3 Minimum construction requirements. Building construction requirements are  
under the authority of the Michigan construction code, administered by the bureau of  
construction codes, as provided in amendments to section 2.1 of the code in R 400.18102.  
32.3.2 Means of egress.  
32.3.2.2.2 Doors. Doors in means of egress shall be as follows:  
(1) Doors complying with 7.2.1 shall be permitted.  
(2) Doors within individual rooms and suites of rooms may be swinging.  
(3) Door, other than those meeting the requirement of 32.3.2.2.2(4) or (5) shall be not be  
equipped with a lock or latch that requires the use of a tool or key from the egress side.  
(4) Delayed-egress locks in accordance with 7.2.1.6.1 shall be permitted, provided that  
not more than 1 device is located in any egress path.  
(5) Access controlled egress doors in accordance with 7.2.1.6.2 shall be permitted,  
provided that not more than 1 device is located in any egress path.  
(6) Doors located in the means of egress that are permitted to be locked under other  
provisions of chapter 32, other than those meeting the requirement of 32.3.2.2.2(4) or (5),  
shall have adequate provisions made for the rapid removal of occupants by means such as  
remote control of locks, keying of all locks to keys carried by staff at all times, or other  
such reliable means available to staff at all times.  
(7) Only 1 such locking device, as described in 32.3.2.2.2(6) shall be permitted on each  
door.  
32.3.2.2.10 Deleted.  
32.3.2.11.2 Lockups are not permitted.  
32.3.2.2.3.1 Exterior stairs used as a means of egress that exceed a vertical distance  
from grade of more than 4 feet shall be enclosed and separated from the remainder of the  
Page 18  
facility with 1-hour rated fire barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
32.3.3.2.3 Oxygen storage.  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive-rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
32.3.3.2.4 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive-rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
32.3.3.4.2 Initiation. The required fire alarm system shall be initiated by all of the  
following:  
(1) Manual means in accordance with 9.6.2.  
(2) Required automatic sprinkler system.  
(3) Required detection system.  
32.3.3.4.7 Delete.  
32.3.3.4.8 Smoke detection systems.  
32.3.3.4.8.1 Approved smoke detectors shall be provided in accordance with 9.6.1.3.  
32.3.3.4.8.2 Smoke detectors shall be installed on all levels, including basements but  
excluding crawl spaces and unfinished attics.  
32.3.3.4.8.3 Additional smoke detectors shall be installed in all living areas, as defined  
in 3.3.17.5.  
32.3.3.4.8.4 Each sleeping room shall be provided with an approved smoke detector.  
32.3.6.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Page 19  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
32.3.6.2.5. Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA  
pamphlet # 211, which is adopted by reference in 2.1 of the code, as amended by R  
400.18102.  
(4) Apartments  
32.4 An adult foster care facility shall not be located in, or be a part of, an apartment  
building.  
32.4.1 to 32.4.3.3 Deleted.  
(5) Miscellaneous requirements  
32.5.1 Facilities housing persons who use wheelchairs shall be provided with ramps at  
the required means of egress.  
(6) Basements  
32.6.1. A basement shall not be used as a resident bedroom, unless it meets the  
definition of a “story above grade.”  
32.6.2 A basement that is used for resident activities shall have 2 remotely located  
means of escape separated by not less than 50% of the longest dimension of the floor, as  
practical. One of the means of escape shall exit directly to the outside at grade. The  
second means of escape may be the interior stairway that serves the first floor of the  
facility.  
(7) Operating features  
32.7.1.1 The administration of every adult foster care facility shall have in effect and  
available to all personnel, written copies of a plan for protecting all persons in the event  
of fire and for evacuating persons from the building to the designated point of safety.  
The plan shall include special staff response, including the fire protection procedures  
needed to ensure the safety of any resident, and shall be amended or revised whenever  
any resident with unusual needs is identified. All employees shall be periodically  
instructed and kept informed with respect to their duties and responsibilities under the  
plan, including the operation of fire alarm and other fire protection equipment. Such  
instruction shall be reviewed by the staff not less than every 2 months. A copy of the  
plan shall be readily available at all times within the facility. The evacuation plan shall  
include provisions to protect residents who are either permanently or temporarily  
incapable of self-preservation. The evacuation plan shall be evaluated annually to ensure  
that all information is current and correct.  
32.7.1.1.1 The written fire safety plan shall provide for the following:  
(a) Use of alarms.  
(b) Transmission of alarm to fire department.  
Page 20  
(c) Response to alarms.  
(d) Isolation of fire.  
(e) Evacuation of building.  
