DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
BUREAU OF FIRE SERVICES  
ADULT FOSTER CARE FACILITIES  
(By authority conferred on the bureau of fire services in cooperation with the department  
of human services and the state fire safety board by section 10 of 1979 PA 218, MCL  
400.710.  
PART 1. GENERAL PROVISIONS  
R 400.18101 Applicability.  
Rule 101. (1) These rules apply to all adult foster care facilities licensed for 7 or  
more adults pursuant to the provisions of 1979 PA 218, MCL 400.701 to 400.737  
(2) These rules supersede all local regulations applicable specifically to adult foster  
care facilities. Local ordinances, regulations, or construction codes regulating institutions  
shall not be applied to adult foster care facilities licensed for 7 or more adults including  
existing adult foster care congregate facilities. This subrule shall not be construed to  
exempt adult foster care facilities from local construction codes that are applicable to  
private residences. This provision is in compliance with section 33 of the adult foster care  
facility licensing act, 1979 PA 218, MCL 400.733.  
History: 1994 AACS; 2012 AACS.  
R 400.18102 Life safety code; adoption by reference; access to Michigan rules as  
referenced.  
Rule 102. (1) The provisions of chapters 1 to 10, 32 and 33 of national fire protection  
association (NFPA) standard 101, 2006 edition, entitled "Life Safety Code," referred to  
in these rules as “code” are adopted by reference in these rules.  
(2) Copies of the adopted provisions in subrules (1) and (3) of this rule are available  
for inspection and from the National Fire Protection Association, 1 Batterymarch Park, P.  
otherwise specified in subrule (3) of this rule. The cost as of the time of adoption of  
these rules is $75.00. The costs of the adopted provisions in subrule (3) of this rule are  
specified in subrule (3) of this rule. Copies of adopted standards are available for  
inspection at the offices of the Bureau of Fire Services, 4th Floor, 525 West Allegan, P. O.  
Box 30700, Lansing, Michigan 48909. Copies of the adopted provisions may be  
purchased from the bureau of fire services at the same cost as from the national source  
identified in subrules (1) and (3) of this rule plus $30.00 for shipping and handling as of  
the time of the adoption of these rules.  
(3) Chapter 2 of the code is amended to read as follows:  
2.1 General.  
Page 1  
The documents or portions thereof listed in this chapter are referenced within this  
code and are adopted by reference in these rules. The cost of each standard at the time of  
the adoption of these rules is indicated after the title.  
2.2 NFPA Publications. www.nfpa.org  
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.  
NFPA 1. “Uniform Fire Code ,” 2006 edition.  
NFPA 10. “Standard for Portable Fire Extinguishers,” 2002 edition.  
$38.00/each  
$72.00/each  
NFPA 11. “Standard for Low-, Medium-, and High-Expansion Foam,” 2005 edition.  
$38.00/each  
NFPA 12. “Standard on Carbon Dioxide Extinguishing Systems, 2005 edition.”  
$38.00/each  
NFPA 12A. “Standard on Halon 1301 Fire Extinguishing Systems, 2004 edition.”  
$38.00/each  
NFPA 13. “Standard for the Installation of Sprinkler Systems, 2002 edition”  
$72.00/each  
NFPA 13D. “Standard for the Installation of Sprinkler Systems in One- and Two-  
Family Dwellings and Manufactured Homes, 2002 edition.”  
$34.50/each  
NFPA 13R. “Standard for the Installation of Sprinkler Systems in Residential  
Occupancies up to and Including Four Stories in Height,” 2002 edition.  
$34.50/each  
NFPA 14. “Standard for the Installation of Standpipe and Hose Systems,” 2003  
edition.  
$34.50/each  
NFPA 15. “Standard for Water Spray Fixed Systems for Fire Protection,” 2001  
edition.  
$38.00/each  
NFPA 16. “Standard for the Installation of Foam-Water Sprinkler and Foam-Water  
Spray Systems,” 2003 edition.  
$34.50/each  
NFPA 17. “Standard for Dry Chemical Extinguishing Systems,” 2002 edition.  
$34.50/each  
NFPA 17A. “Standard for Wet Chemical Extinguishing Systems,” 2002 edition.  
$29.00/each  
NFPA 25. “Standard for the Inspection, Testing, and Maintenance of Water-Based  
Fire Protection Systems,” 2002 edition.  
$44.00/each  
Page 2  
NFPA 30B. “Code for the Manufacture and Storage of Aerosol Products, 2002  
edition.”  
$38.00/each  
NFPA 31. “Standard for the Installation of Oil-Burning Equipment,” 2001  
edition. References to this standard mean the Michigan administrative rules R 29.5401 to  
R 5419, promulgated by the Michigan department of natural resources and environment.  
NFPA 40. “Standard for the Storage and Handling of Cellulose Nitrate Film,” 2001  
edition.  
$29.00/each  
NFPA 45. “Standard on Fire Protection for Laboratories Using Chemicals,” 2004  
edition.  
$38.00/each  
NFPA 54. “National Fuel Gas Code,” 2006 edition.  
$44.00/each  
NFPA 58. “Liquefied Petroleum Gas Code,” 2004 edition. References to this code  
mean the Michigan administrative rules relating to storage and handling of liquefied  
petroleum gases, R 29.6001 to R 29.6097, promulgated by the Michigan department of  
natural resources and environment pursuant to the act.  
NFPA 70. “National Electrical Code®,” 2005 edition with amendments as provided  
in the Michigan electrical code, R 408.30801 to 408.30873, promulgated by the Michigan  
department of energy, labor, and economic growth, bureau of construction codes.  
NFPA 72. “National Fire Alarm Code,” 2002 edition.  
NFPA 80. “Standard for Fire Doors and Fire Windows,” 1999 edition.  
$38.00/each  
$54.00/each  
NFPA 82. “Standard on Incinerators and Waste and Linen Handling Systems and  
Equipment, 2004 edition.”  
$34.50/each  
NFPA 88A. “Standard for Parking Structures, 2002 edition.”  
$29.00/each  
NFPA 90A. “Standard for the Installation of Air-Conditioning and Ventilating  
Systems, 2002 edition.”  
$34.50/each  
NFPA 90B. “Standard for the Installation of Warm Air Heating and Air-Conditioning  
Systems,” 2006 edition.  
$29.00/each  
NFPA 91. “Standard for Exhaust Systems for Air Conveying of Vapors, Gases. Mists,  
and Noncombustible Particulate Solids,” 2004 edition.  
$29.00/each  
NFPA 92B. “Standard for Smoke Management Systems in Malls, Atria, and Large  
Spaces,” 2005 edition.  
$38.00/each  
NFPA 96. “Standard for Ventilation Control and Fire Protection of Commercial  
Cooking Operations,” 2004 edition.  
$34.50/each  
Page 3  
NFPA 99. “Standard for Health Care Facilities,” 2005 edition.  
$54.00/each  
NFPA 101A. “Guide on Alternative Approaches to Life Safety,” 2004 edition.  
$38.00/each  
NFPA 105. “Standard for the Installation of Smoke Door Assemblies,” 2003 edition.  
$29.00/each  
NFPA 110. “Standard for Emergency and Standby Power Systems,” 2005 edition.  
$34.50/each  
NFPA 111. “Standard on Stored Electrical Energy Emergency and Standby Power  
Systems,” 2005 edition.  
$29.00/each  
NFPA 160. “Standard for the Use of Flame Effects Before an Audience,” 2006  
edition.  
$34.50/each  
NFPA 211. “Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning  
Appliances,” 2003 edition.  
$38.00/each  
NFPA 220. “Standard on Types of Building Construction,” 2006 edition.  
$29.00/each  
NFPA 221. “Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier  
Walls,” 2006 edition.  
$34.50/each  
NFPA 241. “Standard for Safeguarding Construction, Alteration, and Demolition  
Operations,” 2004 edition.  
$34.50/each  
NFPA 251. “Standard Methods of Tests of Fire Resistance of Building Construction  
and Materials,” 2006 edition.  
$34.50/each  
NFPA 252. “Standard Methods of Fire Tests of Door Assemblies, 2003 edition.”  
$29.00/each  
NFPA 253. “Standard Method of Test for Critical Radiant Flux of Floor Covering  
Systems Using a Radiant Heat Energy Source,” 2006 edition.  
$29.00/each  
NFPA 255. “Standard Method of Test of Surface Burning Characteristics of Building  
Materials,” 2006 edition.  
$29.00/each  
NFPA 256. “Standard Methods of Fire Tests of Roof Coverings,” 2003 edition.  
$29.00/each  
NFPA 257. “Standard on Fire Test for Window and Glass Block Assemblies,” 2000  
edition.  
$29.00/each  
Page 4  
NFPA 259. “Standard Test Method for Potential Heat of Building Materials,” 2003  
edition.  
$29.00/each  
NFPA 260. “Standard Methods of Tests and Classification System for Cigarette  
Ignition Resistance of Components of Upholstered Furniture,” 2003 edition.  
$29.00/each  
NFPA 261. “Standard Method of Test for Determining Resistance of Mock-Up  
Upholstered Furniture Material Assemblies to Ignition by Smoldering Cigarettes,” 2003  
edition.  
$29.00/each  
NFPA 265. “Standard Methods of Fire Tests for Evaluating Room Fire Growth  
Contribution of Textile Coverings on Full Height Panels and Walls,” 2002 edition.  
$34.50/each  
NFPA 286. “Standard Methods of Fire Tests for Evaluating Contribution of Wall and  
Ceiling Interior Finish to Room Fire Growth,” 2006 edition.  
$34.50/each  
NFPA 288. “Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance–Rated Floor Systems,” 2001 edition.  
$29.00/each  
NFPA 415. “Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and  
Loading Walkways,” 2002 edition.  
$29.00/each  
NFPA 418. “Standard for Heliports,” 2001 edition.  
$29.00/each  
NFPA 430. “Code for the Storage of Liquid and Solid Oxidizers,” 2004 edition.  
$34.50/each  
NFPA 432. “Code for the Storage of Organic Peroxide Formulations,” 2002 edition.  
$34.50/each  
NFPA 434. “Code for the Storage of Pesticides,” 2002 edition.  
$29.00/each  
NFPA 701. “Standard Methods of Fire Tests for Flame Propagation of Textiles and  
Films,” 2004 edition.  
$29.00/each  
NFPA 703. “Standard for Fire Retardant–Treated Wood and Fire-Retardant Coatings  
for Building Materials,” 2006 edition.  
$29.00/each  
NFPA 750. “Standard on Water Mist Fire Protection Systems, 2003 edition.”  
$38.00/each  
Page 5  
NFPA 914. “Code for Fire Protection of Historic Structures,” 2001 edition.  
$54.00/each  
NFPA 1124. “Code for the Manufacture, Transportation, Storage, and Retail Sales of  
Fireworks and Pyrotechnic Articles,” 2006 edition.  
$38.00/each  
NFPA 1126. “Standard for the Use of Pyrotechnics Before a Proximate Audience,”  
2006 edition.  
$29.00/each  
NFPA 2001. “Standard on Clean Agent Fire Extinguishing Systems,” 2004 edition.  
$44.00/each  
NFPA 5000. “Building Construction and Safety Code,” 2006 edition. References to  
this code mean the Michigan residential code, R 408.30501 to 408.30547, promulgated  
by the Michigan department of energy, labor, and economic growth, bureau of  
construction codes.  
2.3 Other Publications.  
2.3.1 ACI Publication. www.concrete.org American Concrete Institute, P.O. Box  
9094, Farmington Hills, MI 48333. ACI 216.1/TMS 0216.1. “Standard Method for  
Determining Fire Resistance of Concrete and Masonry Construction Assemblies,” 1997.  
$70.50/each  
2.3.2 ANSI Publications.  
American National Standards Institute, Inc., 25 West 43rd Street, 14th floor, New  
York, NY 10036. ANSI A14.3. “Safety Requirements for Fixed Ladders,” 2002.  
$219.00/each  
ICC/ANSI A117.1. “American National Standard for Accessible and Usable  
$35.00/each  
BHMA/ANSI A156.19. “American National Standard for Power Assist and Low  
$40.00/each  
2.3.3 Deleted.  
2.3.4 ASME Publications. www.asme.org  
American Society of Mechanical Engineers  
Three Park Avenue, New York, NY 10016-5990.  
2.3.5 ASTM Publications. www.astm.org  
American Society for Testing and Materials, 100 Barr Harbor Drive, West  
Conshohocken, PA 19428-2959.  
ASTM D 1929. “Standard Test Method for Determining Ignition Temperatures of  
Plastic,” 2001.  
$36.00/each  
ASTM D 2859. “Standard Test Method for Ignition Characteristics of Finished  
Textile Floor Covering Materials,” 2004.  
$37.20/each  
Page 6  
ASTM D 2898. “Standard Test Methods for Accelerated Weathering of Fire-  
Retardant-Treated Wood for Fire Testing,” 1994 (1999).  
$37.20/each  
ASTM E 136. “Standard Test Method for Behavior of Materials in a Vertical Tube  
Furnace at 750°C,” 2004.  
$36.00/each  
ASTM E 814. “Standard Test Method for Fire Tests of Through Penetration Fire  
Stops,” 2002.  
$43.20/each  
ASTM E 1966. “Standard Test Method for Fire-Resistive Joint Systems,” 2001.  
$50.40/each  
ASTM E 2074. “Standard Test Method for Fire Tests of Door Assemblies, Including  
Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies,”  
2000e1.  
$50.40/each  
2.3.6 FMGR Publication.  
FM Global Research, FM Global, 1301 Atwood Avenue, P.O. Box 7500, Johnston,  
RI 02919.  
FM 4880. “Approval Standard for Class I Insulated Wall or Wall and Roof/Ceiling  
Panels; Plastic Interior Finish Materials; Plastic Exterior Building Panels; Wall/Ceiling  
Coating Systems; Interior or Exterior Finish Systems,” 1994. Free PDF download online  
200.com per UL website. (All revisions included in purchase of standard) Underwriters  
Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062.  
UL 555. “Standard for Fire Dampers,” 1999, Revised 2002.  
$974.00 per  
hard copy/$779.00 per PDF copy  
UL 555S. “Standard for Smoke Dampers,” 1999, Revised 2003.  
$248.00/each  
UL 924. “Standard for Emergency Lighting and Power Equipment,” 1995, Revised  
2001.  
$974.00 per hard copy/$779.00 per PDF copy  
UL 1040. “Standard for Fire Test of Insulated Wall Construction,” 1996.  
$490.00 per  
hard copy / $392.00 PDF copy  
UL 1715. “Standard for Fire Test of Interior Finish Material,” 1997.  
$875.00 per hard copy / $699.00 per  
PDF copy  
UL 1975. “Standard for Fire Tests for Foamed Plastics Used for Decorative  
Purposes,” 1996.  
$974.00 per hard  
copy/$779.00 per PDF copy  
2.3.8 U.S. Government publication. www.gpoaccess.gov/CFR  
U.S. Government Printing Office, Washington, DC 20402.  
Page 7  
Title 16. “Code of Federal Regulations, Part 1632, Standard for the Flammability of  
Mattresses and Mattress Pads.”  
$63.00/each  
2.3.9 Other Publication.  
“Merriam-Webster's Collegiate Dictionary,” 11th edition, Merriam-Webster, Inc.,  
2.4 References for rxtracts in mandatory sections.  
NFPA 1. “Uniform Fire Code ,” 2006 edition.  
NFPA 72®. “National Fire Alarm Code®,” 2002 edition.  
$54.00/each  
$26.95/each  
$72.00/each  
NFPA 80. “Standard for Fire Doors and Fire Windows,” 1999 edition.  
$38.00/each  
NFPA 88A. “Standard for Parking Structures,” 2002 edition.  
$29.00/each  
NFPA 101B. “Code for Means of Egress for Buildings and Structures,” 2002 edition.  
$44.00/each  
NFPA 102. “Standard for Grandstands, Folding and Telescopic Seating, Tents, and  
Membrane Structures,” 1995 edition.  
$29.00/each  
NFPA 288. “Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance–Rated Floor Systems,” 2001 edition.  
$29.00/each  
NFPA 301. “Code for Safety to Life from Fire on Merchant Vessels,” 2001 edition.  
$8.00/each  
NFPA 415. “Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and  
Loading Walkways,” 2002 edition.  
$29.00/each  
NFPA 914. “Code for Fire Protection of Historic Structures,” 2001 edition.  
$54.00/each  
NFPA 921. “Guide for Fire and Explosion Investigations,” 2004 edition.  
$72.00/each  
(4) Rules pertaining to flammable and combustible liquid handing referenced in  
8.7.3.1. of the code are available for inspection from the bureau of fire services as  
identified in subrule (2) of this rule, and are promulgated by and also available from the  
Michigan department of environmental quality storage tank unit by calling (517) 335-  
code.”  
(5) Rules pertaining to the Michigan elevator code, Michigan mechanical code, the  
Michigan building code, Michigan electrical code, and Michigan plumbing code are  
available for inspection at the Okemos office of the bureau of construction codes. Copies  
of these rules are available from the Michigan government website,  
Page 8  
Michigan Department of Energy, Labor, & Economic Growth, Bureau of Construction  
Codes, 2501 Woodlake Circle, Okemos, Michigan 48864.  
mm) from the building, between the building and a point 6 feet (1,829 mm) from  
the building.  
(j) "Interconnected" means that the entire fire detection system is connected  
together so that, when 1 detection device is activated, a general alarm will sound  
which shall be audible in all habitable areas.  
(k) "Licensee" means the agency, association, corporation, organization, person, or  
department or agency of the state, county, city, or other political subdivision that  
has been issued a license to operate an adult foster care facility.  
(l) "Listed" means the material listed by an approved independent nationally  
recognized testing laboratory acceptable to the state fire marshal.  
(m) "New" means a facility licensed after the effective date of these rules.  
(n) "Story above grade" means any story that has its finished floor surface  
entirely above grade, except that a basement shall be considered as a story above grade  
when the distance from grade to the finished surface of the floor above the  
basement is more than 6 feet (1,829 mm) for more than 50% of the total perimeter or  
more than 12 feet (3,658 mm) at any point.  
(o) "Twin-twenty" means 2 20-bed facilities that are attached or located inside the  
same building, separated from each other by not less than a 2-hour fire wall.  
(p) "Usable floor space" means floor space under a ceiling not less than 6 feet 6  
inches in height, excluding closets.  
History: 1994 AACS; 2012 AACS.  
R 400.18103 Definitions.  
Rule 103. As used in these rules for new and existing adult foster care facilities and  
congregate facilities licensed for 7 or more adults:  
(a) "Act" means 1979 PA 218, MCL 400.701 to 400.737  
(b) "Adult foster care facility" has the same meaning as defined in the act.  
(c) "Approved" means acceptable to the bureau of fire services, unless specifically  
indicated otherwise in these rules.  
