DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
BUREAU OF CONSTRUCTION CODES  
SKILLED TRADES REGULATION RULES  
(By authority conferred on the director of the department of licensing and  
regulatory affairs by sections 207, 209, and 907 of the skilled trades regulation act,  
2016 PA 407, MCL 339.5207, 339.5209, and 339.5907, and Executive  
Reorganization Order Nos. 1996-2, 2003-1, 2008-4, 2011-4, and 2017-1, MCL  
445.2001, 445.2011, 445.2025, 445.2030, and 339.3102)  
PART 1. GENERAL PROVISIONS  
R 339.5101 Definitions.  
Rule 101. (1) As used in these rules, “act” means the skilled trades regulation act,  
2016 PA 407, MCL 339.5101 to 339.6133.  
(2) A term defined in the act has the same meaning when used in these rules.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5102 Advertising.  
Rule 102. (1) An individual who does not hold a license issued under the act shall  
not advertise for work that requires a license, as that term is defined in section 105 of the  
act, MCL 339.5105.  
(2) A violation of this rule constitutes false advertising pursuant to section 607(f) of  
the act, MCL 339.5607.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 2. ISSUANCE OF LICENSES  
R 339.5111 Verification of licensure.  
Rule 111. An individual who is seeking written verification that a person is or is not  
licensed shall submit to the department a written request for this verification, along with a  
$30.00 fee.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5112 License; name or address change, or both; duplicate license request.  
Page 1  
Rule 112. Except as provided in the act, a licensee who is seeking to amend his or  
her contact name, address, phone number, or email address shall submit the department  
form with 1 of the following fees, as applicable:  
(a) Name change with reprint ...........................................................................$10.00.  
(b) Address change with reprint ........................................................................$10.00.  
(c) Name change, no reprint..............................................................................No fee.  
(d) Address change, no reprint..........................................................................No fee.  
(e) No data change, duplicate license request ..................................................$10.00.  
(f) Online data change, no reprint..................................................................... No fee.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5113 License classification.  
Rule 113. (1) A licensee who is seeking an additional mechanical license  
classification shall submit to the department an application provided by the department  
along with the nonrefundable application fee.  
(2) A boiler licensee who is seeking to upgrade his or her license to a higher  
classification shall maintain his or her current license in good standing for at least 1  
year and take the prescribed examination. A boiler licensee may only upgrade his or her  
license 1 classification at a time.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5114 License examination; minimum grade.  
Rule 114. (1) An individual who is applying for licensure pursuant to section 203  
of the act, MCL 339.5203, shall take a written examination approved by the  
department. A score of 75% is required to pass the written examination.  
(2) A written examination may include a duplicate question or questions, as needed.  
(3) If a hands-on examination, commonly referred to as a practical exam in the industry,  
is administered as part of a license examination, the practical exam must be either pass or  
fail. The practical exam may be in addition to a written examination, as provided in  
subrule (1) of this rule.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5115 Minimal standards.  
Rule 115. (1) The minimal standard of acceptable practice is the Stille-DeRossett-  
Hale single state construction code act, 1972 PA 230, MCL 125.1501 to 125.1531. A  
licensee who deviates from the minimal standard of acceptable practice or the specified  
requirements of the codes adopted pursuant to the Stille-DeRossett-Hale single state  
construction code act, 1972 PA 230, MCL 125.1501 to 125.1531, its rules, these rules, or  
Page 2  
any acts by which the licensee operates may be considered to have committed an act  
demonstrating incompetence as described in section 607(g) of the act, MCL 339.5607.  
(2) The department may verify any work or experience information provided by an  
applicant for licensure to establish the applicant’s minimum practical experience in the  
applicant’s desired license trade or classification. This work may be inspected, when  
practical, or it may be proven by the applicant submitting to the department pictures,  
diagrams, or other evidence as considered necessary and appropriate by the department.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5116 Renewal for licensure application.  
Rule 116. Unless otherwise specified in the act, a licensee who fails to submit the  
renewal for licensure application within 60 days after the license’s expiration date shall  
pay to the department, in addition to the renewal fee, a late renewal fee of $100.00 for  
renewal.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5117 License renewal.  
Rule 117. Unless otherwise specified in the act, an individual’s license for his or her  
trade expires on December 31 of every calendar year.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5118 Relicensure.  
Rule 118. Unless otherwise specified in the act, a licensee who fails to renew a  
license 3 or more years after the license expired or who had his or her license revoked  
shall meet the requirements in section 411 of the act, MCL 339.5411, and shall take and  
pass the required examination.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5119 Code update courses; instructors; standards.  
Rule 119. (1) Unless otherwise provided in the act, the department shall approve  
instructor-provided code update courses that comply with the act and these rules.  
Instructors shall be approved by the department. A certificate of completion must be  
issued, either electronically or by paper, by a course provider to an individual who has  
successfully completed the code update class by required attendance. The certificate must  
contain all of the following information: A course approval number granted by the  
department. The name and address of the individual, school, organization, or company  
who sponsors or administers the course. The date the certificate was issued. The  
student’s name and license number.  
Page 3  
(4) The department may withdraw the approval of a course if the approval was issued  
in error, if the approval was issued based on incorrect information, or if the course is  
found to be in violation of these rules. Notice of withdrawal of approval must be in  
writing and must state the reason for the withdrawal of approval. An appeal of the  
withdrawal must be processed pursuant to the administrative procedures act of 1969,  
1969 PA 306, MCL 24.201 to 24.328.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 4. LICENSE FEES  
R 339.5121 Nonrefundable application fee.  
Rule 121. The nonrefundable application fee is the initial license fee, as established  
pursuant to the respective cycle duration, as specified in the applicable article within the  
act.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 5. COMPLAINTS  
R 339.5131 Complaints.  
Rule 131. A complaint filed under the act must be made within 12 months after the  
latest of the following:  
Last day at jobsite.  
Final approval from the inspector.  
Payment or partial payment tendered.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 6. PENALTIES AND REMEDIES  
R 339.5141 Violations.  
Rule 141. (1) A licensee shall respond to the department within 30 days of the date a  
citation is issued against a licensee. Failure to respond to the department within 30 days is  
a violation of the act.  
(2) A licensee may receive written communication from the department requesting  
information for any reason. The licensee shall respond to the department, with the  
requested information, within the timeline allocated by the department in the written  
request, no later than the date that is prescribed in a letter to the licensee. Failure to  
respond to the department within the timeline allocated is a violation of the act.  
Page 4  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 7. ELECTRICIANS AND ELECTRICAL CONTRACTORS  
R 339.5151 Licenses; issuance.  
Rule 151. (1) If a master electrician ceases to represent an electrical contractor, both  
the electrical contractor and the master electrician who was employed by the electrical  
contractor shall notify the department immediately of any changes in the employment  
status of the master electrician. The contractor license may be summarily suspended  
pursuant to section 507 of the act, MCL 339.5507, until the contractor designates an  
employee or officer who is a licensed master electrician to qualify for the contractor.  
If a fire alarm specialty technician ceases to represent a fire alarm contractor, both  
the fire alarm contractor and the fire alarm specialty technician who was employed by the  
fire alarm contractor shall notify the department immediately of any changes in the  
employment status of the fire alarm specialty technician. The contractor license may be  
summarily suspended pursuant to section 507 of the act, MCL 339.5507, until the  
contractor designates an employee or officer who is a licensed fire alarm specialty  
technician to qualify for the contractor license.  
If a sign specialist ceases to represent a sign contractor, both the sign contractor and  
the sign specialist who was employed by the sign contractor shall notify the department  
immediately of any changes in the employment status of the sign specialist. The  
contractor license may be summarily suspended pursuant to section 507 of the act, MCL  
339.5507, until the contractor designates an employee or officer who is a licensed sign  
specialist to qualify for the contractor license.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 8. MECHANICAL CONTRACTORS  
R 339.5161 Mechanical specialty license classifications.  
Rule 161. (1) A mechanical specialty license is a license limited to a specific type of  
mechanical installation. Specialty licenses are not required if the work is covered under a  
different license classification, as follows:  
Limited to solar heating and cooling. Solar heating and cooling means theinstallation  
of equipment and systems intended to utilize solar energy for space heating or cooling.  
Limited to solid fuel and vented decorative gas appliances. Solid fuel equipment and  
vented decorative gas appliances means the installation of equipment that utilizes  
combusted solid fuel to produce heat or a vented fuel gas appliance in which the primary  
function lies in the aesthetic effect of the flames.  
Page 5  
Limited to liquified petroleum gas (LP) distribution piping. LP distribution piping  
means it is limited to the installation of fuel gas piping from the outlet of the first stage  
regulator to the inlet of the second stage regulator.  
Limited to fuel gas piping. Fuel gas piping means the installation of piping, valves,  
and fittings from the outlet of the point of delivery to the outlet of the appliance shut off  
valve used to convey natural gas, manufactured gas, LP, or a mixture of these gases.  
Limited to fuel gas piping and venting. Fuel gas piping and venting means the  
installation of fuel gas piping and the installation of a continuous open passageway from  
the flue collar or draft hood of an appliance to the outside atmosphere for the purpose of  
removing flue or vent gases.  
(2) An individual who holds a heating, ventilation and air conditioning (HVAC)  
equipment license is not required to obtain a specialty license limited to solid fuel and  
vented decorative gas appliances, LP distribution piping, solar heating and cooling, fuel  
gas piping, or fuel gas piping and venting.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 9. BOILER  
SUBPART A. BOILER LICENSES  
R 339.5171 Scope of rules; adoption of national examination.  
Rule 171. (1) The rules in this subpart establish minimum requirements for each of  
the following:  
The licensing of boiler inspectors, boiler repairers, boiler installers, and stationary  
engineers.  
The requirements for the issuance of permits to install, repair, and alter boilers, boiler  
external piping, and non-boiler external piping.  
The fees charged by the department for the issuance of a boiler license or boiler  
permit.  
(2) Under section 927 of the act, MCL 339.5927, the board adopts the examination  
prepared by the National Institute for Uniform Licensing of Power Engineers (NIULPE),  
Inc., 510 N. Wolcott Ave., Chicago, Illinois 60622. The examination topics may be  
reviewed under the certification requirements for each level of boiler operator or  
stationary engineer at https://niulpe.org. The written examination for all classifications of  
boiler operator and stationary engineer must be delivered and administered by NIUPLE.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5172 Out-of-state applicant for licensure in this state.  
Rule 172. If an individual holds a national organization’s license as a boiler repairer  
or boiler installer in another state, that individual may be licensed in this state for the  
work he or she is licensed to perform by the national organization. The individual shall  
submit to the department both of the following:  
Page 6  
An application with a copy of his or her current and valid national license.  
Payment of the nonrefundable application fee.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5173 Boiler installer’s or repairer’s license.  
Rule 173. (1) A boiler installer or repairer shall be licensed as required by section  
939 of the act, MCL 339.5939.  
An individual who is applying for a boiler installer’s license must have at least 5  
years of experience in all phases of boiler installation in the class of license for which the  
applicant is applying. A credit of 2 years of experience toward the 5 years of experience  
may be given for 2 years of experience in the design, construction, manufacture, or  
inspection of boilers.  