(f) Closure of bedroom doors and corridor access doors upon exiting.  
(g) Use of fire extinguishers.  
32.7.1.2 The proper protection of adult foster care facility residents shall require the  
prompt and effective response of staff members. The basic response required of staff  
shall include the removal of all occupants directly involved with the fire emergency,  
transmission of an appropriate fire alarm signal to warn other building occupants and  
summon staff, confinement of the effects of the fire by closing doors to isolate the fire  
area, and evacuation of residents as detailed in the fire safety plan.  
32.7.2.4 Deleted.  
32.7.3.1 Emergency egress and relocation drills shall be conducted not less than once  
per quarter per scheduled shift; daytime, 7 a.m. to 3 p.m., evening, 3p.m. to 11 p.m., and  
night, 11 p.m. to 7 a.m.  
32.7.3.5 Deleted.  
32.7.3.6 Deleted.  
32.7.4.1.1 Smoking regulations shall include the following:  
(1) Smoking shall he prohibited in any room, compartment, or area where flammable or  
combustible liquids, combustible gases, or oxygen is used or stored and in any other  
hazardous location. Both of the following also shall apply:  
(a) Signs shall be posted with signs that read “NO SMOKING” or bear the international  
symbol for no smoking. Sign letters shall be not less than 2 inches (5.08 cm) high and ¼  
inch (635 cm) wide stroke.  
(b) In residential board and care facilities where smoking is totally prohibited and signs  
so indicating are placed at all major entrances, secondary signs with language that  
prohibits smoking are not required.  
(2) Smoking by residents classified as not responsible with regard to their ability to  
safely use and dispose of smoking materials shall be prohibited, unless the resident is  
under direct supervision by staff or by a person approved by the administration. In such a  
case, smoking may be permitted.  
(3) Smoking materials shall not be provided to residents nor maintained by residents  
without the approval of the administration.  
(4) Areas where smoking is permitted shall be clearly identified.  
(5) Ashtrays of noncombustible material shall be provided and required to be used in all  
areas where smoking is permitted.  
(6) Self-closing cover devices into which ashtrays may be emptied shall be made  
available to all areas where smoking is permitted, and shall be required to be used.  
32.7.4.3 Smoking shall be permitted in a designated location only. Smoking in resident  
or staff bedrooms or in stairwells, exit corridors, and fire escapes is prohibited.  
32.7.5.1.1 These requirements are applicable only to new draperies, curtains,  
upholstered furniture, and mattresses. The term “new” means unused, normally via  
procurement from the marketplace, either by purchase or donation of items not  
previously used. If a facility purchases contract furniture, then such new, unused  
furniture, whether purchased or received as a donation, is regulated by section 32.7.5.2.  
Page 21  
32.7.5.2.2 Upholstered furniture belonging to residents shall not be required to be tested,  
provided that a smoke alarm is installed in such rooms.  
32.7.5.3 New mattresses within board and care homes shall be tested for rates of heat  
release in accordance with 10.3.4. Mattresses manufactured and sold within the United  
States shall pass testing per 16 CFR 1632 (FF4-72), “Standard for the Flammability of  
Mattresses and Mattress Pads.”  
32.7.5.3.2 Mattresses belonging to residents in sleeping rooms shall not be required to  
be tested, provided that a smoke alarm is installed in such rooms.  
32.7.6 Staff shall be on duty and in the facility at all times when residents are present.  
History: 1994 AACS; 2012 AACS.  
R 400.18202 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18203 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18204 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18205 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18206 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18207 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18208 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 22  
R 400.18209 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18210 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18211 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18212 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18213 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18214 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18215 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18216 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18217 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18218 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 23  
R 400.18219 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18220 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18221 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18222 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18223 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18224 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18225 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18226 Rescinded.  
History: 1994 AACS; 2012 AACS.  
PART 3. EXISTING SMALL AND LARGE ADULT FOSTER CARE  
FACILITIES LICENSED ON  
OR  
BEFORE MARCH 27, 1980; EXISTING SMALL AND LARGE ADULT  
FOSTER CARE FACILITIES  
LICENSED ON OR BEFORE MARCH 27, 1980, AND RELICENSED  
BEFORE JULY 2, 1991  
R 400.18301 Application.  
Page 24  
Rule 301. This part applies to all existing small and large adult foster care facilities  
licensed on or before March 27, 1980, and existing small and large adult foster care  
facilities licensed on or before March 27, 1980, and relicensed before July 2, 1991.  
History: 1994 AACS.  
R 400.18302 Home environment.  
Rule 302. (1) A group home shall be constructed, arranged, and maintained  
to adequately provide for the health, safety, and well-being of occupants.  