(d) "Authority having jurisdiction" means the bureau of fire services, an employee of the  
bureau of fire services, or an employee of a city, village, or township delegated to enforce  
the code under section 2b of the act.  
(e) "Code" means national fire protection association standard no. 101, 2006 edition,  
entitled “life safety code.”  
(f) “Congregate facility” means an adult foster care facility with the approved capacity  
to receive more than 20 adults for foster care.  
(g) "Conversion" means either of the following:  
(i) To change the license category for an existing facility.  
(ii) To change the purpose for which a building, a room, or an area is designed.  
(h) “Cosmetic remodeling” means surface changes made solely to the wall, floor, or  
ceiling, that do not decrease the fire rating of the wall, floor, or ceiling, including the  
replacement of windows and doors.  
(i) "Department" means the Michigan department of licensing and regulatory affairs.  
Page 9  
(j) “Evacuation capability” means the ability of residents, occupants, and staff, as a  
group, to evacuate the adult foster care facility. Evacuation capability may be classified  
as “prompt,” “slow,” or “impractical.”  
(k) "Existing facility" means a facility that was licensed before the effective date of  
these rules or a change in facility ownership without a conversion of the facility.  
(l) "Grade" means a reference plane that represents the average of finished ground level  
adjoining the building at all exterior walls. When the finished ground level slopes away  
from the exterior walls, the reference plane shall be established by the lowest points  
within the area between the building and the lot line or, when the lot line is more than 6  
feet (1,829 mm) from the building, between the building and a point 6 feet (1,829 mm)  
from the building.  
(m) “Impractical” means that a facility’s evacuation capability is such that the facility  
cannot be evacuated in less than 8 minutes.  
(n) "Interconnected" means that the entire fire alarm system is connected together so  
that, when 1 alarm device is activated, a general alarm will sound which shall be audible  
in all habitable areas.  
(o) "Licensee" means the agency, association, corporation, company, organization,  
person or persons, or department or agency of the state, county, city, or other political  
subdivision that has been issued a license to operate an adult foster care facility.  
(p) "Listed" means the material listed by an approved independent nationally recognized  
testing laboratory acceptable to the bureau of fire services.  
(q) “Large facility” means an adult foster care facility with the approved capacity to  
receive at least 13 but not more than 20 adults for foster care.  
(r) “Maintenance” means repair that is required to keep the building and its component  
parts in an operative condition at all times. “Maintenance” includes the replacement of a  
building’s components when, for any reason, they become undependable or inoperable,  
but does not include remodeling.  
(s) "New" means a facility licensed after the effective date of these rules or a facility  
licensed before the effective date of the rules that changes license category.  
(t) “Prompt” means that a facility’s evacuation capability is such that the facility can be  
evacuated in 3 minutes or less.  
(u) “Remodeling” means an alteration or change of fire-rated assembly, or the  
installation of new equipment required by these rules.  
(v) "Resident" means a person who is receiving adult foster care and resides in an adult  
foster care facility.  
(w) “Slow” means that a facility’s evacuation capability is such that the facility can be  
evacuated in less than 8 minutes, but more than 3 minutes.  
(x) “Small facility” means an adult foster care facility with the approved capacity to  
receive at least 7 but not more than 12 adults for foster care.  
(y) "Story above grade" means any story that has its finished floor surface entirely  
above grade, except that a basement shall be considered as a story above grade when the  
distance from grade to the finished surface of the floor above the basement is more than 6  
feet (1,829 mm) for more than 50% of the total perimeter.  
(z) "Twin-twenty" means 2 20-bed facilities that are attached or located inside the same  
building, separated from each other by not less than a 2-hour fire wall.  
Page 10  
(aa) "Usable floor space" means floor space under a ceiling not less than 6 feet 6 inches  
in height, excluding closets.  
History: 1994 AACS; 2012 AACS.  
R 400.18104 Plans and specifications.  
Rule 104. (1) A registered architect or engineer shall submit plans and specifications to  
the bureau of fire services for all projects that involve construction, additions,  
remodeling, or conversions.  
(2) An adult foster care facility is not required to submit plans and specifications for  
routine maintenance functions or cosmetic remodeling, subject to both of the following:  
(a) An adult foster care facility shall ensure that all work is in compliance with these  
rules.  
(b) Cosmetic remodeling shall not diminish the fire safety of any features being  
replaced.  
(3) Plans and specifications for construction, remodeling, or an addition that involves  
the practices of architecture or engineering, as defined by the provisions of PA 299, MCL  
339.101 to 339.2919, known as the occupational code, shall bear the seal of an architect  
or engineer who is registered pursuant to 1980 PA 299, MCL 339.101 to 339.2919.  
(4) Plans and specifications shall contain all of the following information, as applicable:  
(a) Complete floor plan and layout of the building drawn accurately to scale.  
(b) Use of each room.  
(c) Dimensions of each room.  
(d) Size, location, direction of swing, and fire rating of each door and frame assembly.  
(e) Size and location of windows.  
(f) Wall construction, including fire-resistance rating.  
(g) Type of construction as identified in the “Standards on types of building  
construction,” referenced in Chapter 2 of the life safety code which is adopted by  
reference in R 400.18102.  
(h) Number of stories, including basement and attic areas.  
(i) Interior finish classification.  
(j) Location of fuel-fired equipment.  
(k) Type of furnace and water heater.  
(l) Air-handling system specifications.  
(m) Fire detection and alarm system plans and specifications that are in compliance with  
the fire prevention code, 1941 PA 207, MCL 29.1. to 29.34.  
(n) Sprinkler or other suppression system plans and specifications that are in compliance  
with the fire prevention code, 1941 PA 207, MCL 29.1 to 29.34.  
(o) Type, size, and location of fire extinguishers.  
(p) Other pertinent information that is required to determine compliance with these  
rules.  
(5) Plan approval that is given before the effective date of these rules shall terminate 6  
months after the effective date of these rules if construction has not started.  
History: 1994 AACS; 2012 AACS.  
Page 11  
R 400.18105 Inspections during construction; approval for occupancy.  
Rule 105. (1) During construction, additions, remodeling, or conversions: the architect,  
professional engineer, or construction manager shall notify the bureau of fire services, in  
writing, that the building is ready for inspection at both of the following times:  
(a) When the building is framed and mechanical systems are substantially complete, but  
before concealment.  
(b) When construction is completed.  
(2) A person shall not occupy a newly constructed facility or a facility that is being  
remodeled or added to, in whole or in part, unless approved by the bureau of fire services  
and unless licensed by the department of human services, bureau of children and adult  
licensing  
History: 1994 AACS; 2012 AACS.  
R 400.18106 Projects affecting outside configuration of building, site plan and  
specifications; bureau of fire services or local fire authority specifications; fire  
safety measures during construction.  
Rule 106. (1) Before construction begins for projects that involve construction, addition,  
or remodeling that affects the outside configuration of a building, and as part of the  
building plans and specifications otherwise required by these rules, the licensee’s or  
licensee applicant’s designated architect, engineer or construction manager shall provide  
the bureau of fire services and the local fire authority with a site plan and specifications  
that detail all of the following:  
(a) The available water supply.  
(b) Hydrant locations.  
(c) Vehicle access routes.  
(d) Fire lanes.  
(2) The bureau of fire services or local fire authority may specify any of the following:  
(a) The size of the water mains that supply the hydrants.  
(b) The location of hydrants.  
(c) The locations and dimensions of fire department vehicle access routes.  
(d) The posting of fire lanes.  
(3) As soon as possible during construction, the adult foster care facility shall ensure  
that appropriate fire safety measures shall be taken, including the provision of fire  
extinguishers and fire suppression systems and the establishment of access routes to the  
building that can be traveled by fire department vehicles.  
History: 1994 AACS; 2012 AACS.  
R 400.18107 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 12  
R 400.18108 Universal amendments to code.  
Rule 108. Sections 4.6.10.1, 7.1.10.1, 8.7.3.1, 3.3.65.1, 9.1.1, 9.1.2, 9.4.2.1, and section  
10.2.6.1 of the code, which is adopted by reference in rule 102 of these rules, are  
amended; sections 7.1.7.2.5, 7.2.1.8.1.1, 9.1.1.1, 9.1.1.2, 9.1.1.3, 9.1.1.4, 9.1.2.1, and  
9.1.2.2 are added, and 3.2.1, 3.2.2, 3.2.3, 3.2.5, 9.4.2.2, 9.4.3, 9.4.4, 9.4.5, 9.4.6, and 9.4.7  
are deleted to read as follows:  
3.2.1 Deleted.  
3.2.2 Deleted.  
3.2.3 Deleted.  
3.2.5 Deleted.  
4.6.10.1 A person may occupy a building or portions of a building during construction,  
repair, alterations, or additions only if all means of egress and all fire protection features  
in the building and on site are in place and continuously maintained for the part occupied  
and if the occupied portion is separated from the part under construction by a wall that  
has a 1-hour-fire-resistance rating. The temporary 1-hour fire-resistive rated wall that is  
used for this purpose may be constructed of combustible material. Instead of having all  
means of egress and fire protection features in place, the adult foster care facility may  
take other measures that would provide equivalent safety if approved by the bureau of  
fire services. An adult foster care facility or any of its parts shall not be occupied, in  
whole or in part, without approval from the bureau of fire services, and the Michigan  
department of human services, bureau of children and adult licensing.  
7.1.7.2.5. Facilities housing residents, who regularly require wheelchairs, shall be  
equipped with ramps located at the required means of escape. Ramps shall be in  
compliance with section 7.2.5 of the code.  
7.1.10.1 Means of egress shall be continuously maintained free of all obstructions or  
impediments to full instant use in the case of fire or other emergency. Seasonal  
obstructions such as ice and snow shall not impede safe passage away from the facility to  
a point of safety.  
7.2.1.8.1.1 A door required to be equipped with a self-closing device shall be positive-  
latching upon closure.  
8.2.1.3 Where the building or facility includes additions or connected structures of  
different construction types, all of the following shall apply:  
(a) The rating and classification of the structure shall be based on 1 of the following:  
(i) Separate buildings, if a 2-hour or greater vertically aligned fire barrier wall in  
accordance with NFPA 221, Standard for Fire Walls and Fire Barrier Walls, exists  
between the portions of the building.  
(ii) Separate buildings, if provided with previously approved separations.  
(iii) Least fire-resistive type of construction of the connected portions, if separation as  
specified in paragraph (i) or (ii) of this subdivision is not provided.  
(b) Each proposed facility shall be inspected and licensed independently.  
(c) Each facility shall have a distinct living area, dining area, sleeping area and  
multipurpose area, sized accordingly.  
(d) Each facility may share common services such as laundry, kitchen and heating  
plants.  
Page 13  
8.7.3.1 The adult foster care facility shall store flammable and combustible liquids in  
compliance with R 29.5101 to R 29.5516 promulgated by the Michigan department of  
environmental quality under the act.  
9.1.1 Gas. Equipment using gas and related gas piping shall be in accordance with the  
following requirements:  
9.1.1.3 The installation, use, and maintenance of a gas appliance and gas piping shall be  
in accordance with the provisions of NFPA 54, national fuel gas code, which is adopted  
by reference in R 400.18102.  
9.1.1.4 A liquefied petroleum gas installation shall be in compliance with R_29.6001 to  
R_29.6097 promulgated under the act. When a gas supply line is placed in a tunnel, it  
shall be installed without joints and the tunnel shall have forced ventilation.  
9.1.2 Electrical systems.  
9.1.2.1 The adult foster care facility or designated representative shall ensure that the  
electrical wiring and equipment, including an emergency electrical supply if installed, is  
installed in compliance with the provisions of the NFPA 70, as adopted in Chapter 2.2, as  
amended by and available as specified in R 400.18102.  
9.1.2.2 Electrical inspection shall be made by an electrical inspection authority  
acceptable to the bureau of fire services. The authority shall issue a final approval  
certificate of compliance covering the installation.  
9.4.2.1 The adult foster care facility shall ensure that new and existing elevators,  
escalators, dumbwaiters, and moving walks shall be installed in compliance with R  
408.7001 to R 408.8695.  
9.4.2.2 Deleted.  
9.4.3 Deleted.  
9.4.4 Deleted  
9.4.5 Deleted.  
9.4.6 Deleted.  
9.4.7 Deleted.  
10.2.6.1 The required flame spread or smoke developed classification of surfaces of  
walls, partitions, columns, and ceilings shall not be attained by applying approved fire  
retardant coatings to surfaces that have a higher flame spread rating than permitted.  
Applications approved prior to the effective date of these rules shall be maintained in  
accordance with section 10.2.6.2.  
History: 1994 AACS; 2012 AACS.  
R 400.18109 Fire reporting.  
Rule 109. After the occurrence of a fire, the adult foster care licensee shall immediately  
notify the local fire department and the bureau of fire services with all details of the fire.  
History: 1994 AACS; 2012 AACS.  
R 400.18110 Fire alarm system requirements.  
Rule 110. The adult foster care licensee or designated representative shall ensure that  
the installation, modification, testing, servicing, inspection, or maintenance of a fire  
Page 14  
alarm or fire suppression system required by these rules shall be in compliance with 1941  
PA 207, MCL 29.1 to MCL 29.34.  
History: 1994 AACS; 2012 AACS.  
R 400.18111 Aid for emergency services.  
Rule 111. Every facility shall have the address number displayed in a position easily  
observed and readable from the public right-of-way. All numbers shall be in Arabic  
numerals at least 3 inches (76 mm) high and ½ inch (13 mm) stroke minimum  
History: 1994 AACS; 2012 AACS.  
PART 2. NEW SMALL AND LARGE ADULT FOSTER CARE FACILITIES  
R 400.18201 Application; amendments to chapter 32 of the code.  
Rule 201. Sections 32.1.1.3, 32.1.1.6.3, 32.1.3, 32.2.1.1.1, 32.2.1.1.2, 32.2.1.2,  
32.2.2.5.1, 32.2.2.5.2, 32.2.2.5.5.1, 32.2.3.1.2, 32.2.3.2, 32.2.3.4.3, 32.2.3.4.3.1,  
32.2.3.4.3.2, 32.2.3.4.3.3, 32.2.3.4.3.4, 32.2.3.5.1, 32.3.1.1.1, 32.3.1.1.2, 32.3.1.3,  
32.3.2.2.2, 32.3.2.11.2, 32.3.3.4.2, 32.3.3.4.8, 32.3.3.4.8.1, 32.3.3.4.8.2, 32.3.3.4.8.3,  
3.2.4, 32.7.1.1, 32.7.1.2, 32.7.3.1, and 32.7.6 of the code are amended, sections  
32.2.2.6.4, 32.2.3.2.3.1, 32.2.3.2.6, 32.2.3.2.7, 32.2.5.2.4, 32.3.2.2.3.1, 32.3.3.2.3,  
32.3.3.2.4, 32.3.3.4.8.4, 32.3.6.2.4, 32.3.6.2.5, 32.5, 32.6, 32.6.1, 32.6.2, 32.7.1.1.1,  
32.7.4.1, 32.7.5, and 32.7.5.3, 32.7.4.1.1, 32.7.4.3, 32.7.5.1.1, 32.7.5.2.2, 32.7.5.3, and  
32.7.5.3.2 are added, and sections 32.1.1.4, 32.2.2.5.1.2, 32.2.2.6.2, 32.2.3.1.5,  
32.2.3.2.1, 32.2.3.2.2, 32.2.3.5.2, 32.3.2.2.10, 32.3.3.4.7, 32.4.1, 32.4.1.1, 32.4.1.1.2,  
32.4.1.1.3, 32.4.1.1.4, 32.4.1.2, 32.4.1.3, 32.4.1.4, 32.4.1.4.1, 32.4.1.4.2, 32.4.2.1,  
32.4.2.2, 32.4.3, 32.4.3.1, 32.4.3.1.1, 32.4.3.1.2, 32.4.3.2, 32.4.3.2.1, 32.4.3.2.2, 32.4.3,  
32.4.3.1, 32.4.3.1.1, 32.4.3.1.2, 32.4.3.2, 32.4.3.2.1, 32.4.3.2.2, 32.4.3.3, 32.7.2.4,  
32.7.3.5, and 32.7.3.6 are deleted to read as follows:  
General Requirements  
32.1.1.3 Chapter Sections. This chapter is divided into 7 sections as follows:  
(1) Section 32.1 — General Requirements  
(2) Section 32.2 — Small facilities (7-12 residents)  
(3) Section 32.3 — Large facilities (13 to 20 residents)  
(4) Section 32.4 — Apartments  
(5) Section 32.5 — Miscellaneous  
(6) Section 32.6 — Basements  
(7) Section 32.7 — Operating features  
(1) General Requirements  
Page 15  
32.1.1.4 Conversions. For the purposes of this chapter, exceptions for conversions shall  
apply only for a change of occupancy from an existing residential or health care  
occupancy to an adult foster care facility. A change of licensee does not change the  
status of an existing facility to “new” if the new license application is made not later than  
60 days of the previous license expiration date and the license category has not been  
changed, except as provided in MCL 400.721.  
32.1.3 Definitions. The following are terms used in this chapter:  
(1) Personal care. See 3.3.181.  
(2) Point of safety. See 3.3.186.  
(3) Residential board and care facility means an adult foster facility licensed by the  
Michigan department of human services.  
(4) Residential board and care occupancy means a building or portion thereof that is  
used for lodging and boarding of 7 to 20 residents for the purpose of providing personal  
care services. See R 400.18103 for definitions of small and large facilities.  
(5) Residential board and care resident means a person who is receiving adult foster care  
and resides in an adult foster care facility.  
(6) Staff (residential board and care). See 3.3.232.  
(7) Thermal barrier. See 3.3.24.3.  
(2) Small Facilities  
32.2.1.1.1 Section 32.2 applies to adult foster care facilities that provide adult foster care  
for small facilities that house 7 to 12 residents.  
32.2.1.1.2 Where there are sleeping accommodations for 13 to 20 residents, the  
occupancy shall be classified as a large adult foster care facility in accordance with  
section 32.3.  
32.2.1.2 Requirements based upon evacuation capabilities shall comply with  
“impractical,” “prompt,” and “slow,” as defined in Rule 103 of these rules.  
32.2.2.5.1 A door opening to a means of escape shall not be less than 32 inches (81 cm)  
clear width.  
32.2.2.5.1.2 Deleted.  
32.2.2.5.2 Means of escape doors shall be swinging.  
32.2.2.5.5.1 Delayed-egress locks complying with 7.2.1.6.1 shall be permitted for exit  
doors only.  
32.2.2.6.2 Deleted.  
32.2.2.6.4 Exterior stairs used as a means of escape, that exceed a vertical distance from  
grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with 1-hour rated fire barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
32.2.3.1.2 Vertical openings shall be separated by smoke partitions in accordance with  
section 8.4 that resist the passage of smoke from 1 story to another story.  