An individual who is applying for a boiler repairer’s license must have at least 5 years  
of experience in all phases of boiler repair in the class of license for which the applicant  
is applying. A credit of 3 years of experience toward the 5 years of experience may be  
given for 3 years of experience in the design, construction, manufacture, or inspection of  
boilers.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5174 Classes of boiler installer’s licenses.  
Rule 174. (1) A class 1B installer’s license qualifies an individual to install a low-  
pressure boiler that does not exceed a firing rate of 1,000,000 British thermal units (BTU)  
per hour as certified by the boiler manufacturer. For a class 1B license, the sum of all  
modules in a modular boiler must not exceed a firing rate of 1,000,000 BTU per hour as  
certified by the boiler manufacturer.  
(2) A class 2B installer’s license qualifies an individual to do both of the following:  
Install a low-pressure boiler of any capacity or firing rate.  
Perform work covered by a class 1B license.  
(3) A class 3B installer’s license qualifies an individual to do all the following:  
Install a power boiler that has a capacity of not more than 5,000 pounds of steam per  
hour. Install or replace non-boiler external piping as defined by the American Society of  
Mechanical Engineers (ASME), as defined in Subpart B Part1, code B31.1, 2018, and R  
339.5209. Perform work covered by a class 2B license.  
(4) A class 4B installer’s license qualifies an individual to do all the following:  
Install a power boiler that has a capacity of not more than 300,000 pounds of steam  
per hour. Install or replace non-boiler external piping as defined by ASME code B31.1  
and R 339.5209. Perform work covered by a class 3B license.  
(5) A class 5B installer’s license qualifies an individual to do all of the following:  
Install a power boiler of any capacity or firing rate, except for a nuclear heat source  
boiler.  
Install or replace non-boiler external piping as defined by ASME code B31.1 and R  
339.5209.  
Page 7  
Perform work covered by a class 4B license.  
(6) A class 6B installer’s license qualifies an individual to install a boiler that utilizes  
a nuclear heat source or its parts, appurtenances, or system components. Before a license  
is issued, an individual who is applying for a class 6B license shall submit evidence of  
both of the following:  
Familiarity with and knowledge of all federal rules and regulations regarding the  
installation of a boiler that has a nuclear heat source.  
Employment by a company in possession of a valid ASME nuclear code symbol  
applicable to the portions of any nuclear boiler system that the company proposes to  
install.  
(7) A class P license qualifies an individual to install or replace non-boiler external  
piping or repair non-boiler external piping as defined by ASME code B31.1 and R  
339.5209.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5175 Boiler repairers; classes of licenses.  
Rule 175. (1) A class I license allows a licensee to repair a low-pressure boiler by  
means other than welding, riveting, or other fabrication process.  
(2) A class II license allows a licensee to do both of the following:  
Repair a low-pressure boiler, a hot water supply boiler, and a fire tube boiler of any  
pressure.Perform work covered by a class I license.  
(3) A class III license allows a licensee to do all of the following:  
Repair a high-pressure boiler. Repair or replace non-boiler external piping, as defined  
by ASME code B31.1 and R 339.5209. Perform work covered by a class II license.  
(4) A class IV license allows a licensee to do both of the following:  
Repair or field-erect a boiler of any pressure, except for a boiler that has a nuclear  
hear source. Repair or replace non-boiler external piping as defined by ASME code  
B31.1 and R 339.5209.  
(5) A class V license allows a licensee to erect and repair a boiler or its parts that has  
a nuclear heat source, appurtenances, or system components, and also provides that the  
licensee may repair or replace non-boiler external piping, as defined by ASME code  
B31.1 and R 339.5209. Before a license is issued, an applicant for a class V license shall  
submit evidence of the following:  
Familiarity with and knowledge of all federal rules and regulations regarding the  
construction of a boiler that has a nuclear heat source.  
Employment by a company in possession of a valid ASME N-type symbol stamp  
applicable to the portions of any nuclear boiler system he or she proposes to repair.  
(6) A class P license qualifies a person to install or repair non-boiler external piping  
as defined by ASME code B31.1, 2018, and R 339.5209.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5176 Fees.  
Page 8  
Rule 176. (1) Fees for licenses, examinations, boiler operator and stationary engineer  
registration; permit applications, certificates, and inspections are as follows:  
(a) Licenses:  
Installer license  
Installer examination  
Installer renewal  
Repairer license  
Repairer examination  
Repairer renewal  
Inspector license  
Inspector examination  
Inspector renewal  
$100.00.  
$100.00.  
$100.00.  
$100.00.  
$100.00.  
$100.00.  
$100.00.  
$100.00.  
$75.00.  
Boiler operator registration  
Boiler operator examination  
Boiler operator registration renewal  
Stationary engineer registration  
$80.00.  
$100.00.  
$80.00.  
$100.00.  
(xiv) Stationary engineer written examination $100.00.  
(xv) Stationary engineer registration renewal $100.00.  
(xvi) Out of state applicant  
$200.00.  
(b) Permit applications:  
Nuclear installation permit application  
Nuclear repair permit application .  
Low-pressure installation permit application  
$1,500.00.  
$500.00.  
$100.00.  
High pressure installation permit application $130.00 + .06 cents per foot of  
piping.Repair permit application .  
(c) Certificates:  
$75.00.  
Certificates  
$75.00.  
Reprinting of certificate more than 30 days after issuance  
(d) Inspections:  
$40.00.  
Power boilers-150 square feet or less  
$85.00.  
Power boilers-more than 150 square feet to 4,000 square feet $175.00.  
Power boilers-more than 4,000 square feet to 10,000 square fee..$200.00.  
Power boilers-more than 10,000 square feet  
Low-pressure heating boiler without manhole ...  
$225.00.  
$85.00.  
(vi) Inspection of an additional low-pressure heating boiler without a manhole at the  
same physical location, on the same date $70.00.  
(vii) Low-pressure heating boiler with manhole $85.00.  
(viii) Low-pressure hot water supply boilers $85.00.  
(ix) Inspection of an additional low-pressure hot water supply boiler at the same  
physical location, on the same date $65.00.  
(x) Low-pressure process boiler without manhole $85.00.  
(xi) Low-pressure process boiler with manhole $85.00.  
(xii) Miniature hobby locomotive boiler  
Permit application fees are nonrefundable.  
$15.00.  
Certificate inspection reports submitted to the department’s boiler division for data  
entry must be assessed a fee of $5.00 per page.  
Page 9  
A copy of a boiler report will be provided by the department at a cost of $1.00 per  
page. Payment must be received by the department before a copy of a report will be  
released.  
The department’s boiler division shall provide special inspections not otherwise  
covered in subrule (1) of this rule or section 919 of the act, MCL 339.5919. The fee  
assessed by the department for special inspections must be at the rate of $100.00 for the  
first hour and $120.00 for each additional hour, plus lodging, meals, transportation, and  
other related expenses incurred for performing special inspections.  
History: 2023 MR 8, Eff. May 3, 2023.  
SUBPART B. BOILER INSPECTORS, INSTALLERS, REPAIRERS, AND  
OPERATORS AND STATIONARY ENGINEERS  
PART 1. GENERAL PROVISIONS  
R 339.5201 Scope.  
Rule 201. The rules in this part establish minimum standards of safety for the use,  
construction, installation, inspection, alteration, and repair of boilers, boiler external  
piping, and non-boiler external piping, licensing of boiler inspectors, boiler repairers, and  
boiler installers, requirements for permits to install, repair, and alter, and fees to be  
changed.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5202 Definitions.  
Rule 202. (1) As used in this part:  
(a) “Accident” means a sudden and accidental breakdown of a boiler or a part of a  
boiler that results in physical damage to the boiler that necessitates the repair or  
replacement of the boiler or a part of the boiler. Accident does not mean a breakdown  
due to any of the following unless a unique or unusual explosion hazard exists as a  
result of the breakdown:  
Normal erosion.  
Corrosion.  
Wastage of metal that requires restoration.  
Leaking tubes.  
Weakened metal, such as water legs or handhole areas.  
(b) “Aftercooler” means a device used for lowering the temperature of a boiler  
blowoff discharge before it enters the building drain.  
(c) “Alteration” means any change in the item described on the original  
manufacturer’s data report that affects the pressure-containing capability of the boiler or  
its piping. A nonphysical change such as an increase in the maximum allowable pressure,  
whether internal or external, or design temperature of a boiler or its piping is an  
alteration.  
Page 10  
(d) “ASME”, “ASME boiler and pressure vessel code”, “ASME code”, or “code”  
means the boiler and pressure vessel code of the American Society of Mechanical  
Engineers, with addenda, as prescribed and approved by the council of the society.  
(e) “Authorized inspector” means an individual who is designated as an authorized  
inspector by an authorized inspection agency, who holds a valid certificate of  
competency and national board commission with an “A” or “B” endorsement, and who  
is employed by the authorized inspection agency that assumes responsibility for the  
individual’s actions.  
“Boiler assembler” means a corporation, company, partnership, or individual who  
assembles a boiler that has been delivered in pieces. For ASME code section I power  
boiler assemblies, a boiler assembler shall possess the appropriate code symbol stamps.  
“Boiler blowoff piping” means the piping, fittings, and valves from the boiler to the  
blowoff tank, blowoff separator, or other safe point of discharge through which the  
water in the boiler may be blown out under pressure, except for drains such as those used  
in water columns, gauge glasses, or piping to feed water regulators and similar devices.  
“Boiler blowdown vessel” means an unfired pressure vessel into which water is  
discharged above atmospheric pressure from a boiler blowoff line.  
“Boiler installation” means the installation of a boiler, including all connected piping,  
valves, fittings, flanges, firing equipment, controls, appurtenances, and auxiliaries. The  
term includes the field assembly of boilers.  
“CSD-1” means the 2018 ASME code for controls and safety devices for  
automatically fired boilers.  
“Certificate of competency” means a certificate issued to a person that has passed an  
examination for inspectors prescribed by the board of boiler rules.  
“Chief inspector” means the chief boiler inspector appointed under the act.  
“Condemned boiler” means a boiler that has been inspected and declared unsafe or  
rejected for use by an inspector who is qualified to take such action and who has applied  
a stamping or marking designating its rejection.  
“Deputy inspector” means an inspector who is licensed under the act and employed  
by the director.  
“Existing installation” means any steam boiler constructed, installed, placed in  
operation, or contracted for before August 10, 1917, or any hot water heating or supply  
boiler constructed, installed, placed in operation, or contracted for before the effective  
date of these rules.  
"Existing steam boilers,” means steam boilers that are in actual use, or that are  
installed and ready for use before August 10, 1917. Existing steam boilers does not  
include secondhand boilers, rental boilers, or boilers that are subject to change in  
ownership or are to be reset, in which case the rules for new construction apply.  
“External inspection” means an inspection that is conducted while the boiler is under  
pressure and that does not involve examination of the internal surfaces of the pressure  
parts of the boiler.  
“Field assembly” means assembling prefabricated boiler pressure parts without field  
welding or riveting.  