(2) All occupied rooms shall be of standard lath and plaster construction or  
equivalent.  
History: 1994 AACS.  
R 400.18303 Living areas.  
Rule 303. Traffic to and from any room shall not be through a resident's bedroom.  
History: 1994 AACS.  
R 400.18304 Bedrooms.  
Rule 304. (1) A room shall not be used as a bedroom where more than 1/2 the  
room height is below grade, except where the ceiling of such portion of a building is  
located 5 feet or more above grade for more than 25% of the perimeter measurement of  
the building. Such acceptable bedrooms shall have 2 acceptable means of egress.  
(2) Bedrooms for residents shall be separated from halls, corridors, and other  
rooms by floor-to-ceiling walls that do not have any openings other than doorways.  
(3) Interior doorways of bedrooms occupied by residents shall be equipped  
with a side-hinged, permanently mounted door equipped with positive-latching  
hardware that will ensure opening of the door by a single motion, such as turning a  
knob or by pressing with normal strength on a latch.  
(4) Residents who have impaired mobility shall not sleep in, or be assigned to,  
bedrooms located above the first or main floor.  
(5) Bedrooms shall have at least 1 window. Bedrooms shall be well-  
ventilated and maintained at a comfortable temperature.  
(6) A single occupancy bedroom shall have not less than 70 square feet of usable  
floor space. Usable floor space is defined as floor space that is under a ceiling which is  
not less than 6 feet 6 inches in height.  
(7) A multioccupancy bedroom shall have not less than 65 square feet of usable  
floor space per bed and a maximum of 4 beds per bedroom. Usable floor space is  
defined as the floor space that is under a ceiling which is not less than 6 feet 6 inches in  
height.  
History: 1994 AACS.  
Page 25  
R 400.18305 Fire safety.  
Rule 305. (1) A group home shall be inspected and approved for fire safety  
before the accommodation of residents and at least annually, except that existing group  
homes shall not be required to remove residents for the purpose of the initial fire  
inspection. To meet these requirements, carpeting shall have been tested pursuant  
to criteria outlined in NFPA-255, ASTM-E-84, or UL-723, have a flame spread of not  
more than 75, and have a smoke development of not more than 200.  
(2) At a minimum, a group home shall be of ordinary construction, light platform  
frame. The home shall have a C classification interior finish or better.  
History: 1994 AACS.  
R 400.18306 Interior finishes and materials.  
Rule 306. (1) The alphabetical classification of finish materials is for flame spread,  
fuel contribution, and smoke development as determined by the tunnel test in  
accordance with the provisions of NFPA-255-1972, ASTM-E-84-1968, or UL-723-  
1971 and grouped as follows:  
Flame Fuel Smoke  
Class Spread Contributed Developed  
A 0-25 0-35 0-50  
B 26-75 36-75 51-125  
C 76-200 76-200 126-200  
(2) The same alphabetical classification is used for  
combustibility  
of  
prefabricated acoustical tile units only, pursuant to  
specifications SS-A-118B-1958.  
the  
provisions of federal  
(3) The documents referred to in subrules (1) and (2) of this rule may be purchased  
as follows:  
(a) NFPA-255-1972, from the National  
Batterymarch Park, Quincy, Massachusetts 02269, at the cost of 50 cents per page.  
(b) UL-723-1960, from Underwriters Laboratories, Incorporated, 333  
Pfingsten Road, Northbrook, Illinois 60662, at a cost of 20 cents per page.  
Fire  
Protection  
Association,  
(c) SS-A-118B-1958, from the State Fire Safety Board, 7150 Harris Drive,  
Lansing, Michigan 48913.  
(4) Paper, cardboard, asphalt paper, or other highly flammable material shall not  
be used for the interior finish of a group home.  
(5) Group homes accommodating 13 or more residents shall have  
a
complete, 100% coverage, underwriters laboratories-approved automatic fire detection  
system, including at least 1 manual pull station per floor level and basement, except in  
group homes protected completely with an approved automatic sprinkler system. A fire  
alarm detection system shall be a closed circuit, self-supervised, continuous-ringing  
system.  
History: 1994 AACS.  
Page 26  
R 400.18307 Smoke detection system.  
Rule 307. Sections 23-2.3.4.2 and 23-2.3.4.3 of the code are amended to read as  
follows:  
23-2.3.4.2. For small facilities, approved smoke detectors shall be installed in  
compliance with the provisions of national fire protection association pamphlet no.  