32.2.3.1.5 Deleted.  
32.2.3.2 Protection from hazards.  
_______________________________________________________________________  
Page 16  
Hazardous Area Description  
Separation/Protection____________  
Boiler and fuel-fired heater rooms 1 hour  
Central/bulk laundries larger than 100 ft2 (9.3 m2) 1 hour  
paint shops employing hazardous substances and 1 hour  
materials in quantities less than those that would  
be classified as a severe hazard  
Physical plant maintenance shops  
Soiled linen rooms  
1 hour  
1 hour  
Storage rooms larger than 50 ft2 (4.6 m2), but not  
exceeding 100 ft2 (9.3 m2), storing combustible  
material  
Smoke partition  
Trash collection rooms  
1 hour  
32.2.3.2.1 Deleted.  
32.2.3.2.2 Deleted.  
32.2.3.2.6 Oxygen storage  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, which is adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
32.2.3.2.7 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive-rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
32.2.3.4.3 Smoke detectors.  
32.2.3.4.3.1 Approved smoke detectors shall be provided in accordance with 9.6.1.3.  
32.2.3.4.3.2 Smoke detectors shall be installed on all levels, including basements but  
excluding crawl spaces and unfinished attics.  
32.2.3.4.3.3 Additional smoke detectors shall be installed in all living areas, as defined  
in 3.3.17.5.  
32.2.3.4.3.4 Each sleeping room shall be provided with an approved smoke detector.  
Page 17  
32.2.3.5.1 All facilities shall be protected throughout by an approved automatic  
sprinkler system, installed in accordance with 32.2.3.5.3, using quick-response or  
residential sprinklers.  
32.2.3.5.2 Deleted.  
32.2.5.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
32.2.5.2.5 Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA  
pamphlet # 211, which is adopted by reference in 2.1 of the code, as amended by R  
400.18102.  
(3) Large Facilities  
32.3.1.1.1 Section 32.3 applies to adult foster care facilities that provide adult foster care  
for large facilities that house 13 to 20 residents.  
32.3.1.1.2 Where there are sleeping accommodations for 7 to 12 residents, the  
occupancy shall be classified as a small adult foster care facility in accordance with  
Section 32.2.  
32.3.1.3 Minimum construction requirements. Building construction requirements are  
under the authority of the Michigan construction code, administered by the bureau of  
construction codes, as provided in amendments to section 2.1 of the code in R 400.18102.  
32.3.2 Means of egress.  
32.3.2.2.2 Doors. Doors in means of egress shall be as follows:  
(1) Doors complying with 7.2.1 shall be permitted.  
(2) Doors within individual rooms and suites of rooms may be swinging.  
(3) Door, other than those meeting the requirement of 32.3.2.2.2(4) or (5) shall be not be  
equipped with a lock or latch that requires the use of a tool or key from the egress side.  
(4) Delayed-egress locks in accordance with 7.2.1.6.1 shall be permitted, provided that  
not more than 1 device is located in any egress path.  
(5) Access controlled egress doors in accordance with 7.2.1.6.2 shall be permitted,  
provided that not more than 1 device is located in any egress path.  
(6) Doors located in the means of egress that are permitted to be locked under other  
provisions of chapter 32, other than those meeting the requirement of 32.3.2.2.2(4) or (5),  
shall have adequate provisions made for the rapid removal of occupants by means such as  
remote control of locks, keying of all locks to keys carried by staff at all times, or other  
such reliable means available to staff at all times.  
(7) Only 1 such locking device, as described in 32.3.2.2.2(6) shall be permitted on each  
door.  
32.3.2.2.10 Deleted.  
32.3.2.11.2 Lockups are not permitted.  
32.3.2.2.3.1 Exterior stairs used as a means of egress that exceed a vertical distance  
from grade of more than 4 feet shall be enclosed and separated from the remainder of the  
Page 18  
facility with 1-hour rated fire barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
32.3.3.2.3 Oxygen storage.  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive-rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
32.3.3.2.4 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive-rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
32.3.3.4.2 Initiation. The required fire alarm system shall be initiated by all of the  
following:  
(1) Manual means in accordance with 9.6.2.  
(2) Required automatic sprinkler system.  
(3) Required detection system.  
32.3.3.4.7 Delete.  
32.3.3.4.8 Smoke detection systems.  
32.3.3.4.8.1 Approved smoke detectors shall be provided in accordance with 9.6.1.3.  
32.3.3.4.8.2 Smoke detectors shall be installed on all levels, including basements but  
excluding crawl spaces and unfinished attics.  
32.3.3.4.8.3 Additional smoke detectors shall be installed in all living areas, as defined  
in 3.3.17.5.  
32.3.3.4.8.4 Each sleeping room shall be provided with an approved smoke detector.  
32.3.6.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Page 19  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
32.3.6.2.5. Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA  
pamphlet # 211, which is adopted by reference in 2.1 of the code, as amended by R  
400.18102.  
(4) Apartments  
32.4 An adult foster care facility shall not be located in, or be a part of, an apartment  
building.  
32.4.1 to 32.4.3.3 Deleted.  
(5) Miscellaneous requirements  
32.5.1 Facilities housing persons who use wheelchairs shall be provided with ramps at  
the required means of egress.  
(6) Basements  
32.6.1. A basement shall not be used as a resident bedroom, unless it meets the  
definition of a “story above grade.”  
32.6.2 A basement that is used for resident activities shall have 2 remotely located  
means of escape separated by not less than 50% of the longest dimension of the floor, as  
practical. One of the means of escape shall exit directly to the outside at grade. The  
second means of escape may be the interior stairway that serves the first floor of the  
facility.  
(7) Operating features  
32.7.1.1 The administration of every adult foster care facility shall have in effect and  
available to all personnel, written copies of a plan for protecting all persons in the event  
of fire and for evacuating persons from the building to the designated point of safety.  
The plan shall include special staff response, including the fire protection procedures  
needed to ensure the safety of any resident, and shall be amended or revised whenever  
any resident with unusual needs is identified. All employees shall be periodically  
instructed and kept informed with respect to their duties and responsibilities under the  
plan, including the operation of fire alarm and other fire protection equipment. Such  
instruction shall be reviewed by the staff not less than every 2 months. A copy of the  
plan shall be readily available at all times within the facility. The evacuation plan shall  
include provisions to protect residents who are either permanently or temporarily  
incapable of self-preservation. The evacuation plan shall be evaluated annually to ensure  
that all information is current and correct.  
32.7.1.1.1 The written fire safety plan shall provide for the following:  
(a) Use of alarms.  
(b) Transmission of alarm to fire department.  
Page 20  
(c) Response to alarms.  
(d) Isolation of fire.  
(e) Evacuation of building.  
(f) Closure of bedroom doors and corridor access doors upon exiting.  
(g) Use of fire extinguishers.  
32.7.1.2 The proper protection of adult foster care facility residents shall require the  
prompt and effective response of staff members. The basic response required of staff  
shall include the removal of all occupants directly involved with the fire emergency,  
transmission of an appropriate fire alarm signal to warn other building occupants and  
summon staff, confinement of the effects of the fire by closing doors to isolate the fire  
area, and evacuation of residents as detailed in the fire safety plan.  
32.7.2.4 Deleted.  
32.7.3.1 Emergency egress and relocation drills shall be conducted not less than once  
per quarter per scheduled shift; daytime, 7 a.m. to 3 p.m., evening, 3p.m. to 11 p.m., and  
night, 11 p.m. to 7 a.m.  
32.7.3.5 Deleted.  
32.7.3.6 Deleted.  
32.7.4.1.1 Smoking regulations shall include the following:  
(1) Smoking shall he prohibited in any room, compartment, or area where flammable or  
combustible liquids, combustible gases, or oxygen is used or stored and in any other  
hazardous location. Both of the following also shall apply:  
(a) Signs shall be posted with signs that read “NO SMOKING” or bear the international  
symbol for no smoking. Sign letters shall be not less than 2 inches (5.08 cm) high and ¼  
inch (635 cm) wide stroke.  
(b) In residential board and care facilities where smoking is totally prohibited and signs  
so indicating are placed at all major entrances, secondary signs with language that  
prohibits smoking are not required.  
(2) Smoking by residents classified as not responsible with regard to their ability to  
safely use and dispose of smoking materials shall be prohibited, unless the resident is  
under direct supervision by staff or by a person approved by the administration. In such a  
case, smoking may be permitted.  
(3) Smoking materials shall not be provided to residents nor maintained by residents  
without the approval of the administration.  
(4) Areas where smoking is permitted shall be clearly identified.  
(5) Ashtrays of noncombustible material shall be provided and required to be used in all  
areas where smoking is permitted.  
(6) Self-closing cover devices into which ashtrays may be emptied shall be made  
available to all areas where smoking is permitted, and shall be required to be used.  
32.7.4.3 Smoking shall be permitted in a designated location only. Smoking in resident  
or staff bedrooms or in stairwells, exit corridors, and fire escapes is prohibited.  
32.7.5.1.1 These requirements are applicable only to new draperies, curtains,  
upholstered furniture, and mattresses. The term “new” means unused, normally via  
procurement from the marketplace, either by purchase or donation of items not  
previously used. If a facility purchases contract furniture, then such new, unused  
furniture, whether purchased or received as a donation, is regulated by section 32.7.5.2.  
Page 21  
32.7.5.2.2 Upholstered furniture belonging to residents shall not be required to be tested,  
provided that a smoke alarm is installed in such rooms.  
32.7.5.3 New mattresses within board and care homes shall be tested for rates of heat  
release in accordance with 10.3.4. Mattresses manufactured and sold within the United  
States shall pass testing per 16 CFR 1632 (FF4-72), “Standard for the Flammability of  
Mattresses and Mattress Pads.”  
32.7.5.3.2 Mattresses belonging to residents in sleeping rooms shall not be required to  
be tested, provided that a smoke alarm is installed in such rooms.  
32.7.6 Staff shall be on duty and in the facility at all times when residents are present.  
History: 1994 AACS; 2012 AACS.  
R 400.18202 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18203 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18204 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18205 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18206 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18207 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18208 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 22  
R 400.18209 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18210 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18211 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18212 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18213 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18214 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18215 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18216 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18217 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18218 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 23  
R 400.18219 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18220 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18221 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18222 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18223 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18224 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18225 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18226 Rescinded.  
History: 1994 AACS; 2012 AACS.  
PART 3. EXISTING SMALL AND LARGE ADULT FOSTER CARE  
FACILITIES LICENSED ON  
OR  
BEFORE MARCH 27, 1980; EXISTING SMALL AND LARGE ADULT  
FOSTER CARE FACILITIES  
LICENSED ON OR BEFORE MARCH 27, 1980, AND RELICENSED  
BEFORE JULY 2, 1991  
R 400.18301 Application.  
Page 24  
Rule 301. This part applies to all existing small and large adult foster care facilities  
licensed on or before March 27, 1980, and existing small and large adult foster care  
facilities licensed on or before March 27, 1980, and relicensed before July 2, 1991.  
History: 1994 AACS.  
R 400.18302 Home environment.  
Rule 302. (1) A group home shall be constructed, arranged, and maintained  
to adequately provide for the health, safety, and well-being of occupants.  
(2) All occupied rooms shall be of standard lath and plaster construction or  
equivalent.  
History: 1994 AACS.  
R 400.18303 Living areas.  
Rule 303. Traffic to and from any room shall not be through a resident's bedroom.  
History: 1994 AACS.  
R 400.18304 Bedrooms.  
Rule 304. (1) A room shall not be used as a bedroom where more than 1/2 the  
room height is below grade, except where the ceiling of such portion of a building is  
located 5 feet or more above grade for more than 25% of the perimeter measurement of  
the building. Such acceptable bedrooms shall have 2 acceptable means of egress.  
(2) Bedrooms for residents shall be separated from halls, corridors, and other  
rooms by floor-to-ceiling walls that do not have any openings other than doorways.  
(3) Interior doorways of bedrooms occupied by residents shall be equipped  
with a side-hinged, permanently mounted door equipped with positive-latching  
hardware that will ensure opening of the door by a single motion, such as turning a  
knob or by pressing with normal strength on a latch.  
(4) Residents who have impaired mobility shall not sleep in, or be assigned to,  
bedrooms located above the first or main floor.  
(5) Bedrooms shall have at least 1 window. Bedrooms shall be well-  
ventilated and maintained at a comfortable temperature.  
(6) A single occupancy bedroom shall have not less than 70 square feet of usable  
floor space. Usable floor space is defined as floor space that is under a ceiling which is  
not less than 6 feet 6 inches in height.  
(7) A multioccupancy bedroom shall have not less than 65 square feet of usable  
floor space per bed and a maximum of 4 beds per bedroom. Usable floor space is  
defined as the floor space that is under a ceiling which is not less than 6 feet 6 inches in  
height.  
History: 1994 AACS.  
Page 25  
R 400.18305 Fire safety.  
Rule 305. (1) A group home shall be inspected and approved for fire safety  
before the accommodation of residents and at least annually, except that existing group  
homes shall not be required to remove residents for the purpose of the initial fire  
inspection. To meet these requirements, carpeting shall have been tested pursuant  
to criteria outlined in NFPA-255, ASTM-E-84, or UL-723, have a flame spread of not  
more than 75, and have a smoke development of not more than 200.  
(2) At a minimum, a group home shall be of ordinary construction, light platform  
frame. The home shall have a C classification interior finish or better.  
History: 1994 AACS.  
R 400.18306 Interior finishes and materials.  
Rule 306. (1) The alphabetical classification of finish materials is for flame spread,  
fuel contribution, and smoke development as determined by the tunnel test in  
accordance with the provisions of NFPA-255-1972, ASTM-E-84-1968, or UL-723-  
1971 and grouped as follows:  
Flame Fuel Smoke  
Class Spread Contributed Developed  
A 0-25 0-35 0-50  
B 26-75 36-75 51-125  
C 76-200 76-200 126-200  
(2) The same alphabetical classification is used for  
combustibility  
of  
prefabricated acoustical tile units only, pursuant to  
specifications SS-A-118B-1958.  
the  
provisions of federal  
(3) The documents referred to in subrules (1) and (2) of this rule may be purchased  
as follows:  
(a) NFPA-255-1972, from the National  
Batterymarch Park, Quincy, Massachusetts 02269, at the cost of 50 cents per page.  
(b) UL-723-1960, from Underwriters Laboratories, Incorporated, 333  
Pfingsten Road, Northbrook, Illinois 60662, at a cost of 20 cents per page.  
Fire  
Protection  
Association,  
(c) SS-A-118B-1958, from the State Fire Safety Board, 7150 Harris Drive,  
Lansing, Michigan 48913.  
(4) Paper, cardboard, asphalt paper, or other highly flammable material shall not  
be used for the interior finish of a group home.  
(5) Group homes accommodating 13 or more residents shall have  
a
complete, 100% coverage, underwriters laboratories-approved automatic fire detection  
system, including at least 1 manual pull station per floor level and basement, except in  
group homes protected completely with an approved automatic sprinkler system. A fire  
alarm detection system shall be a closed circuit, self-supervised, continuous-ringing  
system.  
History: 1994 AACS.  
Page 26  
R 400.18307 Smoke detection system.  
Rule 307. Sections 23-2.3.4.2 and 23-2.3.4.3 of the code are amended to read as  
follows:  
23-2.3.4.2. For small facilities, approved smoke detectors shall be installed in  
compliance with the provisions of national fire protection association pamphlet no.  
74, 1989 edition, standard for the installation, maintenance, and use of household fire  
warning equipment, which is adopted by reference in R 400.18314. Smoke detectors  
shall be powered from the building electrical system, shall be interconnected, and,  
when activated, shall initiate an alarm that is audible in all habitable areas. Smoke  
detectors shall be installed on all levels, including basements, but excluding crawl  
spaces and unfinished attics. Additional smoke detectors shall be installed for living  
rooms, dens, dayrooms, and similar spaces. A plug-in, cord-connected unit is not  
permitted.  
Exception no. 1: In buildings protected throughout by an approved supervised  
automatic sprinkler system that is in compliance with the provisions of section 23-  
2.3.5 of the code, as amended in R 400.18217, using quick-response or residential  
sprinklers, smoke detection equipment shall be required in compliance with either the  
provisions of this section or section 23-2.3.4.3 of the code, as amended in this part.  
Exception no. 2: Existing battery-powered smoke detectors, rather than building  
electrical service-powered smoke detectors, shall be acceptable where, in the opinion  
of the authority having jurisdiction, the facility has demonstrated testing, maintenance,  
and battery replacement programs that ensure the reliability of power to the  
smoke detectors. This exception shall expire 2 years from the effective date of these  
rules.  
23-2.3.4.3. For small facilities, each sleeping room shall be provided with an  
approved smoke detector that is installed in compliance with the provisions of national  
fire protection association pamphlet no. 74, 1989 edition, standard for the installation,  
maintenance, and use of household fire warning equipment, which is adopted by  
reference in R 400.18314.  
Smoke detectors shall be powered from the building electrical system, shall be  
interconnected, and, when activated, shall initiate an alarm that is audible in all habitable  
areas. A plug-in, cord-connected unit is not permitted.  
Exception no. 1: In buildings protected throughout by an approved supervised  
automatic sprinkler system that is in compliance with the provisions of section 23-  
2.3.5 of the code, as amended in R 400.18217, using quick-response or residential  
sprinklers, smoke detection equipment shall be required in compliance with either the  
provisions of this section or section 23-2.3.4.2 of the code, as amended in this part.  
Exception no. 2: Existing battery-powered detectors, rather than building electrical  
service-powered detectors, shall be acceptable where, in the opinion of the authority  
having jurisdiction, the facility has demonstrated testing, maintenance, and battery  
replacement programs that ensure the reliability of power to the smoke detectors.  
This exception shall expire 2 years from the effective date of these rules.  
History: 1994 AACS.  
R 400.18308 Exits.  
Page 27  
Rule 308. (1) A means of egress shall be considered the entire way and method  
of passage to free and safe ground outside a group home. Means of egress shall be  
maintained in unobstructed, easily traveled condition at all times. Where basements  
are regularly utilized for resident activities, there shall be 2 acceptable means of egress.  
Doors that form a part of a required means of egress shall be equipped with  
positive-latching, nonlocking-against-egress-type hardware, be not less than 30 inches  
in width, and ensure adequate egress for residents who require wheelchairs, including  
ramps where necessary.  
Exception: Special locking requirements complying with 5-2.1.6 are permitted  
if a facility complies with the following conditions:  
(a) The facility is equipped with a complete approved automatic sprinkler  
system in compliance with the provisions of section 7-7 of the code. A small facility  
with a sprinkler system in compliance with national fire protection association  
pamphlet no. 13D, 1991 edition, standard for sprinkler systems in one- and two-family  
dwellings and mobile homes, which is adopted by reference in R 400.18108, with a 30-  
minute water supply, and that has each habitable area and closet sprinklered with  
quick-response or residential sprinklers is also permitted. A large facility with a  
sprinkler system in compliance with national fire protection association pamphlet no.  