“Field erection” means the erecting and assembling of boiler parts by welding,  
riveting, or other fabrication process.  
Page 11  
“Flash tank” means a closed vessel equipped with internal baffles or an apparatus for  
the purpose of separating moisture from flash steam as it passes through the vessel.  
(u) “Hobby” means an interest or activity that an individual pursues in his or her leisure  
time without compensation.  
(v) “Hot water heating and hot water supply boiler:” means a boiler that operates at  
pressure of not more than 160 pounds per square inch (PSI) or temperatures of not more  
than 250 degrees Fahrenheit, at or near the boiler outlet.  
(w) “Inspector” means an individual who holds a valid certificate of competency  
and national board commission.  
(x) “Internal inspection” means an inspection made when a boiler is shut down and  
handholes or manholes are opened for inspection of the interior.  
(y) “Labeled” means devices, equipment, appliances, or material to which a label,  
seal, symbol, or other identifying mark of a nationally recognized testing laboratory,  
inspection agency, or other organization concerned with product evaluation that  
maintains periodic inspection of the production of the items has been affixed and by  
whose label the manufacturer attests to compliance with applicable nationally  
recognized standards.  
(z) “Licensed boiler installer” means a person licensed under the act to engage in the  
business of making piping connections to a boiler or in the business of field-assembling  
boilers.  
(aa) “Licensed boiler repairer” means a person licensed under the act to engage in  
making or supervising all phases of boiler repair, alterations, or field erection.  
(bb) “Listed” means equipment, appliances, or material included in a list published  
by a nationally recognized testing laboratory, inspection agency, or other organization  
concerned with product evaluation that maintains periodic inspection of production of  
listed equipment, appliances, or materials, and whose listing states either that the  
equipment, appliances, or material meets nationally recognized standards or has been  
tested and found suitable for use in a specified manner. The authority having jurisdiction  
shall utilize the system employed by the listing organization to identify a listed product.  
(cc) “Maximum allowable working pressure” or “MAWP” means the maximum gage  
pressure permissible for the boiler to operate.  
(dd) “Maximum operating pressure” means the maximum operating pressure of the  
complete boiler system as designed, which includes supply, return, feed, and blow off  
piping.  
(ee) “Mechanical assembly” means the work necessary to establish or restore a  
pressure retaining boundary whereby pressure retaining capability is established through  
a mechanical, chemical, or physical interface.  
(ff) “Mechanical repair” means a method of repair which restores a pressure  
retaining boundary whereby pressure retaining capability is established through a  
mechanical, chemical, or physical interface.  
(gg) “Miniature boiler” means a power boiler that does not have any of the  
following:  
An inside diameter of the shell of more than 16 inches.  
A working pressure of more than 100 p.s.i.g.  
A gross volume of more than 5 cubic feet.  
More than 20 square feet of heating surface.  
Page 12  
(hh) “Miniature locomotive boiler” means a miniature hobby steam locomotive  
boiler that operates on a narrow-gauge track that is less than 24 inches wide and that is  
for public display or use.  
(ii) “Modular boiler” means a steam or hot water heating assembly consisting of a  
grouping of individual boilers called modules, intended to be installed as a unit, with a  
single inlet and a single outlet. Modules may be under 1 jacket or may be individually  
jacketed.  
(jj) “NBIC” means national board inspection code.  
(kk) “Nonstandard boiler” means a boiler that does not bear the National Board  
Stamping or stamp of any state or political subdivision that has adopted a standard of  
construction equivalent to that required by the board of boiler rules.  
(ll) “New boiler” means a boiler constructed, installed, placed in operation, or  
contracted for after July 1, 1966.  
(mm) “Owner or user” means a person, firm, partnership, or corporation that owns or  
operates a boiler within this state.  
(nn) “Out-of-use boiler” means a boiler not ready for use having the fuel supply,  
electricity, and all piping that may pressurize the boiler disconnected.  
(oo) “Portable boiler” means a boiler that is primarily intended for temporary location  
and that is, by its construction and usage, obviously portable.  
(pp) “Pressure-retaining items” means any boiler, pressure vessel, piping, or material  
used for the containment of pressure, either internal or external. The pressure may be  
obtained from an external source, by the application of heat from a direct source, or any  
combination of these methods.  
(qq) “Reinstalled boiler” means a boiler that is removed from its original setting and  
that is reinstalled at the same location or reinstalled at a new location.  
(rr) “Reinstatement” means the granting of a license or registration, with or without  
limitations or conditions, to a person whose license or registration has been suspended by  
the chief inspector.  
(ss) “Rental boiler” means a boiler that is in temporary use for not more than 1 year  
regardless of whether installed inside a boiler room, temporary room, temporary shed, or  
without external covering.  
(tt) “Repair” means the work necessary to restore a boiler or its piping to a safe and  
satisfactory operating condition.  
(uu) “Safe point of discharge” means a point of discharge that will protect personnel  
and property from injury due to discharge.  
(vv) “Special inspector” means a boiler inspector who holds a license in this state  
pursuant to the act, and who is regularly employed by an insurance company authorized  
to insure against a loss from boiler accidents in this state or by any city that is exempt  
under the act and has an authorized boiler inspection department.  
(ww) “Standard boiler” means a boiler that bears the stamp of the National Board of  
Boiler and Pressure Vessel Inspectors or of another state or political subdivision that has  
adopted a standard of construction equivalent to that required by the board of boiler rules  
of this state.  
(xx) “Traction boiler” means a boiler designed for the express purpose of pulling  
farm equipment or to convert steam power into flywheel energy driving farm apparatus  
such as threshers, saws, or grinding equipment.  
Page 13  
(yy) “Used boiler” means a boiler that is being reinstalled by the same owner.  
(zz) “Water heater” means a heater, in commercial or industrial size, that provides  
corrosion resistance for supplying potable hot water at pressure not exceeding 160 psi or  
temperatures not exceeding 210 degrees Fahrenheit. A water heater that does not exceed  
any of the following is exempt from these rules:  
A heat input of more than 200,000 BTU per hour.  
A water temperature of more than 210 degrees Fahrenheit.  
A nominal water-containing capacity of more than 120 gallons.  
(2) Terms defined in the act have the same meanings when used in these rules.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5203 Adoption by reference of the NBIC.  
Rule 203. (1) An owner of a boiler shall ensure the inspection, repair, and alteration  
of boilers, piping, and blowdown vessels is pursuant to the NBIC, 2019 edition. The code  
is adopted and amended by reference in these rules and available for inspection and  
purchase at the Michigan Department of Licensing and Regulatory Affairs, Bureau of  
Construction Codes, 611 W. Ottawa, Lansing, Michigan 48933 or for purchase from the  
National Board of Boiler and Pressure Vessels Inspectors, 1055 Crupper Avenue,  
Columbus, Ohio 43229, phone: 1(614) 888-8320, https://www.nationalboard.org, at a  
cost as of the time of adoption of these rules of $325.00 for each code book.  
The accreditation program described in the NBIC for repairs and alterations to  
pressure retaining items is mandatory for repairs to all power boilers and high-pressure  
high temperature water boilers and alterations to any boiler not exempted by these rules.  
Repair companies in possession of a certificate of authorization issued by the National  
Board of Boiler and Pressure Vessel Inspectors to repair and alter pressure-retaining  
items shall have in their employ an individual who has an appropriate class repairer  
license issued by the department’s boiler division. Repair companies not currently in  
possession of the certificate of authorization or a certificate of authorization issued by  
ASME have 1 year from the date of adoption of this rule to secure the certificate.  
Companies currently in possession of a valid certificate issued by ASME have until the  
next certificate review or 1 year, whichever is greater, to secure the certificate of  
authorization identified above. The board may waive the time requirement if appropriate  
justification is presented.  
Where the text of the NBIC refers to the “certificate holder,” the reference applies to  
all licensed boiler repairers, except when the reference is in relation to completion of  
NBIC forms and NBIC stamping, the reference refers to repair companies in possession  
of a valid certificate of authorization issued by the National Board of Boiler and Pressure  
Vessel Inspectors to repair and alter pressure retaining items.  
The standard welding procedures referenced in the NBIC are accepted for use in this  
state but are not mandatory. A licensed boiler repairer who elects to use 1 or more of the  
standard welding procedures shall file a list of the standard welding procedure  
identification numbers with the department’s boiler division before conducting any  
repairs or alterations requiring welding.  
Page 14  
R 339.5204 ASME code adoption by reference.  
Rule 204. (1) A boiler, blow down vessel, and expansion tank must be constructed  
as prescribed by these rules and the ASME boiler and pressure vessel code, section I, II,  
III, IV, V, VIII, IX, X, XI, 2019 edition, and ASME code B31.1, 2018 edition, power  
piping, which are adopted by reference as amended in these rules and are available for  
inspection and purchase at the Michigan Department of Licensing and Regulatory  
Affairs, Bureau of Construction Codes, 611 W. Ottawa, Lansing, Michigan 48933 or  
purchase from the ASME International, Two Park Avenue, New York, New York 10016-  
5990, phone: 1(800) 843-2763, https://www.asme.org, at a cost indicated below, as of the  
time of adoption of these rules:  
Section I (1 volume)  
$500.00.  
Section II (4 volumes) $3,150.00.  
Section III (11 volumes)..$6,385.00.  
Section IV (1 volume)…$510.00.  
Section V (1 volume)  
$570.00.  
Section VIII (3 volumes).$2,240.00.  
Section IX (1 volume)  
Section X (1 volume)  
Section XI (2 volumes)  
CSD-1 (1 volume)  
$580.00.  
$450.00.  
$1,450.00.  
$103.00.  
$335.00.  
B31.1 (1 volume)  
(2) An owner of a boiler shall not recalculate design maximum allowable working  
pressures based on ASME codes published after 1998 for boilers in service before  
December 31, 1998.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5205 Inspection and stamping during construction.  
Rule 205. A manufacturer shall register a boiler, blowdown vessel, and expansion  
tank other than a cast sectional boiler built or constructed for use in this state after the  
effective date of these rules, with the National Board of Boiler and Pressure Vessel  
Inspectors.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5206 Adoption; ASME code CSD-1.  
Rule 206. (1) An owner or user of a boiler shall ensure that the installation,  
maintenance, operation, and testing of controls and safety devices is pursuant to  
manufacturer’s instructions and ASME code CSD-1, 2018 edition. The code is adopted  
by reference as amended in these rules and available for inspection and purchase at the  
Michigan Department of Licensing and Regulatory Affairs, Bureau of Construction  
Codes, 611 W. Ottawa, Lansing, Michigan 48933 or for purchase from the ASME  
International, Two Park Avenue, New York, New York 10016-5990, (800) 843-2763,  
Page 15  
https://www.asme.org, at a cost as of the time of adoption of these rules of $103.00 for  
each code book.  
(2) An owner or user of a boiler system shall ensure that the maintenance and testing  
of controls and safety devices is conducted by an individual with a valid mechanical  
contractor license with the appropriate classification under the act. Individuals  
conducting maintenance and testing must be under the guidance and supervision of a  
licensed mechanical contractor.  