74, 1989 edition, standard for the installation, maintenance, and use of household fire  
warning equipment, which is adopted by reference in R 400.18314. Smoke detectors  
shall be powered from the building electrical system, shall be interconnected, and,  
when activated, shall initiate an alarm that is audible in all habitable areas. Smoke  
detectors shall be installed on all levels, including basements, but excluding crawl  
spaces and unfinished attics. Additional smoke detectors shall be installed for living  
rooms, dens, dayrooms, and similar spaces. A plug-in, cord-connected unit is not  
permitted.  
Exception no. 1: In buildings protected throughout by an approved supervised  
automatic sprinkler system that is in compliance with the provisions of section 23-  
2.3.5 of the code, as amended in R 400.18217, using quick-response or residential  
sprinklers, smoke detection equipment shall be required in compliance with either the  
provisions of this section or section 23-2.3.4.3 of the code, as amended in this part.  
Exception no. 2: Existing battery-powered smoke detectors, rather than building  
electrical service-powered smoke detectors, shall be acceptable where, in the opinion  
of the authority having jurisdiction, the facility has demonstrated testing, maintenance,  
and battery replacement programs that ensure the reliability of power to the  
smoke detectors. This exception shall expire 2 years from the effective date of these  
rules.  
23-2.3.4.3. For small facilities, each sleeping room shall be provided with an  
approved smoke detector that is installed in compliance with the provisions of national  
fire protection association pamphlet no. 74, 1989 edition, standard for the installation,  
maintenance, and use of household fire warning equipment, which is adopted by  
reference in R 400.18314.  
Smoke detectors shall be powered from the building electrical system, shall be  
interconnected, and, when activated, shall initiate an alarm that is audible in all habitable  
areas. A plug-in, cord-connected unit is not permitted.  
Exception no. 1: In buildings protected throughout by an approved supervised  
automatic sprinkler system that is in compliance with the provisions of section 23-  
2.3.5 of the code, as amended in R 400.18217, using quick-response or residential  
sprinklers, smoke detection equipment shall be required in compliance with either the  
provisions of this section or section 23-2.3.4.2 of the code, as amended in this part.  
Exception no. 2: Existing battery-powered detectors, rather than building electrical  
service-powered detectors, shall be acceptable where, in the opinion of the authority  
having jurisdiction, the facility has demonstrated testing, maintenance, and battery  
replacement programs that ensure the reliability of power to the smoke detectors.  
This exception shall expire 2 years from the effective date of these rules.  
History: 1994 AACS.  
R 400.18308 Exits.  
Page 27  
Rule 308. (1) A means of egress shall be considered the entire way and method  
of passage to free and safe ground outside a group home. Means of egress shall be  
maintained in unobstructed, easily traveled condition at all times. Where basements  
are regularly utilized for resident activities, there shall be 2 acceptable means of egress.  
Doors that form a part of a required means of egress shall be equipped with  
positive-latching, nonlocking-against-egress-type hardware, be not less than 30 inches  
in width, and ensure adequate egress for residents who require wheelchairs, including  
ramps where necessary.  
Exception: Special locking requirements complying with 5-2.1.6 are permitted  
if a facility complies with the following conditions:  
(a) The facility is equipped with a complete approved automatic sprinkler  
system in compliance with the provisions of section 7-7 of the code. A small facility  
with a sprinkler system in compliance with national fire protection association  
pamphlet no. 13D, 1991 edition, standard for sprinkler systems in one- and two-family  
dwellings and mobile homes, which is adopted by reference in R 400.18108, with a 30-  
minute water supply, and that has each habitable area and closet sprinklered with  
quick-response or residential sprinklers is also permitted. A large facility with a  
sprinkler system in compliance with national fire protection association pamphlet no.  
13R, 1991 edition, standard for sprinkler systems in residential occupancies up to  
and including 4 stories in height, which is adopted by reference in R 400.18108, and  
that has each habitable area and closet sprinklered with quick-response or residential  
sprinklers is also permitted.  
(b) The facility is equipped with self-closing or automatic closing devices on all  
bedroom doors in compliance with section 5-2.1.8.  
(c) The facility is equipped with a manual fire alarm system in compliance  
with section 7-6.  
(d) The facility is equipped with an approved smoke detection system  
in  
compliance with sections 23-2.3.4.3. Exceptions nos. 1 and 2 of 23-2.3.4.3 shall not be  
used with this exception.  
(2) The first floor of a group home shall have not less than 2 separate and  
independent means of egress leading to the outside. Where basements are regularly  
utilized for resident activities, there shall be 2 acceptable means of egress.  