13R, 1991 edition, standard for sprinkler systems in residential occupancies up to  
and including 4 stories in height, which is adopted by reference in R 400.18108, and  
that has each habitable area and closet sprinklered with quick-response or residential  
sprinklers is also permitted.  
(b) The facility is equipped with self-closing or automatic closing devices on all  
bedroom doors in compliance with section 5-2.1.8.  
(c) The facility is equipped with a manual fire alarm system in compliance  
with section 7-6.  
(d) The facility is equipped with an approved smoke detection system  
in  
compliance with sections 23-2.3.4.3. Exceptions nos. 1 and 2 of 23-2.3.4.3 shall not be  
used with this exception.  
(2) The first floor of a group home shall have not less than 2 separate and  
independent means of egress leading to the outside. Where basements are regularly  
utilized for resident activities, there shall be 2 acceptable means of egress.  
(3) In homes housing fewer than 13 residents, the second stairway is not required;  
however, the primary stair shall be enclosed with partitions and doors equal in fire  
resistance to the standard partition construction of the building. Such stairway doors  
shall be equipped with approved self-closing devices and positive-latching,  
nonlocking-against-egress-type hardware. The enclosures shall be constructed and  
arranged so that effective fire and smoke separations between floors are provided or  
else each resident bedroom on the second floor or above shall be equipped with a  
minimum 1 3/4-inch thick solid core wood door.  
In homes housing 13 to 20 residents, at least 1 means of egress from each floor  
shall be directly to the outside or shall be through an enclosed stairway which is  
properly separated from exposure from the floor below and which exits directly to the  
outside at grade level.  
The required second means of egress shall be enclosed with partitions and doors  
equal in fire resistance to the standard partition construction of the building. The  
Page 28  
enclosures shall be constructed and arranged so that effective fire and smoke  
separations between floors are provided.  
(4) Group homes accommodating residents  
who  
regularly  
require  
wheelchairs shall be equipped with ramps located at primary and secondary means of  
egress. A ramp shall not exceed 1 foot of rise in 12 feet of run.  
(5) Stairway and other vertical openings shall be enclosed with partitions and  
doors equal in fire resistance to the standard partition construction of the building, if,  
at a minimum, the partition construction is standard lath and plaster or equivalent.  
Enclosures shall be constructed and arranged so that effective fire and smoke  
separations between floors will be effected or else each resident bedroom on the  
second floor or above shall be equipped with a minimum 1 3/4-inch solid core wood  
door.  
(6) Hardware in an occupied room shall be positive-latching and nonlocking-  
against-egress. In all facilities housing more than 12 residents, exterior doors shall  
swing in the direction of egress and be equipped with nonlatching-against-egress-type  
hardware.  
History: 1994 AACS.  
R 400.18309 Heating.  
Rule 309. (1) Except as provided in this rule, occupancies shall be heated by an  
approved heating plant. If the heating plant is located in the basement of a group  
home, standard building material shall suffice for the separation, which shall include at  
least a 1 3/4-inch solid wood core door or equivalent to create a floor separation  
between the basement and the first floor. If the heating plant is on the same level  
with the residents, the furnace room shall be separated from the remainder of the  
building with materials that will afford a minimum 1-hour protection enclosure. A  
permanent outside vent that cannot be closed shall be incorporated in the design of  
heating plant rooms so that adequate air for proper combustion is assured. Space  
heaters are prohibited.  
(2) Factory mutual and underwriters laboratories-approved, permanent, fixed-  
type electrical heating, such as recognized panel or baseboard fixed-type heating,  
may be utilized in any location. Where an American gas association (AGA)-approved  
sealed combustion wall heater has been installed in accordance with both the  
AGA and the manufacturer's recommendations, approval will be given if the unit is  
located on an outside wall, obtains combustion air directly from the outside, and  
vents products of combustion directly to the outside.  
(3) Flame-producing water heaters or incinerators shall be installed with the  
same protection as a heating plant.  
(4) The storage of combustible materials is prohibited in rooms containing  
the heating plant, water heater, or incinerator.  
History: 1994 AACS.  
R 400.18310 Fire extinguishers.  
Page 29  
Rule 310. A minimum of 1 5-pound multipurpose fire extinguisher or  
equivalent shall be provided for use in a group home on each occupied floor and in  
the basement.  
History: 1994 AACS.  
R 400.18311 Electrical service.  
Rule 311. Electrical service shall be maintained in a safe condition.  
Where conditions indicate a need for inspection, the electrical service shall be  
inspected by a qualified electrical inspection service and a copy of the inspection report  
shall be submitted to the department or its agents.  
History: 1994 AACS.  
R 400.18312 General safety.  
Rule 312. (1) Stairways shall have sturdy and securely fastened handrails  
that are not less than 30 inches, nor more than 34 inches, above the upper surface of the  
tread. Exterior stairways and porches shall have handrails on the open sides.  
(2) Scatter or throw rugs on hard finished floors shall have a nonskid backing.  
(3) Handrails and nonskid surfacing or strips shall be installed in showers and  
bath areas.  
(4) Sidewalks, fire escape routes, and entrances shall be kept free of any hazard,  
such as ice, snow, and debris.  
(5) Cooking appliances shall be suitably installed in accordance with approved  
safety practices. Where metal hoods or canopies are provided, they shall be equipped  
with filters that shall be maintained in an efficient condition and kept clean at all  
times.  
(6) A yard area shall be kept free from all hazards, nuisances, refuse, and litter.  
History: 1994 AACS.  
R 400.18313 Emergency preparedness.  
Rule 313. (1) A group home shall have a telephone. A group home shall have a  
written procedure to be followed in case of fire or medical emergency.  
Responsible employees and residents, to the best of their ability, shall be familiar  
with emergency planning and their responsibilities.  
(2) An emergency plan shall specify all of the following:  
(a) The persons to be notified.  
(b) The locations of alarm signals and fire extinguishers.  
(c) Evacuation routes.  
(d) Procedures for evacuating residents of limited mobility and visitors.  
(3) An emergency plan shall provide for not less than 4 fire drills per year.  
Page 30  
(4) The emergency plan, including appropriate telephone numbers, shall be  
prominently posted and made fully known to all residents and responsible  
persons and shall be reviewed annually.  
(5) Staff shall be trained to perform assigned tasks and be familiar with all fire  
fighting equipment.  
(6) Fire drills shall be conducted quarterly and a record of their performance  
shall be maintained. Evacuation planning shall include the possibility of the  
nighttime movement of patients.  
History: 1994 AACS.  
R 400.18314 Standards and codes adoption.  
Rule 314. The standards and codes specified in this rule are adopted by reference  
in these rules for existing small and large adult foster care facilities licensed on or  
before March 27, 1980, and existing small and large adult foster care facilities  
licensed on or before March 27, 1980, and relicensed before July 2, 1991. Copies of  
the adopted standards are available for inspection and distribution at the office of the  
State Fire Safety Board, Michigan Department of State Police Fire Marshal Division,  
7150 Harris Drive, Lansing, Michigan 48913. National Fire Protection Association  
documents are available from their offices at 1 Batterymarch Park, P.O. Box 9101,  
Quincy, Massachusetts  
02269-9101,  
telephone  
number 1-800-344-3555.  
Underwriters Laboratories, Inc., documents are available at 207 E. Ohio Street,  
Chicago, Illinois 60611. The costs of the standards as of the time of adoption of these  
rules are as indicated:  
Accident, Automotive and Burglary Protection Equipment Lists.  
Underwriters Laboratories, Inc., 1972 edition. Cost: $1.00.  
Directory--Part I Building Material List. Underwriters Laboratories, Inc.,  
January 1973. Cost: $2.00.  
Fire Protection Equipment List, Underwriters Laboratories.  
NFPA 10, 1972 edition, entitled "Portable Fire Extinguishers." Cost: 50 cents per  
page.  
NFPA 13, 1972 edition, entitled "Installation of Sprinkler Systems." Cost: 50  
cents per page.  
NFPA 14, 1971 edition, entitled "Standpipe and Hose Systems." Cost: 50 cents  
per page.  
NFPA 72A, 72B and 72D, 1972 edition, entitled "Proprietary, Auxiliary and  
Local Protective Signaling Systems." Cost: 50 cents per page.  
NFPA 74, 1989 edition, entitled "Standard for the Installation, Maintenance,  
and Use of Household Fire Warning Equipment." Cost: 50 cents per page.  
NFPA 82, 1972 edition, entitled "Incinerators, Rubbish Handling." Cost:  
50 cents per page.  
National Electric Code, 1971 edition, National Fire Protection Association.  
Cost: 50 cents per page.  
NFPA 90A, 1972 edition, entitled "Air Conditioning and Ventilating  
Systems." Cost: 50 cents per page.  
Page 31  
State of Michigan Fire Damper Clarification, 1972, Five Cities Association,  
Jackson, Michigan 49204. Cost: Single copy free.  
Uniform State Specification for Fire Escapes, Michigan Department of State  
Police, Fire Marshal Division, 7150 Harris Drive, Lansing, Michigan 48913.  
History: 1994 AACS.  
PART 4. EXISTING SMALL AND LARGE ADULT FOSTER CARE  
FACILITIES LICENSED  
AFTER MARCH 27, 1980  
R 400.18401 Application.  
Rule 401. Chapter 33, adopted by reference in Rule 102 of these rules is amended as  
follows: Sections 33.1.1.3, 33.1.1.4, 33.2.2.5.2, 33.2.2.5.5.1, 33.2.3.2, 33.2.3.2.2,  
33.2.3.2.3, 33.2.3.6.4, 33.3.1.1.1, 33.3.1.1.2, 33.3.2.2.2, 33.3.2.3.4, 33.3.3.3, 33.3.3.4.2,  
33.3.3.5.1.1, 33.6, 33.7.1.1, 33.7.1.2, 33.7.3.1, 33.7.5, 33.7.5.1, 33.7.5.2.1, 33.7.5.2.2,  
33.7.5.3, and 33.7.6 are amended, 33.2.2.6.4, 33.2.3.2.6, 33.2.3.2.7, 33.2.5.2.4,  
33.2.5.2.5, 33.3.2.2.3.1, 33.3.3.2.3, 33.3.3.2.4, 33.3.3.2.5, 33.3.3.2.6, 33.3.3.4.8.4, 33.6.1,  
33.6.2, 33.7.1.1, 33.7.1.1.1, 33.7.4.1.1, and 33.7.4.3 are added, and 33.2.3.6.1.4,  
33.3.2.3.3, 33.3.3.4.7, 33.3.3.4.8.2, 33.3.3.6.6.1, 33.7.2.4, 33.7.3.5, 33.7.3.6, and  
33.7.5.3.2 are deleted from this chapter as follows:  
(1) General requirements  
33.1.1.3. Chapter Sections. This chapter is divided into 5 sections as follows:  
(1) Section 33.1 — General Requirements  
(2) Section 33.2 — Small facilities (7-12 residents)  
(3) Section 33.3 — Large facilities (13 to 20 residents)  
(4) Section 33.4 — Suitability of an apartment building to house a board and care  
occupancy  
(5) Section 33.5 — Reserved  
(6) Section 33.6 — Basements  
(7) Section 33.7 — Operating features  
33.1.1.4 Conversions. For the purposes of this chapter, exceptions for conversions shall  
apply only for a change of occupancy from an existing residential or health care  
occupancy to an adult foster care facility. A change of licensee does not change the  
status of an existing facility to “new,” if the new license application is made not later than  
60 days of the previous license expiration date and the license category has not been  
changed, except as provided in MCL 400.721.  
(2) Small facilities  
33.2.2.5.2 Doors shall be swinging or sliding. Doors used as the means of escape shall  
be swinging. Exception: bathroom doors.  
Page 32  
33.2.2.5.5.1 Delayed-egress locks complying with 7.2.1.6.1 shall be permitted on exit  
doors only.  
33.2.2.6.4 Exterior stairs used as a means of escape, that exceed a vertical distance from  
grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with fire-resistive rated barriers, with all openings equipped with smoke-actuated  
automatic-closing or self-closing doors having a fire protection rating comparable to that  
required for the enclosure. Unprotected openings within 10 feet of exterior stairs less  
than 4 feet above grade shall be prohibited. Stairs shall comply with 7.2.2.5.3.  
33.2.3.2 Hazardous areas.  
33.2.3.2.2 Spaces requiring protection by 33.2.3.2.1 shall include, but shall not be  
limited to, areas for cartoned storage, food, or household maintenance items in wholesale  
or institutional-type quantities and concentrations, mass storage of residents’ belongings,  
furnaces, heating equipment, and furnace rooms.  
33.2.3.2.3 Areas containing approved, properly installed and maintained residential-type  
cooking and laundry equipment shall not be classified as hazardous areas solely on the  
basis of such equipment.  
33.2.3.2.6 Oxygen storage.  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
33.2.3.2.7 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive rated construction with all openings protected by not less than a 1-  
hour fire-resistive rated, B-labeled door and frame assembly.  
33.2.3.6.1.4 Deleted.  
33.2.3.6.4 Doors shall meet the following requirements:  
(1) Doors shall be provided with latches or other mechanisms suitable for keeping the  
doors closed.  
(2) No doors shall be arranged to prevent the occupant from closing the door.  
Page 33  
(3) Deleted.  
33.2.5.2.4 Fireplaces are prohibited.  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
33.2.5.2.5. Solid fuel-burning central heating appliances shall be in compliance with the  
provisions of sections 9.2.1 and 9.2.2 of the code, as amended, and NFPA pamphlet #  
211, 2003 edition, standard for chimneys, fireplaces, vents, and solid fuel-burning  
appliances, which is adopted by reference in R 400.18102.  
(3) Large Facilities  
33.3.1.1.1 Section 33.3 shall apply to residential board and care occupancies providing  
sleeping accommodations for 13 to 20 residents.  
33.3.1.1.2 Facilities having sleeping accommodations for 7 to 12 residents shall be  
evaluated in accordance with section 33.2.  
33.3.2.2.2 Doors in means of egress shall be as follows:  
(1) Doors complying with 7.2.1 shall be permitted.  
(2) Doors within individual rooms and suites of rooms may be swinging.  
(3) No door, other than those meeting the requirement of 33.3.2.2.2(4) or (5) shall be  
equipped with a lock or latch that requires the use of a tool or key from the egress side.  
(4) Delayed-egress locks in accordance with 7.2.1.6.1 shall be permitted, provided that  
not more than 1 device is located in any egress path.  
(5) Access controlled egress doors in accordance with 7.2.1.6.2 shall be permitted,  
provided that not more than 1 device is located in any egress path.  
(6) Doors located in the means of egress that are permitted to be locked under other  
provisions of chapter 33, other than those meeting the requirement of 33.3.2.2.2(4) or (5),  
shall have adequate provisions made for the rapid removal of occupants by means such as  
remote control of locks, keying of all locks to keys carried by staff at all times, or other  
such reliable means available to staff at all times.  
(7) Only 1 such locking device, as described in 33.3.2.2.2(6) shall be permitted on each  
door.  
33.3.2.2.3.1 Exterior stairs used as a means of egress, that exceed a vertical distance  
from grade of more than 4 feet shall be enclosed and separated from the remainder of the  
facility with 1-hour fire resistive barriers, with all openings equipped with smoke-  
actuated automatic-closing or self-closing doors having a fire protection rating  
comparable to that required for the enclosure. Unprotected openings within 10 feet of  
exterior stairs less than 4 feet above grade shall be prohibited. Stairs shall comply with  
7.2.2.5.3.  
33.3.2.3.3 Deleted.  
33.3.2.3.4 Corridors shall be not less than 36 inches (915mm) wide.  
33.3.3.2.3 Fireplaces are prohibited.  
Page 34  
Exception #1: Sealed, properly vented, UL listed open-flame appliances that are installed  
according to manufacturers’ specifications are permitted. Existing fireplaces in  
conversions shall be sealed off and made inoperable.  
Exception #2: permanently installed UL listed electric fireplaces installed in accordance  
with manufacturers’ instructions are permitted.  
33.3.3.2.2 (1) Boiler and heater rooms  
Boiler and heater rooms located in unoccupied basements are not subject to the one hour  
requirement of 33.3.3.2.2.  
33.3.3.2.4 Solid fuel-burning central heating appliances shall be in compliance with  
sections 9.2.1 and 9.2.2 of the code, as amended in this part, and NFPA pamphlet # 211,  
which is adopted by reference in 2.1 of the code, as amended by R 400.18102.  
33.3.3.2.5 Oxygen storage  
Oxygen used or stored in an adult foster care facility shall be in compliance with all of  
the following requirements:  
(a) A separate room shall be provided for the storage of oxygen and that room shall not  
be used for other storage or for any other use.  
(b) A room for the storage of oxygen shall be separated from the remainder of the  
building by a minimum of 1-hour fire-resistive rated construction.  
(c) A storage room or manifold enclosure for oxygen that has more than a 1,500-cubic  
foot manifold or cylinder capacity shall not be located below grade. The room shall have  
1 wall which is an outside wall of the building and which has a window that is not less  
than 6 square feet in area, 1 square foot of which shall be a permanently open louver for  
ventilation.  
(d) A provision shall be made for a rack or fastening to protect a cylinder from  
accidental damage or dislocation.  
(e) If the manifold or cylinder capacity of oxygen is more than 12,000 cubic feet, the  
oxygen shall be located, installed, and maintained in compliance with the provisions of  
national fire protection association pamphlet no. 50, 1990 edition, bulk oxygen systems at  
consumers' sites, which is adopted by reference in R 400.18108.  
(f) A 1-day supply of oxygen may be kept in the room where it is being used.  
(g) Smoking shall be prohibited in any room or compartment where oxygen is used or  
stored. Such areas shall be posted with "no smoking" signs. Sign letters shall be not less  
than 2 inches (5.08 cm) high and 1/4 inch (.635 cm) wide stroke.  
33.3.3.2.6 Garages shall be separated from the remainder of the facility by a minimum  
of 1-hour fire-resistive rated construction with all openings protected by not less than a 1-  
hour, B-labeled door and frame assembly.  
33.3.3.3 Interior finish. New interior finishes shall comply with this section.  
33.3.3.4.2 Initiation. The required fire alarm system shall be initiated by all of the  
following means:  
(1) Manual means in accordance with 9.6.2, unless there are other effective means, such  
as a complete automatic sprinkler or automatic detection system, for notification of fire as  
required.  
(2) Manual fire alarm box located at a convenient central control point.  
(3) Automatic sprinkler system, other than those not required by another section of this  
code.  
(4) Required detection system.  
Page 35  
33.3.3.4.7 Deleted.  
33.3.3.4.8.2 Deleted.  
33.3.3.4.8.4 Smoke detectors shall be required in all dwelling units, including sleeping  
rooms.  