An owner or user shall provide to the inspector, at the time of certificate inspection,  
evidence showing what maintenance has been performed and what tests have been  
completed. The evidence must be a dated and signed service report or checklist, listing  
each control and safety device tested with the manufacturer’s name, model number, set  
point, and actual operational test point. The service report must include the license  
number and heating service classification of the mechanical contractor who is performing  
or supervising the work.  
If an owner does not provide the inspector with the required evidence of maintenance  
and testing between certificate inspections, then the inspector may issue a certificate of  
inspection for a term less than that stated under section 943 of the act, MCL 339.5943.  
For hot water heating and hot water supply boilers with a BTU input of 400,000 or  
less, the requirements of this subrule must be conducted once during an inspection cycle  
but must be performed within 12 months before the certificate inspection required by R  
339.5213.  
An owner, user, or operator of a boiler system shall ensure that the daily, weekly, and  
monthly operational checks are performed and documented pursuant to the  
manufacturer’s instructions and these rules. If the manufacturer’s instructions are not  
available, CSD-1, 2018 edition, nonmandatory appendix D contains a recommended  
checklist for additional information on periodic checks.  
A manually operated remote shutdown switch, as required by CSD-1, 2018 edition,  
must be located outside of each exit access doorway to the boiler room. The switch may  
be located just inside each exit access doorway should a possibility of tampering or  
weather conditions exist. A licensee may request a deviation from the requirements of  
this subrule by submitting a drawing clearly showing the deviation and stating  
justification for the request to the chief inspector for review and approval before the  
installation of a boiler. The chief inspector shall notify the licensee of the approval or  
denial of the request.  
A single manually operated remote shutdown switch may be used in a multiple boiler  
installation that shares a common boiler room. Kitchen cooking boilers, steam kettles,  
and steam cookers used for food preparation located in a kitchen are exempt from having  
a manually operated remote shutdown switch and lockable disconnect.  
Where applicable, the boiler installation must comply with the, R 408.30901 to R  
408.30998; R 408.30701 to R 408.30796; and R 408.30801 to R 408.30880.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5207 Manufacturer’s data reports: filing.  
Page 16  
Rule 207. A manufacturer’s data report for boilers must be signed by an authorized  
inspector and filed by the manufacturer with the chief inspector before installation. A  
data report that is signed by an authorized inspector and the ASME stamp on the boiler  
denotes that the boiler has been constructed pursuant to these rules. If a boiler is of  
special design, blueprints showing details of the proposed construction must be submitted  
to, and approved by, the chief inspector before construction is started.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5208 Installation and reinstallation of boilers.  
Rule 208. (1) An owner shall ensure that the installation of a new boiler or a  
reinstalled boiler meets the requirements of these rules; the ASME boiler and pressure  
vessel code, 2019 edition, the NBIC 2019 edition, and ASME CSD-1 2018. The ASME  
code requirement for the completion of a P4B data report for the installation of  
mechanically assembled boiler external piping is not required. Witnessing of the pressure  
test required by the NBIC part 1, section 2, paragraph 2.10.2, is not required.  
Where applicable, the boiler installation must comply with R 408.30901 to R  
408.30998; R 408.30701 to R 408.30796; and R 408.30801 to R 408.30880.  
The NBIC code, part 1, section 2, paragraph 2.4.4, is enforced by R 408.30701 to R  
408.30796.  
The NBIC code, part 1, section 3, paragraph 3.6.1, is enforced by R 408.30901 to R  
408.30998.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5209 Non-boiler external piping; power boilers; adoption and amendment  
of standards.  
Rule 209. (1) An owner of a boiler shall ensure that the installation of piping not  
covered by the ASME boiler and pressure vessel code, section I, 2019 edition, is installed  
as prescribed by the ASME code for pressure piping, B31.1, 2018 edition.  
(2) The owner of a chemical plant or petroleum refinery shall comply with subrule  
(1) of this rule or ensure the installation is installed as prescribed by ASME code for  
chemical plants and petroleum refineries, B31.3, 2019 edition.  
(3) A licensee under this rule is not required to possess an ASME code symbol  
stamp, but must hold a valid installer’s license.  
(4) The owner shall ensure that the installation of all of the following piping meets  
the requirements under subrule (1) of this rule:  
Blowoff piping beyond the second valve out to the safe point of discharge.  
Steam piping out to the load.  
Feed-water piping from the pump.  
Condensate piping.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 17  
R 339.5210 Permits; documentation for installation, reinstallation, alteration,  
and repair of boilers, boiler external piping, and non-boiler external piping.  
Rule 210. (1) All of the following provisions apply to installation permits:  
A licensee who is applying for the permit shall ensure that work does not proceed  
until an approved permit has been secured.  
An individual shall not install, alter, repair, or replace welded pipe without holding a  
proper license and first securing a permit from the department’s boiler division. The  
licensee applying for the permit shall ensure that work does not proceed until an  
approved permit has been secured.  
An individual shall not install or replace nonwelded pipe without holding a proper  
license. A permit is not required.  
(2) All of the following provisions apply to repair and alteration permits or reports:  
(a) The licensee who is applying for the permit shall ensure that work does not  
proceed until an approved permit has been secured, except as provided by section 941 of  
the act, MCL 339.5941.  
An individual shall not repair or replace welding piping without holding a proper  
license and first securing a permit from the department’s boiler division. The licensee  
applying for the permit shall ensure that work does not proceed until an approved permit  
has been secured, except as provided for in section 941 of the act, MCL 339.5941.  
An individual shall not perform welded repairs to nonwelded piping without  
holding a proper license and first securing a permit from the department’s boiler  
division. The licensee applying for the permit shall ensure that work does not proceed  
until an approved permit has been secured, except as provided for in section 941 of the  
act, MCL 339.5941.  
A licensee who makes welded repairs to boilers or boiler external piping requiring the  
use of the national board of boiler and pressure vessel inspectors “R” symbol stamp shall  
furnish the department’s boiler division with 1 copy of the approved permit application,  
along with reports as required by the NBIC, upon completion of the work.  
A public utility or industrial plant that has been granted an exemption under section  
947 of the act, MCL 339.5947, that makes a welded repair to non-boiler external piping  
shall maintain records of the repairs and make the records available for review as  
required by these rules.  
(3) A permit is required for either of the following:  
A change in use of an existing boiler from high pressure to low pressure and low  
pressure to high pressure, hot water heat to hot water supply and hot water supply to hot  
water heat, steam heating to hot water heating and hot water heating to steam heating, or  
steam heating to hot water supply and hot water supply to steam heating. The change  
must comply with these rules.  
Replacement by mechanical methods, without welding, of sections in sectional  
boilers, heat exchangers, feed water heater or economizer, and tube bundles.  
(4) A licensee replacing boiler components required by these rules to be code symbol  
stamped and National Board of Boiler and Pressure Vessel Inspectors (National Board)  
registered shall provide the department’s boiler division with the manufacturer’s data  
reports.  
Page 18  
(5) Any changes in the scope of work stated on the original permit application must  
be submitted to the department’s boiler division for approval.  
(6) A licensed boiler repairer shall secure a permit for a change in use of an existing  
boiler or replacement by mechanical methods, without welding, of sections in sectional  
boilers, heat exchangers, feed water heater or economizer, and tube bundles in  
accordance with the act.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5211 Registration of boilers.  
Rule 211. (1) Within 6 months from the effective date of these rules, all owners or  
users of boilers and their installations now in use or installed ready for use in this state  
shall report to the chief inspector on forms prescribed by the department, giving the  
location, type, capacity, age, and date of installation.  
Before transfer of ownership of a boiler is complete, the current owner shall ensure  
that all invoices for inspection certificates and inspections for services rendered under his  
or her ownership are paid in full. Upon completion of transfer of ownership, the new  
owner of a boiler shall notify the department’s boiler division of the change in ownership  
of a boiler or change in ownership of a location where a boiler is installed. Upon written  
notification, a new certificate of inspection must be issued in the name of the new owner.  
A boiler owner or user shall notify the department’s boiler division immediately  
when his or her boiler insurance has been discontinued.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5212 Right of access.  
Rule 212. The director, chief inspector, deputy inspector, or any special inspector  
shall have free access, during reasonable hours, to any premises in this state where a  
boiler is being constructed, installed, repaired, operated, or connected and ready for use  
for the purpose of ascertaining whether the boiler complies with the act.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5213 Boiler inspection.  
Rule 213. After a boiler is inspected by the chief or deputy inspector and the boiler  
and its installation are approved by the department, all certificate inspections must be  
conducted pursuant to the NBIC and these rules by an inspector who is properly licensed  
to inspect boilers in this state.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5214 Extension of internal inspection certificate to 24 or 36 months.  
Page 19  
Rule 214. (1) An internal boiler inspection may be increased from an annual inspection  
to a 24-month inspection frequency by approval of the board of boiler rules. An employee  
delegated by the utility or industrial facility shall apply for the extension and submit a copy  
of the documents that control its program for approval by the board of boiler rules. The  
information must be addressed by plant orders, procedures, or policies. The following  
information may be contained in 1 document or several documents if 1 document contains  
references to all other documents addressing the required information:  
Operator training.  
Boiler maintenance.  
Water chemistry.  
Operating parameters.  
Chemical cleaning schedule.  
Protective devices.  
Boiler external inspection.  
Testing of pressure relief devices pursuant to the NBIC. Repairs must be  
conducted by the valve manufacturer or a “VR” stamp holder.  
(2) The plant owner shall establish a review committee. The inspector must be a  
member of the committee. The purpose of the committee is to determine the  
acceptability of a boiler to operate safely for a 24-month period. The committee shall  
have access to  
and review all information pertaining to the past operation, maintenance, and repair  
of the boiler. The review committee meeting must be conducted within 30 days after the  
internal inspection. The committee may decrease the period of time the boiler may  
operate, but shall not extend the period beyond 24 months. The signed summary report  
of the review committee meetings must be submitted to the department’s boiler division.  
The grace period provided under R 408.4057 does not apply to this rule. The inspector  
shall indicate the next inspection due date on his or her inspection report to the  
department’s boiler division.  
(3) An internal boiler inspection may be increased from a 24-month inspection to a  
36-month inspection frequency if the board of boiler rules approves the inspection  
frequency. An employee designated by the utility or industrial facility shall request a  
change in inspection frequency in writing and submit a copy of the document that  
controls its program with supporting documentation that demonstrates all of the  
following for approval by the board of boiler rules.  
(a) The boiler complies with all of the requirements of subrule (1) of this rule and is  
currently inspected under 24-month inspection frequency approved by the board of boiler  
rules.  
(b) The boiler is a power boiler.  
(c) The following information must be included in the program document, plant  
orders, plant procedures, or plant policies:  
The boiler is fully attended during operations by qualified personnel designated by  
the owner to operate the boiler.  
The owner has a designated organization that provides oversight to boiler  
maintenance, and monitors boiler conditions to prevent significant deterioration from  
scaling, corrosion, erosion, or overheating to boiler components. The program document  
must contain an organizational chart that delineates the reporting structure of this  
Page 20  
organization along with the organization responsible for boiler operation and  
maintenance within the owner’s organization.  