(3) In homes housing fewer than 13 residents, the second stairway is not required;  
however, the primary stair shall be enclosed with partitions and doors equal in fire  
resistance to the standard partition construction of the building. Such stairway doors  
shall be equipped with approved self-closing devices and positive-latching,  
nonlocking-against-egress-type hardware. The enclosures shall be constructed and  
arranged so that effective fire and smoke separations between floors are provided or  
else each resident bedroom on the second floor or above shall be equipped with a  
minimum 1 3/4-inch thick solid core wood door.  
In homes housing 13 to 20 residents, at least 1 means of egress from each floor  
shall be directly to the outside or shall be through an enclosed stairway which is  
properly separated from exposure from the floor below and which exits directly to the  
outside at grade level.  
The required second means of egress shall be enclosed with partitions and doors  
equal in fire resistance to the standard partition construction of the building. The  
Page 28  
enclosures shall be constructed and arranged so that effective fire and smoke  
separations between floors are provided.  
(4) Group homes accommodating residents  
who  
regularly  
require  
wheelchairs shall be equipped with ramps located at primary and secondary means of  
egress. A ramp shall not exceed 1 foot of rise in 12 feet of run.  
(5) Stairway and other vertical openings shall be enclosed with partitions and  
doors equal in fire resistance to the standard partition construction of the building, if,  
at a minimum, the partition construction is standard lath and plaster or equivalent.  
Enclosures shall be constructed and arranged so that effective fire and smoke  
separations between floors will be effected or else each resident bedroom on the  
second floor or above shall be equipped with a minimum 1 3/4-inch solid core wood  
door.  
(6) Hardware in an occupied room shall be positive-latching and nonlocking-  
against-egress. In all facilities housing more than 12 residents, exterior doors shall  
swing in the direction of egress and be equipped with nonlatching-against-egress-type  
hardware.  
History: 1994 AACS.  
R 400.18309 Heating.  
Rule 309. (1) Except as provided in this rule, occupancies shall be heated by an  
approved heating plant. If the heating plant is located in the basement of a group  
home, standard building material shall suffice for the separation, which shall include at  
least a 1 3/4-inch solid wood core door or equivalent to create a floor separation  
between the basement and the first floor. If the heating plant is on the same level  
with the residents, the furnace room shall be separated from the remainder of the  
building with materials that will afford a minimum 1-hour protection enclosure. A  
permanent outside vent that cannot be closed shall be incorporated in the design of  
heating plant rooms so that adequate air for proper combustion is assured. Space  
heaters are prohibited.  
(2) Factory mutual and underwriters laboratories-approved, permanent, fixed-  
type electrical heating, such as recognized panel or baseboard fixed-type heating,  
may be utilized in any location. Where an American gas association (AGA)-approved  
sealed combustion wall heater has been installed in accordance with both the  
AGA and the manufacturer's recommendations, approval will be given if the unit is  
located on an outside wall, obtains combustion air directly from the outside, and  
vents products of combustion directly to the outside.  
(3) Flame-producing water heaters or incinerators shall be installed with the  
same protection as a heating plant.  
(4) The storage of combustible materials is prohibited in rooms containing  
the heating plant, water heater, or incinerator.  
History: 1994 AACS.  
R 400.18310 Fire extinguishers.  
Page 29  
Rule 310. A minimum of 1 5-pound multipurpose fire extinguisher or  
equivalent shall be provided for use in a group home on each occupied floor and in  
the basement.  
History: 1994 AACS.  
R 400.18311 Electrical service.  
Rule 311. Electrical service shall be maintained in a safe condition.  
Where conditions indicate a need for inspection, the electrical service shall be  
inspected by a qualified electrical inspection service and a copy of the inspection report  
shall be submitted to the department or its agents.  
History: 1994 AACS.  
R 400.18312 General safety.  
Rule 312. (1) Stairways shall have sturdy and securely fastened handrails  
that are not less than 30 inches, nor more than 34 inches, above the upper surface of the  
tread. Exterior stairways and porches shall have handrails on the open sides.  
(2) Scatter or throw rugs on hard finished floors shall have a nonskid backing.  
(3) Handrails and nonskid surfacing or strips shall be installed in showers and  
bath areas.  
(4) Sidewalks, fire escape routes, and entrances shall be kept free of any hazard,  
such as ice, snow, and debris.  
(5) Cooking appliances shall be suitably installed in accordance with approved  
safety practices. Where metal hoods or canopies are provided, they shall be equipped  
with filters that shall be maintained in an efficient condition and kept clean at all  
times.  
(6) A yard area shall be kept free from all hazards, nuisances, refuse, and litter.  
History: 1994 AACS.  
R 400.18313 Emergency preparedness.  