33.3.3.5.1.1 In buildings not more than 4 stories in height, a sprinkler system complying  
the NFPA 13R, Standard for the installation of sprinkler systems in residential  
occupancies up to and including 4 stories in height, shall be permitted. Exception: An  
automatic sprinkler system in accordance with NFPA 13D, standard for the installation of  
sprinkler systems in 1- and 2-family dwellings and manufactured homes, shall be  
permitted for up to 16 residents.  
33.3.3.6.6.1 Deleted.  
(6) Basements.  
33.6. Basements.  
33.6.1. A basement shall not be used as a resident bedroom, unless it meets the  
definition of a “story above grade.”  
33.6.2. A basement that is used for resident activities shall have 2 remotely located  
means of escape separated by not less than 50% of the longest dimension of the floor, as  
practical. One of the means of escape shall exit directly to the outside at grade. The  
second means of escape may be the interior stairway that serves the first floor of the  
facility.  
(7) Operating procedures  
33.7.1.1 The administration of every residential board and care facility shall have in  
effect and available to all personnel, written copies of a plan for protecting all persons in  
the event of fire and for evacuating persons from the building to the designated point of  
safety. The plan shall include special staff response, including the fire protection  
procedures needed to ensure the safety of any resident, and shall be amended or revised  
whenever any resident with unusual needs is admitted to the home. All employees shall  
be periodically instructed and kept informed with respect to their duties and  
responsibilities under the plan, including the operation of fire alarm and other fire  
protection equipment. Such instruction shall be reviewed by the staff not less than every  
2 months. A copy of the plan shall be readily available at all times within the facility.  
The evacuation plan shall include provisions to protect residents who are either  
permanently or temporarily incapable of self-preservation. The evacuation plan shall be  
evaluated annually to ensure that all information is current and correct.  
33.7.1.1.1 The written fire safety plan shall provide for the following:  
(a) Use of alarms.  
(b) Transmission of alarm to fire department.  
(c) Response to alarms.  
(d) Isolation of fire.  
(e) Evacuation of building.  
(f) Closure of bedroom doors and corridor access doors upon exiting.  
(g) Use of fire extinguishers.  
Page 36  
33.7.1.2 The proper protection of adult foster care facility residents shall require the  
prompt and effective response of staff members. The basic response required of staff  
shall include the removal of all occupants directly involved with the fire emergency,  
transmission of an appropriate fire alarm signal to warn other building occupants and  
summon staff, confinement of the effects of the fire by closing doors to isolate the fire  
area, and evacuation of residents as detailed in the fire safety plan.  
33.7.2.4 Deleted.  
33.7.3.1 Emergency egress and relocation drills shall be conducted not less than once  
per quarter per scheduled shift; daytime, 7 a.m. to 3 p.m., evening, 3p.m. to 11 p.m., and  
night, 11 p.m. to 7 a.m. (consistent with AFC licensing and current rules in effect.)  
33.7.3.5 Deleted.  
33.7.3.6 Deleted.  
33.7.4.1.1 Smoking regulations shall include the following:  
(1) Smoking shall he prohibited in any room, compartment, or area where flammable or  
combustible liquids, combustible gases, or oxygen is used or stored and in any other  
hazardous location. Both of the following also shall apply:  
(a) Signs shall be posted with signs that read NO SMOKING or bear the international  
symbol for no smoking.  
(b) In residential board and care facilities where smoking is totally prohibited and signs  
so indicating are placed at all major entrances; secondary signs with language that  
prohibits smoking are not required.  
(2) Smoking by residents classified as not responsible with regard to their ability to  
safely use and dispose of smoking materials shall he prohibited, unless the resident is  
under direct supervision by staff or by a person approved by the administration. In such a  
case, smoking may be permitted.  
(3) Smoking materials shall not be provided to residents or maintained by residents  
without the approval of the administration.  
(4) Areas where smoking is permitted shall he clearly identified.  
(5) Ashtrays of noncombustible material shall he provided and required to he used in all  
areas where smoking is permitted.  
(6) Self-closing cover devices into which ashtrays may be emptied shall he made  
available to all areas where smoking is permitted, and shall be required to he used.  
33.7.4.3 Smoking shall be permitted in a designated location only. Smoking in resident  
or staff bedrooms or in stairwells, exit corridors, and fire escapes is prohibited.  
33.7.5 Furnishings, bedding, and decorations.  
33.7.5.1 These requirements are applicable only to new draperies, curtains, upholstered  
furniture, and mattresses. The term “new” means unused, normally via procurement from  
the marketplace, either by purchase or donation of items not previously used. If a facility  
purchases contract furniture, then such new, unused furniture, whether purchased or  
received as a donation, is regulated by section 33.7.5.2.  
Exception: If residents are allowed to bring an upholstered furniture item from the  
resident’s previous residence into the facility, then such an item is not new and is not  
regulated.  
33.7.5.2.1 New upholstered furniture within board and care homes shall be tested for  
rates of heat release in accordance with 10.3.3.  
Page 37  
33.7.5.2.2 Upholstered furniture belonging to residents in sleeping rooms shall not be  
required to be tested, provided that a smoke alarm is installed in such rooms.  
33.7.5.3 New mattresses within board and care homes shall be tested for rates of heat  
release in accordance with 10.3.4. Mattresses manufactured and sold within the United  
States shall pass testing per 16 CFR 1632 (FF4-72), Standard for the flammability of  
mattresses and mattress pads.  
33.7.5.3.2 Deleted.  
33.7.6 Staff. Staff shall be on duty and in the facility at all times when residents are  
present.  
History: 1994 AACS; 2012 AACS.  
R 400.18402 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18403 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18404 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18405 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18406 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18407 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18408 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 38  
R 400.18409 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18410 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18411 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18412 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18413 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18414 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18415 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18416 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18417 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18418 Rescinded.  
History: 1994 AACS; 2012 AACS.  
Page 39  
R 400.18419 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18420 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18421 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18422 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18423 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18424 Rescinded.  
History: 1994 AACS; 2012 AACS.  
R 400.18425 Rescinded.  
History: 1994 AACS; 2012 AACS.  
PART 5. NEW ADULT AND FOSTER CARE CONGREGATE FACILITIES  
R 400.18501 Application.  
Rule 501. New adult foster care congregate facilities shall comply with the health care  
facilities fire safety rules, R 29.1801 to R 29.1871.  
History: 1994 AACS; 2012 AACS.  
R 400.18502 Rescinded.  
Page 40  
History: 1994 AACS; 2012 AACS.  
PART 6. EXISTING ADULT FOSTER CARE CONGREGATE FACILITIES  
R 400.18601 Application.  
Rule 601. This part applies to existing adult foster care congregate facilities as  
defined by section 3(3) of Act No. 218 of the Public Acts of 1979, as amended, being  
S400.703(3) of the Michigan Compiled Laws.  
History: 1994 AACS.  
R 400.18602 Definitions.  
Rule 602. As used in this part:  
"Approved" means acceptable to the state fire marshal.  
"Automatic fire detection system" means at least  
a
local  
system  
incorporating labeled underwriters laboratories, incorporated, control units, with  
audible signal devices, thermostats, and associated instruments and devices listed  
by underwriters laboratories, incorporated, in its fire protection equipment list, and  
installed in accordance with the national fire protection association pamphlets nos.  
72A, 72B, and 72D, 1972 edition, proprietary, auxiliary, and local protective  
signaling systems which are adopted by reference in R 400.18659.  
"Automatic sprinkler system" means a sprinkler system that is installed in  
accordance with the provisions of national fire protection association pamphlet no.  
13, 1972 edition, sprinkler systems, which is adopted by reference in R 400.18659.  
"Authority having jurisdiction" means the Michigan department of state police,  
fire marshal division.  
"Basement" means that portion of a building which is below grade, but which is  
so located that the vertical distance from the grade to the floor is not more than the  
vertical distance from the grade to the ceiling; except that where the ceiling of  
such portion of a building is located 5 feet or more above grade for more than 25% of  
the perimeter measurement of the building or part of the building affected, it shall be  
classed as a first story.  
"Building" means a congregate facility occupied by residents.  
"Cellar" means that portion of a building which is partly below grade, but which  
is so located that the vertical distance from the grade to the floor is greater than the  
vertical distance from the grade to the ceiling.  
"Combustible" means the opposite of noncombustible.  
"Department" means the Michigan department of state police, fire marshal  
division.  
"Director" means the state fire marshal.  
"Existing" means a facility constructed and licensed before February 1, 1975.  
"Exit" means a way of departure from the interior of a building or structure to  
a street or to an open space that provides safe access to a street. An exit may comprise  
vertical and horizontal means of travel, such as doorways, stairways, ramps, corridors,  
passageways, and fire escapes, including all of the elements that are necessary for an  
Page 41  
emergency escape from the building or structure. An exit begins at a doorway or other  
point of access to an exit from which occupants may proceed to the exterior of the  
building or structure with reasonable safety.  
"Fire alarm system" means, at a minimum, a local system that incorporates  
control units, audible signal devices, thermostats, and associated instruments and  
devices listed by underwriters laboratories, incorporated, in its fire protection  
equipment list, and installed in accordance with the 1972 edition of the national  
fire protection association pamphlet nos. 72A, 72B, and 72D, proprietary, auxiliary,  
and local protective signaling systems, which are adopted by  
400.18659.  
reference  
in  
R
"Fire doors" means doors constructed in accordance with the 1970 edition of the  
national fire protection association pamphlet no. 80 entitled, standard for the  
installation of fire doors and windows, which is adopted by reference in R 400.18659  
and labeled in accordance with the listing of underwriters laboratories, incorporated.  
"Fire resistant construction" means a building that has all walls, ceilings,  
floors, partitions, and the roof made of noncombustible materials, such as stone,  
brick, tile, concrete, gypsum, steel, or similar noncombustible materials. Structural  
members shall be of such assembly or be protected by material that will afford a fire-  
resistance rating of 1 hour or more.  
"Fire resistance rating" means materials or an assembly of materials that shall  
afford a rating as prescribed in the 1964 edition, as amended, of the fire resistance rating  
pamphlet published by the national board of fire underwriters or as prescribed in  
the listings of underwriters laboratories, incorporated, building materials list.  
"Flameproof" or "flameproofing" means materials that do not readily ignite or  
propagate flame under test  
conditions.  
Flameproofed  
materials usually are  
combustible materials that have been treated or coated to modify their burning  
properties.  
"Inspecting authority" means the state fire marshal.  
"New" means an existing facility licensed and constructed between February  
1, 1975, and the effective date of these rules. It also includes any addition and  
remodeling to a building after February 1, 1975, and the effective date of these rules.  
"Noncombustible" means any of the following:  
(a) A material that will not ignite and burn when subjected to fire. A material that  
liberates flammable gas when heated to a temperature of 1,380 degrees Fahrenheit  
for 5 minutes is not considered noncombustible.  
(b) A material which has a structural base of noncombustible material as defined  
in subdivision (a) of this rule and which has a surfacing that is not more than 1/8-inch  
thick and that has a flame spread rating of not more than 50 in compliance with the  
provisions of R 400.18639.  
(c) A material, other than a material described in subdivision (a) or (b) of this  
rule, which has a surface flame spread rating of not more than 25 in compliance with the  
provisions of R 400.18639 without evidence of continued progressive combustion  
and which is of such composition that surfaces that would be exposed by cutting  
through the material in any way would not have a flame spread rating of more than 25  
without evidence of continued progressive combustion.  
Page 42  
"Panic hardware" means hardware that is listed as panic hardware in the accident,  
automotive, and burglary protection equipment lists, 1972, of underwriters  
laboratories, incorporated, adopted by reference in R 400.18659.  
"Plenum" means an air compartment or chamber to which 1 or more ducts are  
connected and which forms part of an air distribution system.  
"Protected ordinary construction" means a type of construction in which exterior  
bearing walls are made of masonry, roofs and interior framing are made of wood or  
other combustible material that is protected so as to afford at least a 1-hour-fire  
resistance rating, and the ceilings are attached unfurred directly to the underside of  
the roof joists without an attic or open space above the ceiling joists.  
"Story" means that part of a building between a floor and the floor or roof next  
above. The first story shall be the lowest story of a building, the ceiling of which is  
located 5 feet or more above grade for more than 25% of the perimeter measurement  
of that story. Other stories shall be referred to by numerical designations in their  
order above the first story.  
"Wired glass" means glass which is not less than 1/4-inch thick, which is  
reinforced with wire mesh, no. 24 gauge or heavier, and which has openings that  
are not larger than 1 inch square.  
History: 1994 AACS.  
R 400.18603 General provisions.  
Rule 603. (1) Any person or his or her authorized agent who is confronted  
with practical difficulties in complying with these rules may apply to the director, in  
writing, for modification of the rules. Only a modification that will not constitute a  
definite hazard to life or property shall be considered. The decision of the director,  
including the particulars of any such application, shall be entered upon the records of  
the department and a signed copy thereof sent to the applicant.  
(2) A congregate facility shall be inspected and approved for fire safety at least  
annually.  
(3) Electrical plans and specifications shall be approved by the local electrical  
inspection authority, where available, or by the inspection services of the state  
electrical administrative board. The authority shall issue a final certificate of  
compliance covering the installation. A copy of the certificate shall be provided to the  
state fire marshal.  
History: 1994 AACS.  
R 400.18604 Home environment.  
Rule 604. (1) A congregate facility shall be constructed, arranged, and maintained  
to adequately provide for the health, safety, and well-being of occupants.  
(2) All occupied rooms shall be of standard lath and plaster construction or  
an equivalent.  
History: 1994 AACS.  
Page 43  
R 400.18605 Traffic restriction.  
Rule 605. Traffic to and from any room shall not be through a resident's bedroom.  
History: 1994 AACS.  
R 400.18606 Bedrooms.  
Rule 606. (1) A room shall not be used as a bedroom if more than 1/2 of the room  
height is below grade, except where the ceiling of such portion of a building is located 5  
feet or more above grade for more than 25% of the perimeter measurement of the  
building.  
(2) Bedrooms for residents shall be separated from halls, corridors, and other  
rooms by floor-to-ceiling walls that have no openings other than doorways.  
(3) Interior doorways of bedrooms occupied by residents shall be equipped  
with a side-hinged, permanently mounted door that is equipped with positive-  
latching hardware that will ensure the opening of the door by a single motion, such as  
turning a knob or by pressing with normal strength on a latch.  
(4) Residents who have impaired mobility shall not sleep in, or be assigned to,  
bedrooms located above the first or main floor.  
(5) A bedroom shall have at least 1 window. A bedroom shall be well-  
ventilated and maintained at a comfortable temperature.  
(6) A single-occupancy bedroom shall have not less than 80 square feet of usable  
floor space (70 square feet for existing facilities). Usable floor space is defined as the  
floor space that is under a ceiling that is not less than 6 feet 6 inches in height.  
(7) A multioccupancy bedroom shall have not less than 70 square feet of usable  
floor space per bed (65 square feet for existing facilities) and have a maximum of 4  
beds per bedroom. Usable floor space is defined as the floor space that is under a  
ceiling that is not less than 6 feet 6 inches in height.  
History: 1994 AACS.  
R 400.18607 General safety.  
Rule 607. (1) Scatter or throw rugs on hard finished floors shall have a nonskid  
backing.  
(2) Handrails and nonskid surfacing or strips shall be installed in showers and  
bath areas.  
(3) Sidewalks, fire escape routes, and entrances shall be kept free of any hazard,  
such as ice, snow, and debris.  
History: 1994 AACS.  
R 400.18608 Emergency preparedness.  
Rule 608. (1) A congregate facility shall have a telephone. A congregate facility  
shall have a written procedure to be followed in case of fire or medical emergency.  
Page 44  
Responsible employees and residents, to the best of their ability, shall be familiar  
with emergency planning and their responsibilities.  
(2) An emergency plan shall specify all of the following:  
(a) Persons to be notified.  
(b) Locations of alarm signals and fire extinguishers.  
(c) Evacuation routes.  
(d) Procedures for evacuating residents of limited mobility and visitors.  
(3) An emergency plan shall provide for no less than 4 fire drills per year.  
(4) The emergency plan, including appropriate telephone numbers, shall be  
prominently posted and made fully known to all residents, staff, and responsible  
persons and shall be reviewed annually.  
(5) Staff shall be trained to perform assigned tasks and be familiar with all fire-  
fighting equipment.  
(6) Fire drills shall be conducted quarterly and a record of their performance  
shall be maintained. Evacuation planning shall include the possibility of the  
nighttime movement of residents.  
History: 1994 AACS.  
R 400.18609 Storage restriction.  
Rule 609. A motor vehicle, gasoline-powered equipment, or other devices which  
may cause or communicate fire and which are not necessary for the treatment or care  
of residents shall not be stored within a congregate facility building. Devices and  
materials that need to be used in the building shall be used with reasonable care to  
provide safety from fire.  
History: 1994 AACS.  
R 400.18610 Roofing.  
Rule 610. A roof shall be covered with roofing that is made of spark-  
resistant material.  
History: 1994 AACS.  
R 400.18611 Egress facilities.  
Rule 611. (1) Each floor or story of every building shall have not less than 2  
separate and independent means of egress leading to the outside.  
Additional means of egress are required when the maximum possible  
occupancy is more than 100 residents per story. There shall be at least 1 additional  
means of egress for each 100 additional residents per story.  
There shall be a sufficient number of exits arranged so that it is not necessary to  
travel more than 100 feet from the door of a resident-occupied room to reach  
the nearest approved means of egress from that story.  
Page 45  
(2) Architectural treatment, mirrors, false windows, doors, or other decorations  
shall not give the appearance of doors or exits where no door or exit exists and shall not  
be placed so as to decrease the width of, or impair the use of, the exit. Nothing shall  
be placed or hung in front of an exit sign if it obstructs or prevents a clear view of the  
exit sign.  
(3) A corridor shall lead directly to the outside or to a required stairway that  
has direct egress to the outside through an approved exit door at grade which provides  
access to a public street. Only 1 required stairway may terminate in, and have egress  
directly across, a main floor entrance lobby that has ample approved means of egress  
to the outside.  
(4) An elevator shall not be approved as a required means of egress.  
(5) A corridor, stairway, or passageway to a means of egress shall not be used to  
house residents or for storage of any kind and shall not be obstructed or hidden  
from view by ornamentation, curtains, or other appurtenances.  
(6) A corridor barrier door, other than an approved smoke barrier door, shall be a  
double-action door only and shall not be secured by any device other than by a device  
that will permit opening the door in the direction of travel from either side with a normal  
push or pressure.  
(7) A congregate facility that accommodates residents who regularly require  
wheelchairs shall be equipped with ramps located at primary and secondary means of  
egress. A ramp shall not have more than 1 foot of rise in 12 feet of run.  
History: 1994 AACS.  
R 400.18612 Doors and doorways.  
Rule 612. (1) A doorway that is a part of a means of egress shall be at floor level.  
(2) A door, including a screen and storm door, that forms a part of an approved  
means of egress shall open in the direction of egress travel.  
This rule does not require a door from a resident-occupied room to open into a  
corridor, except that such a door shall not be hung so as to obstruct egress passage.  