The owner has installed instrumentation available and functioning for continuous  
monitoring of water chemistry parameters as identified by the boiler manufacturer and  
routine calibration is performed. This instrumentation must be maintained on a list for  
each boiler to which this paragraph applies to.  
The owner has a program for routine monitoring of the water chemistry condition,  
which includes physical samples being analyzed by the owner’s staff. The owner shall  
maintain a list of the physical samples for each boiler to which this paragraph applies to.  
The owner has alarm response procedures that provide direction to operators for  
actions to correct variations to chemistry parameters that include removing the boiler  
from service.  
(d) The establishment of a review committee whose purpose is to determine the  
acceptability of a boiler to operate safely for a 36-month period. The review committee  
must be made of, at a minimum, the following members:  
(i) A representative from the owner’s boiler operating and maintenance  
organization.  
(ii) A representative from the owner’s organization designated to provide oversight  
to boiler maintenance and monitoring of boiler condition.  
(iii) The inspector.  
(e) The summary report of the review committee meeting.  
The review committee described under subrule (3)(d) of this rule shall have access to  
and review all information pertaining to the past operation, maintenance, and repair of the  
boiler. The review committee meeting must be conducted within 30 days after the  
internal inspection. The review committee may shorten the period of time that the boiler  
may operate but must not extend the period beyond that permitted by the board of boiler  
rules.  
The grace period provided under section 943(c) of the act, MCL 339.5943, does not  
apply to this rule. The inspector shall indicate the next inspection due date on the  
inspection report submitted to the department’s boiler division.  
Utilities or industrial facilities with a prescheduled boiler internal certificate  
inspection period shall communicate the date when the boiler is removed from service  
with the department’s boiler division. The boiler internal inspection may occur at any  
time during the outage period. The next operating period is calculated based on the date  
of the certificate inspection conducted during this period.  
An external inspection of the boiler must be conducted while under pressure, within  
12 months of the certificate inspection, and every 12 months thereafter until the next  
boiler internal inspection.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5215 Reporting unregistered boilers.  
Rule 215. (1) If a special inspector visits a location to conduct an inspection as  
required by these rules, then he or she shall report the location of all boilers that are not  
registered. This reporting is in addition to the reporting of the inspection of registered  
Page 21  
boilers and their installation. The chief inspector shall assign a deputy to visit the location  
to inspect all unregistered boilers and affix a Michigan serial number.  
(2) If a special inspector inspects a boiler that does not bear a Michigan serial  
number, then the inspector shall attempt to verify whether the boiler is unregistered or is  
missing the Michigan serial number tag. If the inspector is unable to determine that the  
boiler is registered, he or she shall report it as prescribed in subrule (1) of this rule.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5216 Filing of welding procedures.  
Rule 216. (1) If welding is employed in the installation, reinstallation, repair,  
replacement, or alteration of a boiler, then the licensed installer or repairer shall file  
welding procedure specifications and the procedure qualification reports qualified  
pursuant to the requirements of ASME code section IX, “welding and brazing  
qualifications,” with the department’s boiler division, before conducting any welding.  
(2) A licensed installer or repairer who utilizes welding in the installation,  
reinstallation, repair, replacement, or alteration shall have available, for the inspector’s  
review, welding procedure specifications and welder performance qualification records to  
be used or that were used in the installation, reinstallation, repair, replacement or  
alteration at the work site or other mutually agreed upon locations.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5217 Inspection of components and systems in a nuclear power plant.  
Rule 217. (1) Preservice or baseline inspections; in service inspections; repairs;  
replacements; modifications; alterations examinations; testing; records; and reports of  
complete nuclear power plants and individual nuclear components, parts, appurtenances,  
piping, supports, nuclear systems, and applicable associated auxiliary systems that  
comply with all of the requirements of the construction code ASME BPV Code, section  
III, when the requirements have been completed, irrespective of the physical location,  
must be as prescribed in section XI, rules for in service inspection of nuclear power plant  
components, of the ASME boiler and pressure vessel code. A copy of the current edition  
of section XI-2019, is available for inspection and purchase at the Michigan Department  
of Licensing and Regulatory Affairs, Bureau of Construction Codes, 611 W. Ottawa,  
Lansing, Michigan 48933, or for purchase from the ASME International, Two Park  
Avenue, New York, New York 10016- 5990, (800) 843-2763, at a cost as of the time of  
adoption of these rules of $16,273.00 for the BPV Code books.  
The owner of a nuclear power plant shall file inspection plans and schedules, pump  
and valve testing programs, and requests for relief from section XI of the ASME code  
requirements with the department’s boiler division.  
The nuclear power plant shall maintain compliance with requirements, as prescribed  
by the Nuclear Regulatory Commission.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 22  
R 339.5218 Reports of inspection to be filed.  
Rule 218. (1) Certificate inspection reports submitted electronically must be in a form  
acceptable to the department’s boiler division.  
Certificate inspection reports submitted to the department’s boiler division for data  
entry must be assessed a fee of $5.00 per report.  
An inspector shall leave a signed and dated inspection sticker or inspection report at  
the inspection location.  
An inspector shall record his or her National Board of Boiler and Pressure Vessel  
Commission number on the inspection report.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5219 Rental boilers.  
Rule 219. A rental boiler must be inspected before it is rented, and the boiler must be  
approved for temporary installation. An inspection certificate for an approved rental  
boiler is valid for 12 months.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5220 Refusal of inspection or nonpayment of fee.  
Rule 220. If the owner or user of a boiler required to be inspected refuses to allow an  
inspection to be made or refuses to pay the fee prescribed by R 339.5176, the chief  
inspector shall suspend the certificate of inspection until the owner or user allows the  
inspection or pays the fee.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5221 Notice of violation.  
Rule 221. (1) A written notice of violation containing the code deficiencies must be  
sent to, or served upon, the owner or user by the chief inspector, deputy inspector, or  
special inspector advising of the existing conditions and stating a compliance date when  
the violation must be corrected. If the code deficiencies are not corrected by the  
compliance date, the violation notice serves as a suspension of the certificate.  
When the notice of violation is issued as certificate blocking, the inspection certificate  
is suspended, and a written notice must be given to the owner or user at the time of the  
notice of violation is issued. The certificate blocking violation continues in effect until the  
boiler conforms to these rules and the certificate has been reinstated.  
A fee must be charged pursuant to R 339.5176 for all follow-up visits by the chief  
inspector or deputy inspector.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 23  
R 339.5222 Defacing or removing certificate or numbers.  
Rule 222. No individual, except the chief inspector or a deputy inspector, shall deface  
or remove any certificate of inspection or mark of identification number on a boiler.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5223 Boiler insurance policies.  
Rule 223. All insurance companies shall notify the chief inspector within 30 days of  
all boiler policies, newly written, canceled, not renewed, or suspended because of unsafe  
conditions.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5224 Notification; defective boilers.  
Rule 224. If a special inspector, upon the first inspection of a new risk, finds that the  
boiler or any of the appurtenances are in such condition that the company refuses  
insurance, the company shall immediately notify the chief inspector and submit a notice  
of violation of the defects.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5225 Notification in case of accident that renders boiler inoperative.  
Rule 225. (1) If an accident occurs that renders a boiler inoperative, then the owner or  
user shall immediately notify the chief inspector.  
For a serious accident, notice must be given immediately by the quickest method  
available, and neither the boiler nor any of its parts shall be removed or disturbed before  
an inspection has been made by the chief inspector, deputy inspector, or special inspector,  
unless the removal is to save human life. A condition or failure that results in bodily  
injury or physical damage to equipment or property other than the boiler or that creates a  
unique or unusual explosion hazard must be reported as a serious accident.  
A detailed accident report must be submitted by the owner’s or user’s insurance  
company boiler inspector.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5226 Restamping of boilers.  
Rule 226. When the stamping on a boiler becomes indistinct, the inspector shall  
instruct the owner or user to have it restamped. A request for permission to restamp the  
boiler must be made to the chief inspector and proof of the original stamping must  
accompany the request made to the chief inspector. Restamping authorized by the chief  
inspector must only be done by an inspector, and must be identical with the original  
Page 24  
stamping, except that it is not required to restamp the ASME code symbol. A notice of  
completion of restamping must be filed with the chief inspector by the inspector who  
stamped the boiler, together with a facsimile of the stamping applied.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5227 Condemned boilers.  
Rule 227. A boiler that has been inspected and declared unsafe by the chief inspector,  
deputy inspector, or special inspector and that the owner has determined will be scrapped  
must be placed out of service and stamped or labeled with the word “condemned.” The  
stamping must be as shown by the facsimile submitted under R 339.5226 and must be  
situated in several conspicuous locations as shown below and as determined by the  
inspector:  
-CONDEMNED-  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5231 Reinstallation of boilers repaired out of state.  
Rule 231. Repairs conducted outside of this state to boilers or pressure parts of boilers  
that will be reinstalled in this state must be conducted by an organization in possession of  
valid certificate of authorization to repair boilers. The organization shall conduct the  
repair pursuant to the NBIC and submit all forms to the department’s boiler division  
required by the NBIC.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5232 Nonstandard boilers.  
Rule 232. (1) An individual may petition the board to approve the use of a  
nonstandard boiler. Upon receipt of the petition, the board shall require the appropriate  
testing and evaluation for the nonstandard boiler to determine whether construction is  
equivalent to standards adopted by reference in R 339.5205.  
(2) A boiler owner requesting to have a special installation and operation permit shall  
submit the following items to the board of boilers rule, as applicable, in the English  
language and units:  
A list of all existing or proposed design and service conditions, maximum allowable  
working pressure (MAWP) and temperature, internal and external loading, corrosion and  
erosion allowance, heat treatment, and service requirements or service conditions.  
Documentation that the manufacture of the boiler is based on requirements from the  
applicable ASME code section as follows:  
Power boilers- section I.  
Materials specifications- section II.  
Nuclear power plant components- section III, divisions 1 and 2.  
Heating boilers- section IV.  
Page 25  
Pressure vessels- section VIII, divisions 1 and 2.  
Welding and brazing qualifications- section IX.  
Fiberglass- reinforced plastic pressure vessels- section X.  
Power piping- ASME B31.1.  
(3) If the design, construction, and certification were not based on ASME code rules,  
the manufacturer of the boiler shall provide a copy of the design rules and show how they  
meet or exceed the ASME code requirements by providing the following:  
A complete set of design drawings showing weld joint details and construction  
including internal and external attachments.  
A list of all pressure boundary materials or those materials and the material’s  
thickness subject to stress due to pressure and loading. The list must include a material  
specification to meet or exceed the applicable ASME codes specification. If material used  
is a specification other than referenced in the applicable ASME code section, the  
manufacturer of the boiler, through the owner, shall submit a copy of the material  
specifications used in the vessel construction and indicate how it is considered equivalent  
to the ASME code stress value permitted for materials in the applicable ASME code  
section.  
Documentation of any mill identification, including location of identification.  
Manufacturers’ materials test reports and traceability including test reports required  
by applicable code section.  
Welding or brazing procedure specifications and welder or brazer performance  
qualification records.  
Non Destructive Examination (NDE) procedures and results of examinations.  