Rule 313. (1) A group home shall have a telephone. A group home shall have a  
written procedure to be followed in case of fire or medical emergency.  
Responsible employees and residents, to the best of their ability, shall be familiar  
with emergency planning and their responsibilities.  
(2) An emergency plan shall specify all of the following:  
(a) The persons to be notified.  
(b) The locations of alarm signals and fire extinguishers.  
(c) Evacuation routes.  
(d) Procedures for evacuating residents of limited mobility and visitors.  
(3) An emergency plan shall provide for not less than 4 fire drills per year.  
Page 30  
(4) The emergency plan, including appropriate telephone numbers, shall be  
prominently posted and made fully known to all residents and responsible  
persons and shall be reviewed annually.  
(5) Staff shall be trained to perform assigned tasks and be familiar with all fire  
fighting equipment.  
(6) Fire drills shall be conducted quarterly and a record of their performance  
shall be maintained. Evacuation planning shall include the possibility of the  
nighttime movement of patients.  
History: 1994 AACS.  
R 400.18314 Standards and codes adoption.  
Rule 314. The standards and codes specified in this rule are adopted by reference  
in these rules for existing small and large adult foster care facilities licensed on or  
before March 27, 1980, and existing small and large adult foster care facilities  
licensed on or before March 27, 1980, and relicensed before July 2, 1991. Copies of  
the adopted standards are available for inspection and distribution at the office of the  
State Fire Safety Board, Michigan Department of State Police Fire Marshal Division,  
7150 Harris Drive, Lansing, Michigan 48913. National Fire Protection Association  
documents are available from their offices at 1 Batterymarch Park, P.O. Box 9101,  
Quincy, Massachusetts  
02269-9101,  
telephone  
number 1-800-344-3555.  
Underwriters Laboratories, Inc., documents are available at 207 E. Ohio Street,  
Chicago, Illinois 60611. The costs of the standards as of the time of adoption of these  
rules are as indicated:  
Accident, Automotive and Burglary Protection Equipment Lists.  
Underwriters Laboratories, Inc., 1972 edition. Cost: $1.00.  
Directory--Part I Building Material List. Underwriters Laboratories, Inc.,  
January 1973. Cost: $2.00.  
Fire Protection Equipment List, Underwriters Laboratories.  
NFPA 10, 1972 edition, entitled "Portable Fire Extinguishers." Cost: 50 cents per  
page.  
NFPA 13, 1972 edition, entitled "Installation of Sprinkler Systems." Cost: 50  
cents per page.  
NFPA 14, 1971 edition, entitled "Standpipe and Hose Systems." Cost: 50 cents  
per page.  
NFPA 72A, 72B and 72D, 1972 edition, entitled "Proprietary, Auxiliary and  
Local Protective Signaling Systems." Cost: 50 cents per page.  
NFPA 74, 1989 edition, entitled "Standard for the Installation, Maintenance,  
and Use of Household Fire Warning Equipment." Cost: 50 cents per page.  
NFPA 82, 1972 edition, entitled "Incinerators, Rubbish Handling." Cost:  
50 cents per page.  
National Electric Code, 1971 edition, National Fire Protection Association.  
Cost: 50 cents per page.  
NFPA 90A, 1972 edition, entitled "Air Conditioning and Ventilating  
Systems." Cost: 50 cents per page.  
Page 31  
State of Michigan Fire Damper Clarification, 1972, Five Cities Association,  
Jackson, Michigan 49204. Cost: Single copy free.  
Uniform State Specification for Fire Escapes, Michigan Department of State  
Police, Fire Marshal Division, 7150 Harris Drive, Lansing, Michigan 48913.  
History: 1994 AACS.  
PART 4. EXISTING SMALL AND LARGE ADULT FOSTER CARE  
FACILITIES LICENSED  
AFTER MARCH 27, 1980  
R 400.18401 Application.  