There shall not be any obstruction at any time to the opening and closing of an  
egress door or a door from a resident-occupied room into a corridor.  
(3) In a building which does not have more than 2 levels, in which both levels exit  
at grade, and in which elevations between levels are not more than 4 feet, the building  
will be considered as 1 story and enclosures shall not be required between levels.  
(4) A revolving door shall not be approved as part of a means of egress.  
If a revolving door is installed, a side-hinged door that is in compliance with the  
provisions of this rule shall be installed within 15 feet of each revolving door.  
(5) A door that enters a stair shaft or other vertical opening shall not be held in an  
open position at any time by an under-door wedge or door-holding device.  
(6) A transom or other similar opening between a room and a corridor or passage  
is not permitted.  
History: 1994 AACS.  
Page 46  
R 400.18613 Rubbish handling and incinerators.  
Rule 613. (1) Rubbish handling and incinerators shall be in accordance with the  
provisions of the 1972 edition of the national fire protection association pamphlet no.  
82, entitled, incinerators, rubbish handling, which is adopted by reference in R  
400.18659. A rubbish chute, refuse bin, or room shall be in compliance with the  
provisions of pamphlet no. 82 for industrial-type incinerators. An approved 2-bushel  
or less gas incinerator may be placed in an approved furnace room and shall be  
equipped with approved automatic 100% shutoff controls, including a safety pilot. A  
feed door for an incinerator or rubbish chute shall not be permitted to be installed in  
any corridor or hallway that is used as a passageway to a means of egress. All such  
doors shall be located in an enclosed sprinklered room or compartment that is  
separated from other parts of the building by walls, a floor, and a ceiling that have  
a
fire-resistant rating of not less than 1 hour, and any opening to an enclosed  
sprinklered room or compartment shall be protected by a B-labeled fire door and a  
labeled fire door frame.  
(2) A rubbish chute shall extend not less than 4 feet above the roof and shall be  
covered by a metal skylight that is glazed with thin plain glass.  
A sprinkler head shall be installed at the top of a rubbish chute and within the  
chute at alternate floor levels in buildings that are more than 2 stories in height. A  
rubbish chute shall empty into a separate room, closet, or bin which is constructed  
of materials that have at least a 1-hour resistance to fire and that are protected  
with automatic sprinklers.  
(3) In new construction, incinerator rooms shall have at least 1 outside wall not  
open to a closed court.  
(4) A waste basket or receptacle shall be constructed with noncombustible  
material and, if the basket or receptacle has a capacity of more than 2 cubic feet or  
15 gallons, shall be equipped with a noncombustible cover.  
History: 1994 AACS.  
R 400.18614 Laundry.  
Rule 614. (1) In new construction, a laundry shall be located in a room that is  
constructed of materials, including the doors and frames, that have a 1-hour-fire-  
resistant rating and shall be protected with an approved automatic sprinkler system.  
In existing facilities, a laundry shall be located in a substantial enclosure, including  
the doors and frames, and may have less than a 1-hour-fire-resistant rating if  
acceptable to the inspecting authority.  
(2) A steam line shall be insulated with a noncombustible material and shall have  
a 1-inch clearance from combustibles.  
(3) A dryer shall be constructed of metal. A lint trap shall be cleaned frequently.  
(4) The use of any flammable liquid for cleaning, brushing, scouring, or scrubbing  
is prohibited.  
(5) A gas appliance shall have 100% safety shutoff controls.  
(6) Adequate air for combustion shall be provided in the laundry room.  
History: 1994 AACS.  
Page 47  
R 400.18615 Exit signs and illumination.  
Rule 615. (1) Each exit shall be marked by means of an electrically lighted exit  
sign that has letters which are not less than 3 3/4 inches in height on a background of  
contrasting color and which have strokes that are not less than 3/4 of an inch in width  
and shall be installed so that the sign is legible from the direction of travel toward  
the sign. If doorways and signs are not readily discernible from a resident's room  
doorway, an adequate number of additional electrically lighted directional signs shall  
be provided and shall have an arrow pointing in the direction of the exits.  
(2) Adequate equipment shall be provided in all facilities for the lighting, at all  
times, of corridors, stairways, outside fire escapes, and egress passages.  
(3) In new construction, the lighting required by this rule shall be installed on  
separate circuits which are in nonflexible metallic conduit and which are fused ahead  
of the main entrance switch and cutout.  
(4) In new construction, other wiring shall not be in the same raceway or conduit  
that serves the exit lights and emergency lighting.  
History: 1994 AACS.  
R 400.18616 Fire-extinguishing equipment.  
Rule 616. (1) A fire extinguisher shall be of a type listed by underwriters  
laboratories, incorporated.  
(2) A fire extinguisher shall be housed in a special cabinet or wall rack which is  
readily accessible at all times and which is located so that the top of the extinguisher is  
not more than 5 feet above the floor. The cabinet or the wall in the area of the wall  
rack shall be painted a distinguishing color.  
(3) An extinguisher shall be sized and located as prescribed in the 1972 edition of  
national fire protection association pamphlet no. 10, which is adopted by reference in  
R 400.18659.  
(4) A class A or ABC-type fire extinguisher shall be located in a corridor, a  
storage area for combustible materials, a shop, and a laundry.  
(5) A class B or ABC-type fire extinguisher shall be located in a heating plant  
room, a shop, a laboratory, and a kitchen.  
(6) A standpipe system shall be installed in a building that is more than 2 stories  
in height above the highest grade and that is more than 10,000 square feet in area in  
accordance with the provisions of national fire protection association pamphlet no. 14,  
1971 edition, standpipe and hose systems, which is adopted by reference in R  
400.18659.  
History: 1994 AACS.  
R 400.18617 Fire alarms.  
Rule 617. (1) A new or existing congregate facility shall be equipped with an  
approved electrically operated, closed circuit, self-supervised, local fire alarm system  
Page 48  
that has suitable signaling devices which will communicate the alarm of fire to the  
personnel on each floor of the building. A system shall also have approved actuating  
stations that are suitably located on each floor and in the basement so that it is not  
necessary to travel more than 100 feet from any room to reach a station on the same  
floor.  
(2) A telephone or other suitable means of communicating an alarm of fire to  
the fire department shall be provided. A pay station is not an approved means of  
sending an alarm.  
(3) An alarm shall be tested every 6 months and a record maintained of the test.  
(4) The electrical circuit that serves a fire alarm device shall be installed on a  
separate circuit and, in new construction, shall be installed in nonflexible metallic  
conduit and fused ahead of the main entrance switch.  
History: 1994 AACS.  
R 400.18618 Evacuation plan.  
Rule 618. An approved plan for the protection of residents in the event of fire and  
their evacuation from the building when necessary shall be formulated by the  
management. This plan shall be reduced to writing and posted in places conspicuous  
for personnel and staff who shall be instructed and kept informed regarding their  
duties under the evacuation plan.  
History: 1994 AACS.  
R 400.18619 Smoking.  
Rule 619. Smoking may be permitted where ashtrays made of noncombustible  
material are provided. An ashtray shall not be emptied in an open wastepaper  
container. A metal container that has a self-closing cover device shall be provided  
for the disposal of the contents of an ashtray.  
History: 1994 AACS.  
R 400.18620 Electrical wiring and equipment; oil and gas burners.  
Rule 620. (1) Electrical wiring and equipment shall be installed in accordance  
with the provisions of Act 217 of the Public Acts of 1956, as amended, being  
S338.881, et seq. of the Michigan Compiled Laws and the 1971 edition of the  
national electrical code which is adopted by reference in R 400.18659.  
(2) Only oil and gas burners that are approved by underwriters laboratories,  
incorporated, in its gas and oil equipment list, or by the American gas association shall  
be approved for use in facilities.  
History: 1994 AACS.  
Page 49  
R 400.18621 Chimneys and flues.  
Rule 621. (1) A furnace or other fired unit shall be vented by smoke pipes to a  
chimney which is constructed of brick, solid block masonry, or reinforced concrete,  
which has an approved flue lining, which is properly erected, and which is maintained  
in a safe condition. A bracket chimney is not permitted.  
(2) The provisions of subrule (1) of this rule do not prohibit the installation and  
use of any prefabricated chimney that bears the label of approval of underwriters  
laboratories, incorporated, if it is installed and used in accordance with the  
specifications of underwriters laboratories, incorporated.  
History: 1994 AACS.  
R 400.18622 Hot water heaters and storage tanks.  
Rule 622. (1) A hot water heater, other than an electrically heated heater or a  
booster heater for a dishwasher or for laundry purposes, shall be installed in the  
heating plant or in an enclosure of like fire-resistant construction and shall not  
be used for the storage of any combustible material.  
(2) A hot water storage tank shall be equipped with a safety device that prevents  
temperatures of more than 210 degrees Fahrenheit and pressures in excess of the  
maximum working pressure for which the tank is designed from being reached. Any of  
the following are acceptable safety devices:  
(a) An acceptable pressure relief valve that is combined with an energy cutoff  
approved by underwriters laboratories, incorporated, or  
association.  
the American gas  
(b) An acceptable pressure relief valve and an acceptable temperature relief  
valve of the spillage type.  
(c) An acceptable combined temperature-pressure relief valve of the spillage  
type.  
History: 1994 AACS.  
R 400.18623 Gas.  
Rule 623. (1) The installation, use, and maintenance of a gas appliance and gas  
piping shall be in accordance with the provisions of the 1969 editions of pamphlet  
no. 54, installation of gas appliance and gas piping, and pamphlet no. 54A, standards  
for the installation, maintenance and use of piping, appliances, and fittings for city gas,  
of the national fire protection association, which are adopted by reference in R  
400.18659.  
(2) A liquefied petroleum gas installation shall be in compliance with the  
provisions of Act 207 of 1941, as amended, being S29.1, et seq. of the Michigan  
Compiled Laws. When a gas supply line is placed in a tunnel, it shall be installed  
without joints and the tunnel shall have forced ventilation.  
History: 1994 AACS.  
Page 50  
R 400.18624 Cooking appliances.  
Rule 624. (1) A cooking appliance shall be suitably installed in accordance  
with approved safety practices.  
(2) Where a metal hood or canopy is provided over a main kitchen cooking  
appliance, the hood or canopy shall be equipped and designed in compliance with the  
provisions of the national fire protection association's pamphlet no. 96, 1971 edition,  
entitled standard for the installation of equipment for the removal of smoke and grease-  
laden vapors from commercial cooking equipment, which is adopted by reference in R  
400.18659.  
(3) A filter shall be maintained in an efficient condition and kept clean at all  
times.  
(4) Only vaporproof-type electrical wiring and equipment shall be permitted  
in a hood or canopy.  
(5) An exhaust duct from a hood shall be run to the outside by the shortest  
possible route and when run through an open space between a ceiling and a floor or  
roof or through a floor above, shall be enclosed in a horizontal or vertical shaft that is  
protected from the remainder of the building by construction which will afford a  
2-hour-fire resistance rating.  
History: 1994 AACS.  
R 400.18625 Aids for fire department service.  
Rule 625. (1) A proper driveway to the main building for fire department  
apparatus use shall be maintained free from all obstructions.  
(2) A copy of the plans of the building shall be submitted to the local fire  
department officials to enable them to become familiar with the floor plan of the  
building.  
History: 1994 AACS.  
R 400.18626 Abatement of fire hazard.  
Rule 626. Nothing in these rules prevents the abatement of fire hazards not  
specifically mentioned.  
History: 1994 AACS.  
R 400.18627 New construction, additions, remodeling, and conversions;  
compliance with certain rules.  
Rule 627. New construction, additions, remodeling, and buildings converted  
for the purpose of a congregate facility shall be in compliance with all of the  
requirements of R 400.18601 to R 400.18626 and the requirements of R  
400.18628 to R 400.18641.  
Page 51  
History: 1994 AACS.  
R 400.18628 Construction.  
Rule 628. A congregate facility constructed after the effective date of these rules,  
an addition made to a congregate facility after the effective date of these rules, and a  
building converted for use as a congregate facility after the effective date of these  
rules, shall be made of fire-resistant construction, except as follows:  
(a) The construction, addition, or conversion may be 1-hour protected ordinary  
construction, solid masonry exterior walls, wood joist and studding, if it is not  
more than 1 story in height without the basement or attic and if it is protected  
throughout with an approved automatic sprinkler system.  
(b) Forming materials that are left in place as a part of the permanent structure  
shall be noncombustible. The forming materials shall not be more hazardous than class  
A materials as defined in R 400.18639(3).  
(c) In a building where a fire-resistive ceiling constitutes an essential part of  
a floor or roof assembly to meet the required fire resistance rating, it shall be  
installed as tested and may have openings to accommodate noncombustible piping,  
ducts, or electrical outlets. The aggregate area of the openings in the ceiling shall not  
be more than 16 square inches for each 90 square feet of ceiling area, unless  
the equipment was a part of the test assembly. All ceiling duct openings shall be  
protected with fire dampers as tested in the assembly.  
(d) All alterations shall be in compliance with these rules.  
(e) This rule shall not apply to a building which is attached to a congregate  
facility and which is not used in any fashion for facility purposes if the building is  
separated from a congregate facility building by an unpierced fire wall that has not less  
than a 4-hour-fire-resistance rating. This rule shall not apply to buildings that are not  
used in any fashion for facility purposes if located to provide a horizontal outside  
separation by distance from the building in accordance with recognized standards.  
(f) Additions to existing sprinklered buildings shall be separated from the existing  
building by fire walls and B-labeled fire doors, unless the addition is sprinklered.  
(g) An unsprinklered addition to an existing unsprinklered  
building  
of  
combustible construction shall be separated from the existing building by not less than  
a 15-foot breezeway that has a 1-hour fire separation at either end of the breezeway.  
(h) During remodeling, alterations, or construction of additions, building  
openings that are exposed to construction operations shall be protected by  
noncombustible material. Remodeling, construction, or alterations shall not obstruct  
or render unusable any required means of egress. Where any required means of  
egress is obstructed or rendered unusable due to any remodeling, construction, or  
alteration,  
a
temporary means of egress shall be provided to assure the safety of  
occupants or else the area affected shall be vacated during such work.  
History: 1994 AACS.  
R 400.18629 Restricted location.  
Page 52  
Rule 629. A congregate facility building shall not be located within 300 feet of an  
aboveground storage tank which contains flammable liquids and which is used in  
connection with a bulk plant, marine terminal, aircraft refueling, or the bottling  
plant of a liquefied petroleum gas installation.  
History: 1994 AACS.  
R 400.18630 Egress facilities required.  
Rule 630. (1) A corridor or passageway from a resident bedroom or ward that  
leads to egress stairways and then to the outside, or to the outside from the first story,  
shall be not less than 5 feet in width.  
(2) A corridor and passageway that is considered as an approved means of egress  
shall be not less than 90 inches in height.  
(3) A resident-occupied room shall be located between approved means of egress.  
Exception no. 1: One room on each side of each end of a corridor that does not  
have more than 2 residents in each room. A door from a resident-occupied  
room shall not be more than 15 feet from an approved exit or stairway or egress  
directly to the outside at grade.  
Exception no. 2: One room at the end of a corridor that does not have more than 4  
residents. A door from a resident-occupied room shall not be more than 15 feet from  
an approved exit or stairway or egress directly to the outside at grade.  
(4) A resident bedroom that is located in an area between exits shall be of such  
dimensions that no part of the room is more than 30 feet to the room exit door, unless  
an approved secondary means of egress is provided.  
There shall be an aisle which is not less than 5 feet in width, which leads to the  
room exit or exits, and which is maintained free from any obstruction. There shall be  
not less than 3 feet in width of clear space from 1 side of each bed which is adjacent to  
the aisle.  
(5) A room shall be separated from a corridor with partition construction  
that extends to the floor or deck above or to a ceiling that is a part of a minimum 1-hour  
rated assembly which will afford not less than a 3/4-hour-fire-resistant rating. Any  
glass in  
such  
partitions, including doors, shall be 1/4-inch wired glass in steel  
framing, shall not exceed 1,296 square inches per opening, and shall not have a  
dimension of more than 54 inches.  
(6) Approved means of egress from above the first floor shall be through approved  
enclosed stairways only.  
(7) A resident-occupied room shall have at least 1 doorway that opens directly to  
the outside or to a corridor that has 2 separate and independent means of egress  
which lead to the outside without going through any other occupied room or space,  
except an approved lobby.  
History: 1994 AACS.  
R 400.18631 Inside stairways.  
Page 53  
Rule 631. (1) An inside stairway that forms an approved means of egress shall  
have suitable handrails on each side.  
(2) An inside stairway that forms an approved means of egress shall be not less  
than 44 inches wide in the clear. Handrails attached to walls shall not project into the  
required width of a stairway more than 3 1/2 inches at each side.  
(3) A stairway that forms an approved means of egress shall have treads that are  
not less than 9 1/2 inches wide, exclusive of the nosing, and risers that shall not be  
more than 7 3/4 inches in height. Treads and risers shall be of uniform width and  
height in each individual stairway.  
(4) An inside stairway which forms a means of egress which consists of 2 or more  
steps shall have stair treads of uniform width.  
(5) The maximum vertical distance between platforms or landings in any flight of  
stairs shall not be more than 9 feet.  
History: 1994 AACS.  
R 400.18632 Outside stairways.  
Rule 632. An outside stairway on new construction and on a conversion is not an  
approved means of egress.  
History: 1994 AACS.  
R 400.18633 Doors and doorways.  
Rule 633. (1) A door from a resident bedroom and a door that forms a part of an  
approved means of egress for residents shall be not less than 36 inches in width.  
(2) A door into a stairway enclosure and a door that serves other vertical  
openings shall be a B-labeled fire door in a fire door frame and shall be equipped with  
an approved self-closing device that is designed, installed, and maintained to close the  
doors automatically. The door shall be hung to allow for convenient manual opening and  
closing at all times.  
The door shall be maintained in a closed position and shall have a prominent  
sign on each side that states the following: "Keep Door Closed for Fire Safety."  
(3) An egress door from a resident-occupied room shall be equipped with  
positive-latching hardware that will ensure opening of the door by a single motion,  
such as turning a knob or by pressure on a latch using normal strength. A door that is  
provided or designated as an exit shall have anti-panic hardware that is listed by  
an approved independent, nationally-recognized testing laboratory such as factory  
mutual or underwriters laboratories, incorporated. The use of hooks and eyes, bolts,  
bars, and similar devices is prohibited on a door that is provided for exit purposes or  
that is designated as an exit.  
(4) A doorway that enters upon a common use corridor or egress  
passageway shall be protected by not less than a 1 3/4-inch solid wood core or  
approved hollow metal, side-hinged, swing-type door that is constructed to provide  
a reasonably smoketight enclosure.  
Page 54  
(5) A doorway from a resident bedroom and a door that forms a part of an  
approved means of egress shall be not less than 78 inches in height.  
History: 1994 AACS.  