Record of pressure test or proof test.  
Documentation showing the quality assurance program used by the manufacturer is  
equivalent to requirements of the ASME code.  
Identification of the inspection agency performing inspections and certifying the  
manufacturer’s data report or equivalent.  
Evidence of qualification or certification of the inspection agency by a jurisdictional  
authority.  
Documentation to show that inspectors making certification inspections have been  
certified as required by the jurisdictional authority. Individual names and national board  
commission number, if any, must be provided. System of supervisory control of  
inspection must be included.  
Documentation of fabrication inspections by the manufacturer and inspection agency.  
An internal and external inspection report by inspection agency inspectors.  
A facsimile of the nameplate or stamping.  
A copy of the manufacturer’s data report or equivalent document certified by the  
manufacturer and the inspection agency’s inspector.  
A copy of any code or standard used for design or construction.  
(4) The original code of construction must be used to establish the allowable stresses  
and joint efficiencies when calculating the MAWP of a vessel.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 26  
R 339.5233 Clearance between boilers and other objects.  
Rule 233. (1) A licensee performing an installation shall ensure the installation is  
made pursuant to the NBIC part 1 section 2.3.3 and 3.3.4, except for the requirement that  
the minimum clearance of 24 inches is provided between a boiler, its controls, firing  
equipment, and appurtenances and the building walls and partitions or other boilers or  
machinery.  
The licensee shall ensure that clearances are pursuant to the manufacturer’s  
instructions where required clearances are greater than the minimum required by this  
rule. The boiler owner shall ensure that the clearances are maintained for the life of the  
boiler and not infringed upon by items in storage.  
The elevation of a boiler above the floor must be as specified in R 408.30901a to R  
408.30996.  
A licensee may request a deviation from the requirements of this rule by submitting a  
drawing and the manufacturer’s installation requirements to the chief inspector for review  
and approval before installation of the boiler. The licensee shall be notified by the chief  
inspector of the approval or denial of the request.  
Where applicable, the boiler installation clearances must comply with R 408.30801 to  
R 408.30880.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5234 Steam kettles.  
Rule 234. (1) A fired or electrically heated steam kettle, irrespective of size, that has  
piped feed connections must comply with these rules.  
A fired or electrically heated kettle, irrespective of size without feed piping  
connections, must comply with these rules. Instead of an installation permit, an owner or  
user shall report the installation to the chief inspector before the unit is operated. The  
chief inspector shall assign a deputy inspector to visit the installation location to inspect  
the kettle to determine its safety for operations. A kettle that is operated at or below 15  
psi must be inspected biennially. A kettle that is operated at more than 15 psi must be  
inspected annually.  
Steam kettles manufactured to ASME section VIII division-1 2019 must have the  
minimum appurtenances and controls that are required in mandatory appendix 19.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5235 Safety appurtenances and controls.  
Rule 235. An individual shall not attempt to remove, or do any work on, any safety  
appurtenance or control prescribed by these rules while a boiler is in operation. If an  
appurtenance or control is repaired during an outage of a boiler, it must be reinstalled and  
in proper working order before the appurtenance or control is placed back in service. A  
person shall not load the safety valves to maintain a working pressure of more than that  
stated on the certificate of inspection.  
Page 27  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5236 Prevention of contamination of potable water supply.  
Rule 236. The boiler owner shall ensure that a boiler has proper connections to the  
potable water supply system to prevent contamination. The connections must be as  
specified in R 408.30701 to R 408.30796.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5237 Platforms.  
Rule 237. (1) A platform must be installed at 1 end of all drums of a water tube boiler  
that are more than 4 feet above the floor or walkway to permit safe access to the interior  
of the drums for cleanout and inspection.  
An inspector shall notify the owner or user who is required to conform to this rule and  
give written notice of a violation to the owner or user that the installation of the required  
stairway, runaway, platform, or ladder is to be made. The owner or user is allowed 1 year  
from the date of the violation to complete the work.  
A licensee may request a deviation from the requirements of this rule by submitting  
drawings to the chief inspector for review and approval before installation of the boiler.  
The chief inspector shall notify the licensee of the approval or denial of the request.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5238 Exits from boiler rooms.  
Rule 238. An owner shall ensure that the exit from a boiler room complies with the  
requirements specified in R 408.30401 to R 408.30499a.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5240 Age limit of nonstandard existing steam boilers.  
Rule 240. The age limit of any existing steam boilers of nonstandard construction,  
installed before July 1, 1966, is 30 years except that after a thorough internal and external  
inspection and a hydrostatic pressure of 1-1/2 times the allowable working pressure and  
held for a period of at least 30 minutes, during which no distress or leakage develops, any  
boilers having other than a lap-riveted longitudinal joint may be continued in operation  
without reduction in working pressure.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5241 Age limit of lap seam boilers.  
Page 28  
Rule 241. The age limit of any boiler having lap-riveted longitudinal joints and  
operating at a pressure in excess of 50 psi is 20 years. This type of boiler, when removed  
from an existing setting, must not be reinstalled at a pressure in excess of 15 psi. A  
reasonable time for replacement, not to exceed 1 year, may be given at the discretion of  
the chief inspector.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5242 Lap seam crack.  
Rule 242. The shell or drum of a boiler in which a typical lap seam crack is  
discovered along a longitudinal riveted joint or lap joints must be permanently  
discontinued for use under pressure. “Lap seam crack” as used in this rule, means the  
typical crack frequently found in lap seams extending parallel to the longitudinal joint  
and located either between or adjacent to rivet holes.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5243 Age limit of standard existing boilers.  
Rule 243. The age limit of any existing steam boilers of standard construction is  
dependent on a thorough internal and external inspection and hydrostatic pressure test of  
1-1/2 times the allowable working pressure for a period of 30 minutes. If a boiler under  
these test conditions exhibits no distress or leakage, it may continue to operate at the  
same working pressure.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5244 Portable boilers.  
Rule 244. Portable boilers, used for purely portable purposes and transported from  
place to place, must comply with the rules for new construction when reinstalled at a new  
location. These portable boilers must have a factor of safety of at least a 5.5 strength-to-  
strength ratio for butt-strap construction and a factor of not less than a 6 strength-to-  
strength ratio for lap-seam construction.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5245 Cast-iron headers and mud drums.  
Rule 245. The maximum allowable working pressure on a water-tube boiler, the tubes  
of which are secured to cast iron or malleable iron headers, or that have cast iron mud  
drums, must not exceed 160 p.s.i.g.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 29  
R 339.5246 Safety valves on connected boilers of different pressures.  
Rule 246. When 2 or more boilers operating at different pressures and safety valve  
settings are interconnected, the lower pressure boilers or interconnected piping must be  
equipped with safety valves of sufficient capacity to prevent overpressure, considering the  
maximum amount of steam that can flow into the lower pressure system.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5247 Hydrostatic testing of traction boilers.  
Rule 247. (1) A traction boiler designed to pull farm equipment or to convert steam  
power into flywheel energy driving farm apparatus, such as thrashers, saws, or grinding  
equipment, is subject to both of the following provisions:  
It must be tested hydrostatically every 3 years to a hydrostatic pressure of 1-1/2 times  
working pressure and held for sufficient time to permit visual observation of all seams,  
joints, supports, and attachments.  
All seams, attachments, supports, and joints must be exposed for each inspection.  
Traction boilers used for display or hobby purposes must not be operated for any  
other purpose except for the purpose that they were originally constructed.  
Lap seam boilers must not be operated in excess of 100 psi.  
Any repairs by welding or riveting to traction boilers must be made by licensed repair  
shops only after an approved permit has been obtained and subject to the approval of the  
inspector before and after repair is made.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5248 Miniature hobby locomotive boilers.  
Rule 248. (1) At the initial inspection of a miniature hobby locomotive boiler, the  
owner shall provide the chief boiler inspector with design specifications and calculations  
for review and acceptance. If a boiler is approved for use, then the department’s boiler  
division shall issue an identifying state number and a deputy boiler inspector shall attach  
it to the boiler.  
(2) The owner shall ensure that a miniature hobby locomotive boiler has all the  
following minimum equipment:  
A pressure gauge graduated to approximately 1-1/2 times the operating pressure, but  
not more than 4 times the operating pressure.  
A means to extinguish the fire in the firebox if of a low water condition.  
Two means of feeding water to the boiler, 1 of which must be operable while the  
locomotive is stationary.  
A water level gauge glass located so that the top of the bottom nut of the gauge glass  
is approximately 10% of the distance between the crown sheet and the shell, but not less  
than 1/2 inch above the crown sheet.  
Page 30  
Two safety valves set at not more than 10% above the operating pressure for boilers  
fabricated after the effective date of the rules. The capacity of the safety valves must be  
equal to or greater than the calculated steam generated capacity of the boilers.  
(3) The owner shall determine the maximum allowable working pressure of the  
miniature hobby locomotive boiler by calculation. In place of acceptable calculations, the  
owner shall subject the boiler to a hydrostatic pressure test of 1-1/2 times the owner  
specified operating pressure.  
(4) Every 3 years, during the certificate inspection, the owner shall hydrostatically  
test the boiler to not more than 1-1/2 times the operating pressure.  
(5) The department’s boiler division shall develop procedures, policies, and check  
lists necessary to accomplish the inspections and tests required by these rules.  
(6) Repairs to miniature hobby locomotive boilers are exempt from the licensing and  
permitting requirements of the act. Repair welding must be made pursuant to the  
requirements of ASME code section IX. Welding procedures and performance  
qualifications must be filed with the department’s boiler division for review.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5249 Failure to prepare boiler for internal inspection.  
Rule 249. If a boiler has not been properly prepared for an internal inspection, an  
inspector may decline to make the inspection or test, and a certificate blocking violation  
must be issued as provided in R 339.5221.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5250 Stripping of riveted boiler to determine required data.  
Rule 250. If a riveted boiler is jacketed so that the longitudinal seams of shells,  
drums, or domes cannot be seen, and if data cannot be determined by other means,  
enough of the jacketing, setting wall, or other form of casing or housing must be removed  
so that the size of the rivets, pitch of the rivets, and other data necessary to determine the  
safety of the boiler may be obtained.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5251 Replacement of heating or process boiler pressure relief device.  
Rule 251. When it is necessary to replace pressure relief devices on low pressure  
heating or process boilers for any reason, the replacement must be made with other than  
top-outlet type valves.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5252 Rerolling tubes.  
Page 31  
Rule 252. Rerolling a tube is considered maintenance, except rerolling a tube required  
as a result of an accident is considered a repair. This repair work requires a repair permit  
and must be performed by a licensed repairer.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5253 Qualified technical education program content; department  
approval; application and approval process, standards; fees.  
Rule 253. (1) An organization requesting approval of a qualified technical education  
program (QTEP) or an employer requesting approval of a qualified training program  
(QTP) pursuant to section 903(1)(e) and (f) of the act, MCL 339.5903, shall submit an  
application provided by the department. All applications must be complete. If an  
application is incomplete, a full evaluation is not possible, and the incomplete application  
will be disapproved. The applicant must be notified in writing, by the department’s boiler  
division, of the deficiencies within 30 days after the date that the application is received.  