Rule 401. Chapter 33, adopted by reference in Rule 102 of these rules is amended as  
follows: Sections 33.1.1.3, 33.1.1.4, 33.2.2.5.2, 33.2.2.5.5.1, 33.2.3.2, 33.2.3.2.2,  
33.2.3.2.3, 33.2.3.6.4, 33.3.1.1.1, 33.3.1.1.2, 33.3.2.2.2, 33.3.2.3.4, 33.3.3.3, 33.3.3.4.2,  
33.3.3.5.1.1, 33.6, 33.7.1.1, 33.7.1.2, 33.7.3.1, 33.7.5, 33.7.5.1, 33.7.5.2.1, 33.7.5.2.2,  
33.7.5.3, and 33.7.6 are amended, 33.2.2.6.4, 33.2.3.2.6, 33.2.3.2.7, 33.2.5.2.4,  
33.2.5.2.5, 33.3.2.2.3.1, 33.3.3.2.3, 33.3.3.2.4, 33.3.3.2.5, 33.3.3.2.6, 33.3.3.4.8.4, 33.6.1,  
33.6.2, 33.7.1.1, 33.7.1.1.1, 33.7.4.1.1, and 33.7.4.3 are added, and 33.2.3.6.1.4,  
33.3.2.3.3, 33.3.3.4.7, 33.3.3.4.8.2, 33.3.3.6.6.1, 33.7.2.4, 33.7.3.5, 33.7.3.6, and  
33.7.5.3.2 are deleted from this chapter as follows:  
(1) General requirements  
33.1.1.3. Chapter Sections. This chapter is divided into 5 sections as follows:  
(1) Section 33.1 — General Requirements  
(2) Section 33.2 — Small facilities (7-12 residents)  
(3) Section 33.3 — Large facilities (13 to 20 residents)  
(4) Section 33.4 — Suitability of an apartment building to house a board and care  
occupancy  
(5) Section 33.5 — Reserved  
(6) Section 33.6 — Basements  
(7) Section 33.7 — Operating features  
33.1.1.4 Conversions. For the purposes of this chapter, exceptions for conversions shall  
apply only for a change of occupancy from an existing residential or health care  
occupancy to an adult foster care facility. A change of licensee does not change the  
status of an existing facility to “new,” if the new license application is made not later than  
60 days of the previous license expiration date and the license category has not been  
changed, except as provided in MCL 400.721.  
(2) Small facilities  
33.2.2.5.2 Doors shall be swinging or sliding. Doors used as the means of escape shall  
be swinging. Exception: bathroom doors.  
Page 32  
33.2.2.5.5.1 Delayed-egress locks complying with 7.2.1.6.1 shall be permitted on exit  
doors only.  
33.2.2.6.4 Exterior stairs used as a means of escape, that exceed a vertical distance from  
grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with fire-resistive rated barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
33.2.3.2 Hazardous areas.  
33.2.3.2.2 Spaces requiring protection by 33.2.3.2.1 shall include, but shall not be  
limited to, areas for cartoned storage, food, or household maintenance items in wholesale  
or institutional-type quantities and concentrations, mass storage of residents’ belongings,  
furnaces, heating equipment, and furnace rooms.  
33.2.3.2.3 Areas containing approved, properly installed and maintained residential-type  
cooking and laundry equipment shall not be classified as hazardous areas solely on the  
basis of such equipment.  
33.2.3.2.6 Oxygen storage.  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
33.2.3.2.7 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive rated construction with all openings protected by not less than a 1-  
hour fire-resistive rated, B-labeled door and frame assembly.  
33.2.3.6.1.4 Deleted.  
33.2.3.6.4 Doors shall meet the following requirements:  
(1) Doors shall be provided with latches or other mechanisms suitable for keeping the  
doors closed.  
(2) No doors shall be arranged to prevent the occupant from closing the door.  
Page 33  
(3) Deleted.  
33.2.5.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
33.2.5.2.5. Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended, and NFPA pamphlet #  
211, 2003 edition, standard for chimneys, fireplaces, vents, and solid fuel-burning  
appliances, which is adopted by reference in R 400.18102.  
(3) Large Facilities  
33.3.1.1.1 Section 33.3 shall apply to residential board and care occupancies providing  
sleeping accommodations for 13 to 20 residents.  
33.3.1.1.2 Facilities having sleeping accommodations for 7 to 12 residents shall be  
evaluated in accordance with section 33.2.  
33.3.2.2.2 Doors in means of egress shall be as follows:  
(1) Doors complying with 7.2.1 shall be permitted.  
(2) Doors within individual rooms and suites of rooms may be swinging.  
(3) No door, other than those meeting the requirement of 33.3.2.2.2(4) or (5) shall be  
equipped with a lock or latch that requires the use of a tool or key from the egress side.  
(4) Delayed-egress locks in accordance with 7.2.1.6.1 shall be permitted, provided that  
not more than 1 device is located in any egress path.  
(5) Access controlled egress doors in accordance with 7.2.1.6.2 shall be permitted,  
provided that not more than 1 device is located in any egress path.  
(6) Doors located in the means of egress that are permitted to be locked under other  
provisions of chapter 33, other than those meeting the requirement of 33.3.2.2.2(4) or (5),  
shall have adequate provisions made for the rapid removal of occupants by means such as  
remote control of locks, keying of all locks to keys carried by staff at all times, or other  
such reliable means available to staff at all times.  