R 400.18634 Stairways and other vertical openings.  
Rule 634. (1) An interior stairway shall be enclosed with material that has a fire  
resistance rating of not less than 1 hour. Other vertical openings through floors and  
ceilings, such as spaces around pipes, conduits, and ducts, shall be firestopped with  
noncombustible material.  
(2) An elevator or dumbwaiter shaft shall be  
completely  
enclosed  
by  
noncombustible materials with a fire-resistant rating of not less than 1 hour. Openings  
shall not be permitted through the sidewall enclosures for ventilation or any other  
purpose. A door and frame that services an elevator or dumbwaiter shall be  
approved fire door construction and shall be hung so as to be reasonably smoketight  
when the door is closed. A lintel or panels above the door shall be constructed to  
resist fire for 1 hour. Where necessary, the door shall have wired glass that is 1/4-  
inch thick and the glass shall not be more than 100 square inches.  
(3) There shall be no room doors or openings into stairways other than corridor  
access doors, except where a floor consists of a single open area, such as a large  
open ward floor.  
History: 1994 AACS.  
R 400.18635 Fire doors.  
Rule 635. (1) A fire door shall bear the underwriters laboratories, incorporated,  
or factory mutual label, be installed in a labeled fire door frame, and be equipped with a  
self-closer and a latching device.  
(2) A fire door shall not be equipped with any hold-open device. A B-labeled  
fire door shall be provided as follows:  
(a) In an opening into a vertical shaft, such as any of the following:  
(i) A stairwell, rubbish, or incinerator shaft.  
(ii) A laundry chute.  
(iii) A dumbwaiter shaft.  
(iv) A service shaft other than a ventilation duct opening.  
(b) In an opening into any of the following:  
(i) A storage room for ordinary combustible materials.  
(ii) A janitor room and closet.  
(iii) A linen room--both dirty and clean.  
(iv) A laundry room.  
(v) A heating plant room.  
(vi) A machine and fan room.  
(vii) A flammable liquid storage room.  
(viii) A receiving room.  
(ix) A laundry and rubbish bin room.  
Page 55  
(x) A laundry and rubbish chute feed room.  
(xi) A maintenance shop.  
(xii) A kitchen storage room.  
(xiii) An electrical service room.  
(xiv) A gas meter room.  
(c) An opening from a kitchen to required exit corridors in new construction.  
(d) Fire doors that are used in pairs without mullions shall be equipped with  
astragals and synchronizing closing devices. Astragals shall be made of not less than 10-  
gauge steel and shall be securely attached in place so as to project 3/4 of an inch.  
History: 1994 AACS.  
R 400.18636 Laundry chutes.  
Rule 636. (1) A laundry chute shall be enclosed in a shaft that is constructed of  
an assemblage of noncombustible materials which have not less than a 1-hour  
resistance to fire. If the shaft terminates within the building, the top shall be covered  
with noncombustible material that affords not less than a 1-hour resistance to fire.  
There shall be no openings into the shaft other than those necessary for the intended  
use of the laundry chute. An opening directly into the shaft shall be protected by a chute  
door normally utilized by the industry. The spaces between the chute and the shaft  
shall be filled in at each floor level with noncombustible material. A feed door  
for a laundry chute shall not be installed in any corridor or hallway that is used as a  
passageway to a means of egress. A feed door shall be located in an enclosed  
sprinklered room or compartment that is separated from other parts of the building by  
walls, a floor, and a ceiling that have a fire-resistant rating of not less than 1 hour.  
Openings to the room or compartment shall be protected by B-labeled fire doors in  
labeled fire door frames.  
(2) A sprinkler head shall be installed at the top of the chute and within the  
laundry chute at alternate floor levels in buildings that are more than 2 stories in  
height. A laundry chute shall empty into a separate room, closet, or bin that is  
constructed of materials which have not less than a 1-hour resistance to fire and shall  
be protected with automatic sprinklers.  
(3) If the shaft terminates through the roof of the building, the top may have an  
open vent. If not equipped with an open vent, the top of the shaft shall have a skylight.  
The skylight shall be glazed with ordinary glass that is 10% of the shaft area. If the  
sill of the window is not less than 2 feet above the roof level and not less than 10  
feet from any property line or other exposure on which it faces, the skylight may  
be provided with a window of equivalent construction and size which is set into the  
side of the shaft.  
History: 1994 AACS.  
R 400.18637 Heating plants.  
Rule 637. (1) Heating shall be only from an approved central heating plant or an  
approved permanently installed electrical heating system.  
Page 56  
(2) A heating plant shall be enclosed by walls, a floor, and a ceiling that have not  
less than a 1-hour resistance to fire and at least 1 wall shall be an outside wall that  
does not expose a closed court. A doorway or other opening through a required  
heating plant enclosure shall be protected by a B-labeled fire door in a labeled fire  
door frame, be installed so as to be reasonably smoketight, and be equipped with  
a self-closing device.  
(3) A heating plant room shall not be located beneath any portion of a building.  
This rule does not require the removal of an existing heating plant from beneath an  
existing congregate facility unless it is required in the interest of public safety. If it  
becomes necessary to expand the capacity of a heating plant to heat a congregate  
facility, the expansion shall not be permitted under any portion of the existing building.  
(4) A furnace room or heating plant enclosure shall be provided with approved  
air vents which are connected directly to the outside and which are sufficient in size to  
supply the required volume of  
air  
to  
support proper combustion. Adequate  
ventilation shall be provided directly to the outside from the ceiling of the heating  
plant enclosure to eliminate excessive temperature at all times.  
(5) A portable heating unit is not permitted.  
(6) A gas meter shall be located outside or in a room that is separated from other  
occupancies and exposures by not less than a 1-hour-rated enclosure that is vented  
to the outside. A gas meter may be in the heating plant room if it is located 5 or more  
feet from the heating unit.  
(7) A heating plant room shall not be utilized for the storage of combustibles  
or for a maintenance shop unless the room is protected with automatic sprinklers.  
History: 1994 AACS.  
R 400.18638 Air-conditioning and air-handling systems.  
Rule 638. (1) Air-conditioning, warm air heating, air-cooling systems, and  
ventilating systems shall be in compliance with the provisions of the national fire  
protection association pamphlet no. 90-A, 1972 edition,  
air conditioning and  
ventilating systems, which is adopted by reference in R 400.18659.  
(2) If power exhaust ventilation is to be used, there shall be an air supply equal  
to the amount exhausted, especially in areas that house combustion equipment.  
(3) Fans and air-handling equipment that are used for recirculating air in more than  
1 room or a single area shall be located in a room that is cut off from other portions of  
the building by construction that has a fire-resistant rating of not less than 1 hour,  
including fire dampers for duct openings, and a thermostatic device that has a setting  
of not more than 125 degrees Fahrenheit or an approved automatic smoke detector  
shall be located in the system at a suitable point in the return air duct ahead of the fresh  
air intake which, when activated, shall open the electrical circuit that supplies the  
fan motor. A fan room shall not be designed or used for any other use, except for  
housing other mechanical equipment.  
(4) If a duct system serves 2 or more floors, an approved fire damper shall be  
installed either at each direct outlet or inlet and in each branch duct at the junction  
with the main vertical duct or at each point where a floor is pierced.  
Page 57  
(5) If a duct pierces a smoke barrier or a wall or enclosure that is required to  
have a 1-hour-fire-resistance rating, then heat-actuated fire damper shall be  
a
installed. If a duct pierces a wall that is required to have a 2-hour-or-more-fire-  
resistance rating, a heat-actuated fire damper shall be installed on both sides of the  
wall opening through which the duct passes.  
(6) A required exit corridor shall not be used either as an exhaust plenum or as  
a return plenum chamber in a heating and ventilating system and an opening shall not  
be provided in separation walls or doors between rooms and corridors.  
(7) A duct or plenum space, whether for supply, return, or exhaust, shall be  
constructed of noncombustible materials. Space between a drop ceiling and the floor  
above, where the drop ceiling is protection for exposed steel, shall not be used as a  
plenum.  
(8) A heat-actuated fire damper shall be listed by an approved independent,  
nationally-recognized laboratory such as factory mutual or underwriters laboratories,  
incorporated.  
History: 1994 AACS.  
R 400.18639 Interior finish and materials.  
Rule 639. (1) Wall and ceiling finish materials throughout resident facilities  
shall not be more hazardous than class A, except for necessary wood doors and wood  
trim.  
(2) Folding-type partitions when used as separations in rooms or between rooms  
shall be made of noncombustible material, except that impregnated wood or other  
material that conforms to the criteria of a class B finish material is acceptable.  
(3) The alphabetical classification of finish materials is for flame spread, fuel  
contribution, and smoke development as determined by the tunnel test in accordance  
with the provisions of national fire protection association standard 255-1972, ASTM-  
E-84-1968, or UL-723-1973 and grouped as follows:  
Flame Fuel Smoke  
Class Spread Contributed Developed  
A 0 - 25 0 - 35 0 - 50  
B 26 - 75 36 - 75 51 - 125  
C 76 - 200 76 - 200 126 - 200  
(4) The same alphabetical classification is used for the combustibility of  
prefabricated acoustical tile units only, under federal specifications SS-A 118B-1958.  
(5) The documents referred to in subrules (3) and (4) of this rule are adopted by  
reference in this rule and may be purchased from the National Fire Protection  
Association, Batterymarch Park, Quincy, Massachusetts 02269, at a cost as of the  
time of adoption of these rules of 50 cents per page (NFPA 255-1972); the American  
Society for Testing and Materials, through University Microfilms International, 300  
N. Zeeb Road, Ann Arbor, Michigan 48106, at a cost as of the time of adoption of  
these  
rules  
of $14.75 (ASTM-E-84-1968); Underwriters  
Laboratories,  
Incorporated, 333 Pfingsten Road, Northbrook, Illinois 60062, at a cost as of the time  
of adoption of these rules of 20 cents per page (UL-723-1973); and SS-A-118B-  
Page 58  
1958 is available through the State Fire Safety Board, 7150 Harris Drive, Lansing,  
Michigan 48913.  
(6) Interior finish includes the exposed surfaces of walls, fixed or movable  
partitions, ceilings, and other exposed interior surfaces of buildings.  
(7) The classification of interior finish materials as to their flame spread and  
smoke development shall be that of the basic material used without regard to  
subsequently applied paint or other covering, except where paint or other covering is  
of such character or thickness or so applied as to materially affect the flame  
spread and smoke characteristics. Highly combustible material applications, such as  
lacquer or pyroxylin base materials, and unapproved wall coverings shall not be used.  
(8) Paints or coatings that contain plastics, polyesters, or epoxies may be used on  
noncombustible surfaces without proof of classification if they are not applied in excess  
of 8 mils total thickness.  
(9) Any new floor covering assembly shall be, at a minimum, a class B material.  
History: 1994 AACS.  
R 400.18640 Storerooms and closets.  
Rule 640. A room for the storage of combustible materials, including a janitor  
room and closet, a dirty and clean linen room, a receiving room, a kitchen storage  
room, and a maintenance shop, shall be separated from the remainder of the building  
by construction that has not less than a 1-hour-fire-resistance rating and shall be  
protected by automatic sprinklers.  
History: 1994 AACS.  
R 400.18641 Sprinkler protection.  
Rule 641. (1) For construction defined as protected ordinary construction,  
the entire new construction involved shall be protected throughout by an approved  
automatic sprinkler system.  
(2) If an adequate water supply from a community water system to supply a  
sprinkler system does not exist and if the area to be protected is not more than 20,000  
square feet, a special pressure tank supply for sprinklers as specified in the 1971  
edition of national fire protection association pamphlet no. 22, standard for water  
tanks for private fire protection which is adopted by reference in R 400.18659,  
shall be provided. The special pressure tanks shall contain 2,000 gallons of water in a  
3,000-gallon tank for partial systems and for complete building systems shall  
contain 3,000 gallons of water in a 4,500-gallon tank.  
(3) If an adequate water supply from a community system to supply a sprinkler  
system does not exist and if the total gross area to be protected is more than  
20,000 square feet, then the water supply shall be furnished by a gravity tank which  
has not less than a 30,000-gallon capacity and which is constructed as specified in  
the 1971 edition of national fire protection association pamphlet no. 22, standard for  
water tanks for private fire protection, which is adopted by reference in  
400.18659.  
R
Page 59  
(4) Complete shop drawings shall be submitted to the appropriate inspecting  
authority for approval before the installation of sprinklers.  
(5) A sprinkler system shall be equipped with a flow alarm that is electrically  
relayed to the fire alarm system of the building, except for sprinklers that are installed  
in accordance with the provisions of subrule (6) of this rule.  
(6) The sprinkler piping for any isolated hazardous area that can be adequately  
protected by not more than 2 sprinklers may be connected directly to the domestic  
water system at a point where a minimum 1-inch supply is available. An approved OS  
and Y valve and check valve shall be installed between the sprinklers and the  
connection to the domestic water supply. This method of sprinklering shall be used  
very conservatively.  
(7) A partial sprinkler system in new construction shall be designed to protect all  
of the following areas:  
(a) Heating plant rooms that house incinerators of more than a 2-bushel capacity.  
(b) Incinerator rooms.  
(c) Laundry rooms.  
(d) Storage rooms for combustible material, including janitor rooms and closets.  
(e) Clean and dirty linen rooms.  
(f) Receiving bins.  
(g) Laundry and rubbish chute feed rooms.  
(h) The tops and various levels, where required, of laundry and rubbish chutes.  
(i) Kitchen storage rooms.  
History: 1994 AACS.  
R 400.18642 Existing facilities.  
Rule 642. Existing licensed facilities shall be in compliance  
requirements of R 400.18601 to R 400.18626 and with the requirements of  
400.18643 to R 400.18659.  
with  
the  
R
History: 1994 AACS.  
R 400.18643 Sprinkler system required; exception.  
Rule 643. All existing congregate facilities, or portions thereof, that are made not  
of fire-resistant construction shall be protected by an approved automatic sprinkler  
system, except as follows:  
(a) An existing 1-story congregate facility which has a concrete floor, which does  
not have a basement, which, upon review, may be classified by an authorized inspection  
authority as protected ordinary construction, which has competent partitions and  
doors separating rooms from exit corridors, which has storage rooms that are  
segregated and protected, which is in compliance with other applicable features  
provided for in these rules, and which is entirely protected by an approved automatic  
fire detection system.  
Page 60  
(b) An existing congregate facility where residents occupy the first floor only, if  
other applicable features of these rules are complied with and the entire building is  
protected by an approved automatic fire detection system.  
(c) A building which is attached to a congregate facility building, and which is not  
used in any part for facility purposes, and which is separated from the facility  
building by an unpierced firewall that has not less than a 4-hour-fire-resistance rating.  
(d) A building that is not used in any part for home purposes when so located as  
to provide a horizontal outside separation by distance from the building in accordance  
with recognized standards.  
History: 1994 AACS.  
R 400.18644 Egress facilities required.  
Rule 644. (1) In an existing congregate facility building that is not more than 2  
stories in height, required additional means of egress from the second floor may be  
provided by approved outside stairways.  
(2) In an existing congregate facility building that is provided with outside  
stairways as required means of egress on the effective date of these rules shall not be  
required to replace the outside stairways if the stairways are in compliance with the  
requirements for existing fire escapes contained in these rules.  
(3) A corridor or passageway from a resident bedroom or ward that leads to egress  
stairways and then to the outside, or to the outside from the first story, shall be not less  
than 3 feet in width.  
(4) A corridor or passageway that is considered as an approved means of egress  
shall be not less than 78 inches in height.  
(5) In an existing congregate facility which is of fire resistant construction or  
which is protected by an approved sprinkler system where present exits are separated  
by not less than 50% of the longest dimension of the building, the housing of not more  
than 10 residents beyond a means of egress will be approved if there is no storage  
room, pharmacy, or other hazardous occupancy between the resident rooms and the  
means of egress and if the most remote resident room door is not more than 50 feet from  
the means of egress.  
(6) A resident bedroom that is located in an area between exits shall be of such  
dimensions that no part of the room is more than 30 feet from the room exit door, unless  
an approved secondary means of egress is provided for the room.  
(7) A room-to-corridor partition shall be of substantial standard construction  
and shall be reasonably smoketight.  
(8) Each story of every building used as a congregate facility shall have not  
less than 2 means of egress to the outside. Each resident-occupied room shall  
have at least 1 doorway that opens directly to the outside or to a corridor that leads  
directly or by stairway to the outside or shall have an opening without a door into 1  
adjacent room that has a means of egress directly to the outside.  
History: 1994 AACS.  
Page 61  
R 400.18645 Inside stairways.  
Rule 645. (1) An inside stairway that forms an approved means of egress shall  
have suitable handrails on each side.  
(2) An inside stairway that forms an approved means of egress shall be not less  
than 36 inches wide in the clear. Handrails attached to walls may project not more than  
3 1/2 inches at each side into the required width of a stairway.  
(3) A stairway that forms an approved means of egress shall have treads that are  
not less than 8 inches wide, exclusive of the nosing, and risers that are not more than 8  
1/2 inches in height. Treads and risers shall be of uniform width and height in each  
individual stairway.  
(4) An inside stairway which forms a means of egress which consists of 2 or more  
steps, and which, in changing direction, does so by benefit of the variance in the  
width along each tread shall not be approved. This rule does not prohibit a stairway  
with treads of uniform width throughout  
intermediate landings or platforms.  
that changes directions by benefit of  
History: 1994 AACS.  
R 400.18646 Existing fire escapes.  
Rule 646. An existing fire escape shall be in  
specifications for new fire escapes, except as follows:  
compliance  
with  
the  
(a) The fire escape shall be certified, in affidavit form, by an architect or  
structural engineer who attests to the fire escape's structural stability if so  
required by the appropriate inspecting authority.  
(b) Handrails shall not be lower than 27 inches above the forward edge of the tread.  
(c) Treads shall be not less than 8 inches, exclusive of nosing.  
(d) Risers shall be not more than 8 1/2 inches.  
(e) The vertical distance between platforms or landings in any flight of stairs shall  
not be more than 15 feet.  
(f) The width of stairs shall not be less than 36 inches.  
History: 1994 AACS.  
R 400.18647 New fire escapes.  
Rule 647. New fire escapes shall be constructed as follows:  
(a) Material may be steel or nominal 2-inch lumber.  
(b) Tubular and spiral slide-type escapes are not permitted.  
(c) An outside stairway that constitutes an approved means of egress shall be  
designed, constructed, and maintained to support a live load of 100 pounds per square  
foot on platforms and landings and a concentrated load of 400 pounds on stair treads.  
(d) Supporting members of platforms, landings, and stairs, which are in tension  
and are fastened directly to the building, shall pass through the wall and be fastened  
securely to the framework of the building. Where practicable, an outside  
stairway shall be self-supporting. A counter-balanced stairway is not permitted.  