A fee of $100.00 must accompany the application for the review.  
The QTEP and QTP are not required to address subject matter in refrigeration.  
An application and supporting documentation submitted to the department’s boiler  
division for QTEP and QTP for low or high pressure boiler operators must contain at a  
minimum, the subject matter listed in section 935 of the act, MCL 339.5935.  
An application and supporting documentation submitted to the department’s boiler  
division for QTEP or QTP intended for training third, second, and first class stationary  
engineers must contain the following subject matter in addition to the subjects listed in  
section 935 of the act, MCL 339.5935:  
(a) For a third-class stationary engineer, thermodynamic, applied science, applied  
mechanics, public acts and boiler codes, prime movers, water treatment, control  
instrumentation, and industrial legislation.  
(b) For a second-class stationary engineer, in addition to continuing training in the  
subjects listed in section 935 of the act, MCL 339.5935, and subdivision (a) of this  
subrule, the following subjects must be included:  
Metallurgy and material testing.  
Power plan systems.  
Mechanical drawing.  
Environmental protection.  
(c) For a first-class stationary engineer, in addition to continuing training in the  
subjects listed in section 935 of the act, MCL 339.5935, and subdivisions (a) and (b) of  
this subrule, the following subjects must be included:  
Principles of fluid mechanics.  
Thermodynamics and plant cycles.  
Applied engineering technologies.  
Safety, loss, and environmental management.  
Business and workforce management.  
(6) An application and supporting documentation submitted to the department’s boiler  
division for QTEP or QTP must contain all of the following general information:  
The name and address of the applicant and all training site addresses.  
Page 32  
Name and contact information of the individual responsible for the program.  
Policies and procedures for the selection of instructional staff.  
A statement of purpose and objectives of the program.  
Administrative and technical criteria for the development and delivery of the  
program.  
A description of the facilities, equipment, and instructional materials consistent with  
the purpose, design, and intended outcome of each learning experience in the program.  
A syllabus or course description, including contact hours and topics for each course.  
A statement of the criteria used to determine successful completion by participants in  
each of the training programs offered by the applicant.  
A list of instructional materials and other resources essential for the successful  
presentation of the program.  
(7) Approval of a program by the department must be evidenced by a program  
approval report prepared by the department’s boiler division and issued to the applicant.  
The report must include all of the following:  
Name and address of the applicant.  
Program identification number.  
The date of approval.  
The conditions of approval.  
(8) A program or amendment that has been approved by the department must not be  
altered. If an organization wishes to amend any part of a program, the organization shall  
submit a draft document clearly identifying the changes for department review. The  
organization shall not implement changes to the program without approval by the  
department. All changes must be submitted in writing for approval. The authorization  
must be in writing from the department.  
(9) The department shall have access to any location during the presentation of an  
approved program for the purpose of evaluation to determine compliance with an  
approved program.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 10. BUILDING OFFICIALS, INSPECTORS AND PLAN REVIEWERS  
R 339.5261 Applicability.  
Rule 261. These rules apply to all the following:  
(a) The registration and reregistration of all building officials, plan reviewers, and  
inspectors.  
(b) The approval of educational and training programs, required testing and  
instructors to qualify individuals for registration, reregistration as building officials, plan  
reviewers, or inspectors.  
(c)  
The minimum training and experience standards, qualifications, and  
classification of responsibility applicable to individuals who are engaged in the  
administration and enforcement of codes and plan reviews.  
Page 33  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5262 Educational and training program; program approval process;  
instructional qualifications.  
Rule 262. (1) A provider of an educational and training program shall apply for  
approval of the program by completing an application for program approval as provided  
by the department and submitting the application with the required fee to the department.  
(2) To qualify as an instructor of an educational and training program, an individual  
shall possess experience or education, or both, to supervise and instruct courses as  
required under section 1007 of the act, MCL 339.6007. An individual shall be at least 1  
of the following to qualify:  
(a) A licensed, certified, or approved instructor at any of the following in this state:  
A high school.  
An intermediate school district.  
A community college.  
A public or private university.  
The bureau of construction codes in the department.  
The Michigan occupational safety and health administration.  
Any other federal, state, or local governmental agency.  
(viii) A proprietary school licensed by the department.  
(b) Be currently licensed with at least 3 years of experience, and possess equivalent  
qualifications or relevant experience in the subject matter being taught.  
(3) The subject matter of educational and training programs must meet the minimum  
requirements of section 1007 of the act, MCL 339.6007, and must be relevant to the  
subject trade for which the applicant is seeking approval.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5263 Changes to program, provider information, or test.  
Rule 5263. (1) A provider of an approved education and training program or test who  
wants to make changes to the program, provider information, or test shall notify the  
department, in writing, at least 10 days before making any of the following changes:  
A change in the name of the applicant.  
A change in the address of the applicant.  
A change in the principal officers of an applicant organization.  
(2) Any changes with respect to the program must be made only when approved by  
the department in advance. If the illness of an instructor, natural disaster, or other  
emergency causes a change in the approved program, the provider shall notify the  
department at the earliest opportunity. A written notice that confirms the verbal report  
must be submitted to the department within 10 days after the verbal notification.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 34  
R 339.5264 Registration and reregistration; required hours of training; training  
categories; effective date.  
Rule 264. (1) An individual who is applying for renewal or reregistration shall  
complete not less than the required number of hours of continuing education in an  
approved educational or training program, as described in table 264 of this rule, in all the  
following categories:  
State public acts and state administrative rules, which must include programs and  
courses designed to enhance an individual’s understanding of technical writing, public  
speaking, laws, rules, and the administration and enforcement of related statutes and  
regulations.  
Technical, which must include programs and courses designed to enhance an  
individual’s understanding of state laws, state rules, and the state administration and  
enforcement of related statutes and regulations.  
Plan review, which must include programs to enhance an individual’s ability to  
review and approve residential and commercial construction documents to determine  
compliance with applicable codes, standards, and statutes.  
Specialty, which must include courses designed to increase an individual’s  
knowledge of inspection and construction techniques in the various registration  
classifications.  
(2) Continuing education is valid for reregistration only when accrued during an  
individual’s current 3-year registration period, except as provided in subrule (3) of this  
rule.  
(3) The department may approve any of the following types of educational or training  
programs for the purpose of satisfying registration or reregistration requirements by the  
individual.  
(a) Association programs that are sponsored by any of the following entities:  
Inspector organizations.  
Township, municipal, and county organizations.  
Professional and trade organizations.  
(b) Home study courses, such as online courses.  
(c) Private contractor technical update courses.  
(d) University, college, and community college courses.  
(e) Department-sponsored training programs.  
(f) Training sponsored by nationally recognized model code promulgating  
organizations, such as the International Code Council.  
(4) The department of the commission may approve the following educational or  
training association programs that are sponsored by any of the following entities to  
satisfy an individual’s registration or reregistration requirements:  
(a) Inspector organizations.  
(b) Township, municipal, and county organizations.  
(c) Professional and trade organizations.  
(5) Table 264 reads as follows:  
Table 264  
Hours Required for Reregistration  
Training Registration Classifications  
Page 35  
Category  
Building Inspector  
Plan Reviewer  
Official Building Electrical Mechanical Plumbing Building Electrical Mechanical Plumbing  
Rules and18 hrs (b) 4 hrs (b) 4 hrs (b) 4 hrs (b)  
Acts  
Technical 16 hrs (a) 16 hrs (a) 16 hrs (a) 16 hrs (a)  
4 hrs (b)  
4 hrs (b) 4 hrs (b) 4 hrs (b)  
4 hrs (b)  
16 hrs (a)  
8 hrs  
16 hrs (a) 16 hrs (a) 16 hrs (a) 16 (a)  
Plan  
2 hrs  
2 hrs  
2 hrs  
2 hrs  
2 hrs  
8 hrs  
12 hrs (a) 12 hrs (a) 12 hrs (a)  
40 hrs 40 hrs 40 hrs  
8 hrs  
8 hrs  
Review  
Specialty 8 hrs (a) 12 hrs (a) 12 hrs (a) 12 hrs (a)  
12 hrs(a)  
34 hrs  
12 hrs (a)  
rs  
Total 44 hrs 34 hrs 34 hrs 34 hrs  
(6) When applying for reregistration in 1 or more review classifications, including  
building, electrical, mechanical, and plumbing, the number of technical and specialty  
hours is per classification. If an individual is also a plan reviewer and is also applying for  
reregistration as either a building, electrical, mechanical, or plumbing inspector, the  
number of hours for a technical and specialty may be applied to the same plan reviewer  
classification, refer to table 264 subrule (5) of these rules.  
(7) When applying for reregistration in more than 1 plan reviewer or inspector  
classification, the number of acts and rules hours may be applied to more than 1  
registration classification, refer to table 264 subrule (5) of these rules.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5265 Building official registration qualifications.  
Rule 265. An individual who is applying for registration as a building official shall  
comply with all the following: File a completed application on a form provided by the  
department. Pay the applicable registration fee established under section 1023 of the act,  
MCL 339.6023.  
(c) Pay the applicable examination fee and pass an examination required by the act.  
(d) Provide documentation supporting that the applicant has 2 years of experience  
as a registered inspector or plan reviewer.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5266 Requirements for renewal of registration as a building official.  
Rule 266. (1) As a condition of renewal of a building official registration, an  
individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
(a) Submitting an online application for renewal as a building official as prescribed  
by the department and accompanied by the required fee of $25.00 per year of the  
registration.  
Page 36  
(b) Providing documentation supporting the successful completion of continued  
training and educational programs as approved by the department pursuant to section  
1007 of the act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements, if the building inspector holds additional inspection  
classifications, plan review classifications or other licenses under the act.  
(3) Successful completion of education for a building official includes of all the  
following:  
Eighteen hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to this state’s  
codes and various technical code provisions.  
Two hours of building plan review education.  
Eight hours of specialty training, which includes, but is not limited to, courses  
designed to increase a building official’s knowledge of inspection and construction  
techniques in the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial building official  
registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5270 Building inspector registration; qualifications.  
Rule 270. (1) An individual who is applying for registration as a building inspector  
shall comply with all the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass an examination required by the act.  
Provide documentation supporting that the individual has any of the following:  
(i) A residential builder’s license issued by this state and 6 years of experience  
immediately preceding application in any 1 or more of the following professions:  
A contractor in general building construction as a contractor.  
A skilled trades worker.  
An individual who was in charge of structural construction.  
(ii) A license as a building inspector from other states or foreign countries with  
inspector experience in building construction. The individual shall provide to the  
department the requirements of licensure for that state or country before he or she  
receives approval from the department.  
(iii) Seven years of experience in general building construction in any 1 or more of  
the- following professions:  
A building contractor.  
A person in charge of general building construction.  
Page 37  
A project manager, superintendent, supervisor, or foreman actively engaged in general  
building construction immediately preceding submission of the application.  
A skilled worker in structural carpentry, structural masonry, structural steel erection,  
or structural concrete construction who has been actively engaged in the general building  
construction field immediately preceding the submission of the application.  