(7) Only 1 such locking device, as described in 33.3.2.2.2(6) shall be permitted on each  
door.  
33.3.2.2.3.1 Exterior stairs used as a means of egress, that exceed a vertical distance  
from grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with 1-hour fire resistive barriers, with all openings equipped with smoke-  
actuated automatic-closing or self-closing doors having a fire protection rating  
comparable to that required for the enclosure. Unprotected openings within 10 feet of  
exterior stairs less than 4 feet above grade shall be prohibited. Stairs shall comply with  
7.2.2.5.3.  
33.3.2.3.3 Deleted.  
33.3.2.3.4 Corridors shall be not less than 36 inches (915mm) wide.  
33.3.3.2.3 Fireplaces are prohibited.  
Page 34  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
33.3.3.2.2 (1) Boiler and heater rooms  
Boiler and heater rooms located in unoccupied basements are not subject to the one hour  
requirement of 33.3.3.2.2.  
33.3.3.2.4 Solid fuel-burning central heating appliances shall be in compliance with  
sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA pamphlet # 211,  
which is adopted by reference in 2.1 of the code, as amended by R 400.18102.  
33.3.3.2.5 Oxygen storage  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, which is adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
33.3.3.2.6 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
33.3.3.3 Interior finish. New interior finishes shall comply with this section.  
33.3.3.4.2 Initiation. The required fire alarm system shall be initiated by all of the  
following means:  
(1) Manual means in accordance with 9.6.2, unless there are other effective means, such  
as a complete automatic sprinkler or automatic detection system, for notification of fire as  
required.  
(2) Manual fire alarm box located at a convenient central control point.  
(3) Automatic sprinkler system, other than those not required by another section of this  
code.  
(4) Required detection system.  
Page 35  
33.3.3.4.7 Deleted.  
33.3.3.4.8.2 Deleted.  
33.3.3.4.8.4 Smoke detectors shall be required in all dwelling units, including sleeping  
rooms.  
33.3.3.5.1.1 In buildings not more than 4 stories in height, a sprinkler system complying  
the NFPA 13R, Standard for the installation of sprinkler systems in residential  
occupancies up to and including 4 stories in height, shall be permitted. Exception: An  
automatic sprinkler system in accordance with NFPA 13D, standard for the installation of  
sprinkler systems in 1- and 2-family dwellings and manufactured homes, shall be  
permitted for up to 16 residents.  
33.3.3.6.6.1 Deleted.  
(6) Basements.  
33.6. Basements.  
33.6.1. A basement shall not be used as a resident bedroom, unless it meets the  
definition of a “story above grade.”  
33.6.2. A basement that is used for resident activities shall have 2 remotely located  
means of escape separated by not less than 50% of the longest dimension of the floor, as  
practical. One of the means of escape shall exit directly to the outside at grade. The  
second means of escape may be the interior stairway that serves the first floor of the  
facility.  
(7) Operating procedures  
33.7.1.1 The administration of every residential board and care facility shall have in  
effect and available to all personnel, written copies of a plan for protecting all persons in  
the event of fire and for evacuating persons from the building to the designated point of  
safety. The plan shall include special staff response, including the fire protection  
procedures needed to ensure the safety of any resident, and shall be amended or revised  
whenever any resident with unusual needs is admitted to the home. All employees shall  
be periodically instructed and kept informed with respect to their duties and  
responsibilities under the plan, including the operation of fire alarm and other fire  
protection equipment. Such instruction shall be reviewed by the staff not less than every  
2 months. A copy of the plan shall be readily available at all times within the facility.  
The evacuation plan shall include provisions to protect residents who are either  
permanently or temporarily incapable of self-preservation. The evacuation plan shall be  
evaluated annually to ensure that all information is current and correct.  
33.7.1.1.1 The written fire safety plan shall provide for the following:  
(a) Use of alarms.  
(b) Transmission of alarm to fire department.  
(c) Response to alarms.  
(d) Isolation of fire.  
(e) Evacuation of building.  
(f) Closure of bedroom doors and corridor access doors upon exiting.  
(g) Use of fire extinguishers.  
Page 36  
33.7.1.2 The proper protection of adult foster care facility residents shall require the  
prompt and effective response of staff members. The basic response required of staff  
shall include the removal of all occupants directly involved with the fire emergency,  
transmission of an appropriate fire alarm signal to warn other building occupants and  
summon staff, confinement of the effects of the fire by closing doors to isolate the fire  
area, and evacuation of residents as de