Page 62  
(e) On an outside stairway, each landing or platform adjacent to an exit doorway  
of the building shall be not less than 3 inches, nor more than 8 inches, below the sill  
level of the doorway. Each landing or platform shall be at least the full width of the  
doorway it serves and its depth shall be not less than the width of the widest outside  
stairway that leads directly to or from it. The landings or platforms shall be designed  
and constructed so that exit doors, when open, will not decrease the  
unobstructed width of the platform or stairs.  
required  
(f) An outside stairway that is considered an approved means of egress shall lead  
to ground level and the last step in descent to the ground shall not exceed the height  
of the riser immediately above.  
(g) A ladder shall not be used as any portion of an approved means of egress.  
(h) An outside stairway shall be provided with handrails on both sides 36 inches  
above the forward edge of the tread. Not less than 2 rails shall be provided equidistant  
between the handrail and the forward edge of the tread.  
(i) Treads shall be not less than 9 1/2 inches wide, exclusive of nosing.  
(j) The tread or platform shall be covered with a suitable nonslip surface.  
(k) Treads shall include an additional width of 1 inch as nosing when stairs are  
constructed with risers.  
(l) The riser of a stairway shall be not more than 7 3/4 inches.  
(m) The maximum vertical distance between platforms or landings in any flight  
of stairs shall not be more than 12 feet.  
(n) The required width of a new outside stairway shall be not less than 44 inches.  
(o) An outside stairway that is part of an approved means of egress shall be  
protected against fire in the building by blank or closed walls which are directly under  
such stairways and which run for a distance of 6 feet in all other directions. Windows  
may be allowed within an outside stairway if each window is stationary, made of  
steel sash, and glazed with wired glass that is not less than 1/4 of an inch in thickness.  
(p) An outside stairway that is considered an approved egress passage and access  
therefrom to a public street or alley shall be maintained in a safe condition for its  
intended use at all times. A stairway that forms a part of an approved means of egress  
shall be maintained free from ice and snow at all times. There shall be no obstruction  
placed upon or within a stairway or an entrance thereto and there shall be no other  
waste material under or adjacent to the stairway.  
(q) When deemed necessary by the inspection authorities, a stairway shall be  
provided with an approved shelter against ice and snow.  
(r) When iron and steel fire escapes are constructed as part of an approved  
means of egress from a congregate facility, the balconies and stair treads shall be in  
compliance with this rule and shall be made up of 3/16-inch by 1-inch straight bars set  
on edge, spaced 1 inch apart from center to center.  
History: 1994 AACS.  
R 400.18648 Doors and doorways.  
Rule 648. (1) A doorway that leads to a fire escape shall be at floor level, except  
where a proper approved ramp is provided. A ramp shall not have more than 1 foot of  
rise in 12 feet of run.  
Page 63  
(2) A door from a resident bedroom and a door that forms a part of an approved  
means of egress shall be not less than 30 inches in width.  
(3) A door into a stairway enclosure and a door that serves other vertical  
openings shall be of equal fire-resistant rating as the partition in which they are  
installed and shall be equipped with  
approved self-closing devices that are  
designed, installed, and maintained to close the doors automatically. The doors shall be  
hung so as to allow for convenient manual opening and closing at all times. The  
doors shall be maintained in a closed position and shall have a prominent sign on  
each side that states the following: "Keep Door Closed for Fire Safety." Any glass in  
the doors shall be 1/4-inch wired glass and shall not be more than 6 square feet in  
area.  
(4) An egress door from a resident-occupied room shall be equipped with  
hardware that will ensure opening by a single motion, such as turning a knob or by  
pressure of a latch using normal strength. A door which is provided or designated as  
an exit and which gives egress directly to the outside shall be equipped with approved  
anti-panic hardware or a knob of a type that is nonlocking against egress. The use of  
hooks and eyes, bolts, bars, and similar devices is expressly prohibited on doors  
which are provided for exit purposes or which are designated as exits.  
(5) A doorway that enters upon a common use corridor or egress passage shall be  
protected by a substantially constructed side-hinged,  
constructed to provide a reasonably smoketight enclosure.  
swing-type door that is  
(6) An existing transom and any like opening in a corridor or passageway shall be  
permanently sealed and made fire-resistant equal to the fire-resistance rating of the  
related partition construction.  
History: 1994 AACS.  
R 400.18649 Stairways and other vertical openings.  
Rule 649. (1) In buildings of fire-resistant construction, an interior stairway shall  
be enclosed with material that has a fire-resistance rating of not less than 1 hour. In  
buildings of wood joist construction an interior stairway shall be enclosed  
with material having 1/2-hour-fire-resistance rating. One quarter-inch wired glass in  
a steel frame meets the 1/2-hour requirement.  
(2) An elevator or dumbwaiter shaft shall be  
completely  
enclosed  
by  
noncombustible materials that have a fire-resistance rating of not less than 1 hour. An  
opening shall not be allowed through the side wall enclosures for ventilating or  
other purposes. A door that services an elevator or dumbwaiter shall be of solid  
construction, be reasonably smoketight when closed, and shall be constructed to resist  
fire for 1 hour.  
Exception: A door in an elevator may have wired glass that is not more than 6  
square feet.  
History: 1994 AACS.  
R 400.18650 Closets and storerooms.  
Page 64  
Rule 650. A closet or storeroom for the storage of ordinary combustibles shall be  
in compliance with the congregate facility requirements, except that the room shall be  
separated from the remainder of the building by construction that has not less than a  
1/2-hour-fire-resistance rating.  
History: 1994 AACS.  
R 400.18651 Rubbish handling and incinerators.  
Rule 651. An incinerator and rubbish handling shall be in compliance with the  
provisions of R 400.18613 or else use of the incinerator or the handling of rubbish  
shall be discontinued and all chute openings shall be permanently sealed.  
History: 1994 AACS.  
R 400.18652 Laundry chutes.  
Rule 652. A laundry chute shall be in compliance with the provisions of R  
400.18614, except that where an existing laundry chute drop opening is properly  
protected with a qualified laundry chute door and is fed from a corridor or other room,  
the chute drop opening shall not be required to be placed in a specially designed room  
or compartment.  
History: 1994 AACS.  
R 400.18653 Interior finish.  
Rule 653. (1) An interior finish shall be a class A or B finish, except that an  
interior finish in an individual room may be a class C finish for walls only.  
(2) A combustible finish material shall be applied to, or be furred out not more  
than 1 inch from, a noncombustible surface behind which the space is firestopped into an  
area that extends not more than 8 feet in any direction.  
(3) If a combustible interior finish comprises more than 10% of the aggregate  
wall and ceiling surface of any room or space, and if the finish material is more  
hazardous than permitted in the provisions of subrule (1) of this rule, then the  
combustible interior finish may be treated so as to comply with the provisions of  
subrule (1) of this rule, if the material is secured to the walls or ceilings as specified in  
subrule (2) of this rule.  
(4) If interior finish is more hazardous than class A, and if it is furred more than  
1 inch from a noncombustible wall or ceiling surface, it shall be replaced with a  
noncombustible material or reinstalled to comply with the provisions of subrules (1),  
(2), and (3) of this rule.  
(5) Existing wood paneling or combustible acoustical interior finish in lobbies,  
waiting rooms, and office areas in existing buildings may remain if the rooms or areas  
are separated from the rest of the building by proper walls and fire doors.  
Page 65  
(6) In a completely sprinklered building where the basic material is class C and  
is installed to comply with the provisions of subrules (1), (2), (3), and (4) of this  
rule, further treatment is not required.  
However, where the basic material is more hazardous than class C and is installed  
to comply with the provisions of subrules (1), (2), (3), and (4) of this rule, it shall be  
surface treated on its exposed side whether or not the building is sprinklered.  
(7) Class C interior finish in the form of wainscoting which extends not more than  
5 feet above the floor and which is installed to comply with the provisions of subrules  
(1), (2), (3), and (5) of this rule, shall not be required to be surface treated.  
(8) Interior finish means the exposed interior surfaces of buildings including,  
but not limited to, fixed or moveable walls and partitions, columns, and ceilings.  
Doors, trim, the backing of shelving, cabinets, and wardrobes shall be included in the  
10% permissible class C finish category.  
(9) The classification of interior finish materials as to their flame spread and  
smoke development shall be that of the basic material used without regard to  
subsequently applied paint or other covering, except where the paint or other  
covering is of such character or thickness or so applied as to materially affect the  
flame spread and smoke characteristics. Highly combustible material applications,  
such as lacquer or pyroxylin base materials, or unapproved wall coverings shall not be  
used.  
(10) Paints or coatings that contain plastics, polyesters, or epoxies may be used  
on noncombustible surfaces without proof of classification if they are not applied in  
excess of 8 mils total thickness.  
History: 1994 AACS.  
R 400.18654 Cooking appliances.  
Rule 654. (1) A cooking appliance shall be suitably installed in accordance  
with approved safety practices.  
(2) A metal hood or canopy that is provided over a main kitchen cooking  
appliance shall be equipped and designed in compliance with the provisions of the  
national fire protection association pamphlet no. 96, 1971 edition, entitled standard  
for the installation of equipment for the removal of smoke and grease-laden vapors  
from commercial cooking equipment, which is adopted by reference in R 400.18659.  
(3) Filters shall be maintained in an efficient condition and kept clean at all times.  
(4) Only vaporproof-type electrical wiring and equipment shall be permitted  
in hoods or canopies.  
(5) An exhaust duct from a hood shall be run to the outside by the shortest  
possible route and, when run through open spaces between a ceiling and a floor or  
roof or through any floors above, shall be enclosed in a horizontal or vertical shaft that is  
protected from the remainder of the building by construction that will afford a 2-  
hour-fire-resistance rating.  
History: 1994 AACS.  
Page 66  
R 400.18655 Heating plants.  
Rule 655. (1) In an existing facility, the central heating plant shall be segregated in  
a room that has walls, a ceiling, and a floor constructed of materials which have not less  
than a 1-hour-fire-resistance rating.  
(2) A doorway or other opening through a required enclosure for a heating  
plant shall be constructed of materials which have not less than a 1-hour-fire-resistance  
rating which are hung so as to be reasonably smoketight and which are equipped  
with adequate self-closing devices.  
(3) A furnace room or enclosure shall be provided with an air vent which is directly  
to the outside and which is sufficient to admit the required volume of air to support  
proper combustion. An air vent shall be open at all times. A vent may be protected by  
louvers or other approved devices.  
(4) A gas or electric meter shall not be permitted within 5 feet of the heating  
plant.  
(5) A space heater is not permitted in any congregate facility.  
History: 1994 AACS.  
R 400.18656 Air-conditioning and air-handling systems.  
Rule 656. (1) If power exhaust ventilation is to be used, there shall be an air supply  
equal to the amount exhausted, especially in areas that house combustion equipment.  
(2) Fan and air-handling equipment used for recirculating air in more than 1  
room or a single area shall be located in a room that is cut off from other portions of  
the building by construction that has not less than a 1-hour-fire-resistance rating. A room  
that houses fans and air-handling equipment shall not be used for any combustible  
storage.  
(3) A duct or plenum which employs mechanical means for the movement of air  
and which is used for heating and ventilation, including warm air heating systems,  
plain ventilating systems, air-conditioning systems, or exhaust systems, shall be  
constructed entirely of noncombustible material.  
If a duct or plenum of an existing system is constructed, wholly or in part, of  
combustible materials, it shall be  
reconstructed  
entirely  
of noncombustible  
materials, if possible. If revamping or reconstruction is impractical due to design or  
construction, the inspecting authority may accept the existing installation if heat-  
actuated fire dampers are installed in each return air duct opening from every room or  
space.  
(4) A heat-actuated fire damper shall be installed on the discharge side of each  
recirculating fan unit that serves more than 1 room or a single area and, where  
practicable and feasible, there shall be an approved thermostatic device that has a  
setting of not more than 125 degrees Fahrenheit located in the system at a suitable  
point in the return air duct ahead of the fresh air intake, actuation of which shall  
open the electrical circuit that supplies the fan motor. If it is impracticable to locate a  
thermostatic device ahead of the fresh air intake, an approved heat or smoke-actuated  
device, actuation of which will open the electrical circuit that supplies the fan motor,  
shall be located at a suitable point in the air duct on the discharge side of the fan.  
Page 67  
(5) If an existing system utilizes corridors or exitways as return air plenums, the  
system shall be revamped to eliminate the utilization of corridors or exitways as  
return air plenums. If revamping is impractical due to design or construction, the  
inspecting authority may accept the existing system if an approved smoke detector  
is installed in each separated area of the corridors or exitways to automatically  
open the electrical circuit that supplies the fan motor. A smoke detector shall  
incorporate visual or audible signals to indicate any trouble that would interfere with  
the proper operation of the smoke detector. A stairway shall not be used as a return  
air plenum.  
History: 1994 AACS.  
R 400.18657 Sprinkler protection.  
Rule 657. (1) An automatic sprinkler system shall be installed in all congregate  
facilities as required in these rules.  
(2) If an adequate supply of water is available,  
installed to protect all of the following areas:  
a
sprinkler system shall be  
(a) A heating plant room that houses incinerators of more than a 2-bushel  
capacity.  
(b) An incinerator room.  
(c) A laundry room.  
(d) A storage room for combustible material, including a janitor room and closet.  
(e) A clean and dirty linen room.  
(f) A receiving room.  
(g) A maintenance shop.  
(h) A laundry and rubbish receiving room or bin.  
(i) A laundry and rubbish chute feed room.  
(j) The tops and various levels where required of laundry and rubbish chutes.  
(k) A kitchen storage room.  
If an adequate supply of water is not available, the areas specified in this subrule  
shall be protected with an approved automatic fire detection system.  
(3) Water supplies and flow alarms shall be in compliance with new  
construction requirements.  
(4) Complete shop drawings shall be submitted to the appropriate inspecting  
authority for approval before any sprinkler installation is made.  
History: 1994 AACS.  
R 400.18658 Automatic fire detection system.  
Rule 658. (1) An automatic fire detection system shall be installed in all facilities  
as required by these rules.  
(2) An electrical supply for a system shall be installed on a separate circuit in  
metallic conduit and shall be fused ahead of the main entrance switch.  
History: 1994 AACS.  
Page 68  
R 400.18659 Standards and codes adoption.  
Rule 659. The standards and codes specified in this rule are adopted by reference  
in these rules for existing adult foster care congregate facilities. Copies of the  
adopted standards are available for inspection and distribution at the office of the State  
Fire Safety Board, Michigan Department of State Police, Fire Marshal Division,  
7150 Harris Drive, Lansing, Michigan 48913. The cost of the standards as of the  
time of adoption of these rules are as indicated:  
(1) Accident, Automotive and Burglary  
Protection  
Equipment  
Lists,  
Underwriters Laboratories, Inc., 1972. Cost: 20 cents per page.  
(2) Directory--Part I Building Material List Underwriters Laboratories, Inc.,  
January 1973, 333 Pfingsten Road, Northbrook, Illinois 60062. Cost:  
20 cents per page.  
(3) Fire Protection Equipment List, Underwriters Laboratories.  
(4) National Board of Fire Underwriters fire resistance rating pamphlet, 1964  
edition, available from the State Fire Safety Board, 7150 Harris Drive, Lansing,  
Michigan 48913.  
(5) NFPA 10, 1972 edition, entitled "Portable Fire Extinguishers." Cost:  
50 cents per page.  
(6) NFPA 13, 1972 edition, entitled "Installation of Sprinkler Systems." National  
Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.  
Cost: 50 cents per page.  
(7) NFPA 14, 1971 edition, entitled "Standpipe and Hose Systems." National  
Fire Protection Association, Batterymarch Park, Quincy, Massachusetts 02269.  
Cost: 50 cents per page.  
(8) NFPA 22, 1971 edition, entitled "Standard for Water Tanks for Private  
Fire Protection." Cost: 50 cents per page.  
(9) NFPA 54, 1969 edition, entitled "Installation of Gas Appliance and Gas  
Piping." Cost: 50 cents per page.  
(10) NFPA 54A, 1969 edition, entitled "Standards for  
the  
Installation,  
Maintenance and Use of Piping, Appliances, and Fitting for City Gas." Cost: 50  
cents per page.  
(11) NFPA 70, National Electric Code, 1971,  
Association. Cost: 50 cents per page.  
National  
Fire  
Protection  
(12) NFPA 72A, 72B, and 72D, 1972 edition, entitled "Proprietary, Auxiliary  
and Local Protective Signaling Systems." National Fire Protection Association,  
Batterymarch Park, Quincy, Massachusetts 02269.  
Cost: 50 cents per page.  
(13) NFPA 80, 1970 edition, entitled "Standard for the Installation of Fire Doors  
and Windows." Cost: 50 cents per page.  
(14) NFPA 82, 1972 edition, entitled "Incinerators, Rubbish Handling." Cost: 50  
cents per page.  
(15) NFPA 90A, 1972 edition, entitled "Air Conditioning and  
Systems." Cost: 50 cents per page.  
Ventilating  
Page 69  
(16) NFPA 96, 1971 edition, entitled "Standard for the Installation of Equipment  
for the Removal of Smoke and Grease-Laden Vapors from Commercial Cooking  
Equipment." Cost: 50 cents per page.  
(17) State of Michigan Fire Damper Clarification,  
Association, Jackson, Michigan 49204 Cost: Single copy free.  
1972,  
Five  
Cities  
(18) Uniform State Specification for Fire Escapes, Michigan Department of State  
Police, Fire Marshal Division, 7150 Harris Drive, Lansing, Michigan 48913.  
History: 1994 AACS.  
PART 7. AMENDMENTS TO THE STANDARD FOR THE INSTALLATION,  
MAINTENANCE, AND  
USE OF HOUSEHOLD FIRE WARNING EQUIPMENT.  
(NFPA 74, 1989 EDITION, NATIONAL FIRE PROTECTION ASSOCIATION)  
R 400.18701 Power supplies.  
Rule 701. Section 3-1.1.1 of the standard is amended, section 3-2.3 of the  
standard is deleted, and section 3-5 is added to the standard, to read as follows:  
3-1.1.1. For electrically powered detectors, an AC primary power source shall be  
utilized in all new and existing construction.  
3-2.3. Deleted.  
3-5. A secondary source of power is required and it shall be of sufficient  
capacity to operate the system for 24 hours and thereafter to sound alarm devices for  
not less than 4 minutes.  
A
distinctive trouble signal shall be given before the  
secondary power supply is incapable of operating the equipment for alarm purposes.  
History: 1994 AACS.  
R 400.18702 Maintenance, tests, and records.  
Rule 702. Section 6-2 of the standard is amended and section 6-3 is added to  
the standard, to read as follows:  
6-2. Tests or inspections, as recommended by the manufacturer, shall be made by  
the licensee not less than once a month for all smoke detectors.  
6-3. Inspections shall be recorded and the records kept on file for 2 years.  
Records shall be made available upon the request of the authority having jurisdiction.  
History: 1994 AACS.  
Page 70  
;