Possesses a current license as an architect or engineer under the article 20 of the  
occupational code, 1980 PA 299, MCL 339.2001 to 339.2014.  
(2) Contractor and general building construction does not include a plumbing  
contractor’s license, an electrical contractor’s license, or a mechanical contractor’s  
license.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5290 Requirements for renewal of registration as a building inspector.  
Rule 290. (1) As a condition for renewal of a building inspector registration, an  
individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a building inspector as prescribed by  
the department and accompanied by the required fee of $25.00 per year of the  
registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the building inspector  
holds additional inspection classifications, plan review classifications, or other licenses  
under the act.  
(3) Successful completion of continued education for building inspectors includes all  
the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to this state’s  
codes and various technical code provisions.  
Two hours of building plan review education.  
Twelve hours of specialty training, including, but not limited to, courses designed to  
increase a building inspector’s knowledge of inspection and construction techniques in  
the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial building inspector  
registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 38  
R 339.5295 Requirements for renewal of registration as an electrical inspector.  
Rule 295. (1) As a condition of an electrical inspector registration, an individual  
shall meet the requirements of section 1011 of the act, MCL 339.6011, by doing both of  
the following:  
Submitting an online application for renewal as an electrical inspector as prescribed  
by the department and accompanied by the required fee of $25.00 per year of the  
registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the electrical inspector  
holds additional inspection classifications, plan review classifications, or other licenses  
under the act.  
(3) Successful completion of continued education for electrical inspectors includes all  
the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to this state’s codes  
and various technical code provisions.  
Two hours of electrical plan review education.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a building inspector’s knowledge of inspection and construction techniques in  
the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial electrical inspector  
registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300a Requirements for renewal of registration as a mechanical  
inspector.  
Rule 300a. (1) As a condition of renewal of a mechanical inspector registration, an  
individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a mechanical inspector, as prescribed  
by the department, and accompanied by the required fee of $25.00 per year of the  
registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the mechanical inspector  
Page 39  
holds additional inspection classifications, plan review classifications, or other  
licenses under the act.  
(3) Successful completion of continued education for a mechanical inspector includes  
all of the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Two hours of mechanical plan review education.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a mechanical inspector’s knowledge of inspection and construction techniques in  
the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial mechanical  
inspector registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300b Requirements for renewal of registration as a plumbing inspector.  
Rule 300b. (1) As a condition of renewal of a plumbing inspector registration, an  
individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a plumbing inspector, as prescribed  
by the department, and accompanied by the required fee of $25.00 per year of the  
registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the plumbing inspector  
holds additional inspection classifications, plan review classifications, or other licenses  
under the act.  
(3) Successful completion of continued education for a plumbing inspector includes  
of all the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Two hours of plumbing plan review education.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a plumbing inspector’s knowledge of inspection and construction techniques in  
the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.(5) This rule  
Page 40  
does not apply to an individual who obtains an initial plumbing inspector registration  
partially through a 3- cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300c Requirements for renewal of registration as a building plan  
reviewer.  
Rule 300c. (1) As a condition of renewal of a building plan reviewer registration, an  
individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a building plan reviewer, as  
prescribed by the department, and accompanied by the required fee of $25.00 per year of  
the registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the building plan reviewer  
holds additional plan review classifications, inspector classifications, or other licenses  
under the act.  
(3) Successful completion of continued education for a building plan reviewer  
includes all of the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a building plan reviewer’s knowledge of plan review and construction  
techniques in the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial building plan  
review registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300d Requirements for renewal of registration as an electrical plan  
reviewer.  
Rule 300d. (1) As a condition of a renewal of an electrical plan reviewer registration,  
an individual shall meet the requirements of section 1011 of the act. MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as an electrical plan reviewer, as  
prescribed by the department, and accompanied by the required fee of $25.00 per year of  
the registration.  
Page 41  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements, if the electrical plan reviewer holds additional plan review  
classifications, inspector classifications, or other licenses under the act.(3) Successful  
completion of continued education for an electrical plan reviewer includes all of the  
following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Eight hours of electrical plan review education.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase an electrical plan reviewer’s knowledge of plan review and construction  
techniques in the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial building plan  
review registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300e Requirements for renewal of registration as a mechanical plan  
reviewer.  
Rule 300e. (1) As a condition of renewal of a mechanical plan reviewer registration,  
an individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a mechanical plan reviewer, as  
prescribed by the department, and accompanied by the required fee of $25.00 per year of  
the registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5002.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements specified in subrule (1) of this rule, if the mechanical plan  
reviewer holds additional plan review classifications, inspector classifications, or other  
licenses under the act.  
(3) Successful completion of continued education for a mechanical plan reviewer  
includes all of the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Eight hours of mechanical plan review education.  
Page 42  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a mechanical plan reviewer’s knowledge of plan review and construction  
techniques in the various trades.  
(3) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(4) This rule does not apply to an individual who obtains an initial mechanical plan  
review registration partially through 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5300f Requirements for renewal of registration as a plumbing plan  
reviewer.  
Rule 300f. (1) As a condition of renewal of a plumbing plan reviewer registration,  
an individual shall meet the requirements of section 1011 of the act, MCL 339.6011, by  
doing both of the following:  
Submitting an online application for renewal as a plumbing plan reviewer, as  
prescribed by the department, and accompanied by the required fee of $25.00 per year of  
the registration.  
Providing documentation supporting the successful completion of continued training  
and educational programs as approved by the department pursuant to section 1007 of the  
act, MCL 339.6007, and required in R 339.5502.  
(2) The fee and continued training are in addition to any other fee and continued  
education requirements, if the plumbing plan reviewer holds additional plan review  
classifications, inspector classifications, or other licenses under the act.  
(3) Successful completion of continued education for a plumbing plan reviewer  
includes all of the following:  
Four hours of education regarding state public acts and state administrative rules  
directly related to this state’s construction regulations.  
Sixteen hours of education regarding technical knowledge related to state codes and  
various technical code provisions.  
Eight hours of plumbing plan review education.  
Twelve hours of specialty training including, but not limited to, courses designed to  
increase a plumbing plan reviewer’s knowledge of plan review and construction  
techniques in the various trades.  
(4) Failure to comply with all renewal requirements in the act or these rules will result  
in the denial of the registration renewal and the forfeiture of all renewal fees.  
(5) This rule does not apply to an individual who obtains an initial plumbing plan  
review registration partially through a 3-cycle registration cycle.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5301 Acts and rules; continuing education.  
Rule 301. (1) An individual who attends the acts and rules continuing education  
training, specified in R 339.5502, during his or her 3-year registration cycle will have  
Page 43  
satisfied the required training for all other registrations he or she may hold as an  
official, inspector, plan reviewer, or any other combination of those registrations for  
his or her renewal requirement. An individual who holds multiple registrations shall  
take the acts and rules continuing education training only once every 3-year  
registration cycle.  
(2) All other courses must be tailored to either the specific trade inspector  
classification, the trade plan reviewer classification, or the building official  
registration, to attain the total number of continuing education training hours required  
for each registration renewal.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5302 Building plan reviewer registration; qualifications.  
Rule 302. An individual who is applying for registration as a building plan  
reviewershall comply with all the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass an examination required by the act.  
Provide documentation supporting that the applicant has 1 of the following:  
(i) A residential builder’s license issued by this state and 6 years of experience  
immediately preceding application in any 1 or more of the following professions:  
General building construction as a contractor.  
Skilled trades worker.  
A person in charge of structural construction.  
(ii) A license as a building plan reviewer from another state or foreign country with  
plan reviewer experience in building construction. The individual shall provide to the  
department the requirements of licensure for that state or country before he or she  
receives approval from the department.  
(iii) Seven years of experience in general building construction in 1 or more of the  
following professions:  
A contractor.  
A skilled trades worker.  
An individual who was a person in charge of structural construction.  
(iv) An individual under paragraph (iii) of this subdivision must also possess 2 years  
of experience as a journey level, structural, construction, or skilled trades worker  
including as a carpenter, brick layer or mason, or steel worker.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5305 Electrical inspector registration; qualifications.  
Rule 305. An individual who is applying for an electrical inspector registration shall  
comply with all of the following:  
File a completed application on a form provided by the department.  
Page 44  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass an examination required by the act.  
Provide documentation supporting that the individual is licensed as an electrical  
journeyman or master electrician as required under section 1022 of the act, MCL  
339.6022.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5306 Electrical plan reviewer registration; qualifications.  
Rule 306. An individual who is applying for registration as an electrical plan reviewer  
shall comply with all of the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass an examination required by the act.  
Provide documentation supporting that the individual is licensed as an electrical  
journeyman or master electrician as required under section 1022 of the act, MCL  
339.6022.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5309 Mechanical inspector registration; qualifications.  
Rule 309. (1) An individual who is applying for registration as a mechanical inspector  
shall comply with all of the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass an examination required by the act.  
Hold a mechanical license from this state in 3 of the 4 following categories for at least  
1 year immediately preceding application:  
Hydronic heating and cooling and process piping.  
HVAC equipment.  
Refrigeration.  
Fire suppression.  
(2) If the individual does not hold a mechanical license from this state, as specified in  
subrule (1)(d) of this rule, he or she shall provide to the department an affidavit of  
experience from previous and current employers. The affidavit must comply with both of  
the following:  
(a) Attest that the individual has been actively engaged in the performance of  
mechanical work in 3 of the 4 following categories for 6 years under a licensed  
mechanical contractor:  
Hydronic heating and cooling process piping.  
HVAC equipment.  
Page 45  
Refrigeration.  
Fire suppression.  
(b) Attest that the licensed mechanical contractor who supervised the applicant was  
licensed in the required category at the time of supervision.  
(3) If the individual holds a license as a mechanical inspector from another state or  
foreign country with inspector experience in mechanical code enforcement, he or she  
shall provide to the department proof of licensure and the requirements of licensure for  
that state or country to be eligible to receive approval from the department.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5400 Mechanical plan reviewer registration; qualifications.  
Rule 400. (1) An individual who is applying for registration as a mechanical plan  
reviewer shall comply with all the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass a required examination established under  
section 321 of the act, MCL 339.5321.  
Hold a mechanical license from this state in 3 of the 4 following categories, for at  
least 1 year immediately preceding application:  
Hydronic heating and cooling process piping.  
HVAC equipment.  
Refrigeration.  
Fire suppression.  
(2) If the individual does not hold a mechanical license in this state, as specified in  
subrule (1)(d) of this rule, he or she shall provide to the department an affidavit of  
experience from previous and current employers. The affidavit must comply with both  
of the following:  
(a) Attest that the applicant has been actively engaged in the performance of  
mechanical work for 6 years under a licensed mechanical contractor in 3 of the 4  
following categories:  
Hydronic heating and cooling and process piping.  
HVAC equipment.  
Refrigeration.  
Fire suppression.  
(b) Attest that the licensed mechanical contractor or contractors who supervised the  
applicant were licensed in the required category or categories at the time of supervision.  
(3) If the individual holds a license as a mechanical plan reviewer from another state  
or foreign country with inspector experience in mechanical code enforcement, he or she  
shall provide to the department proof of licensure and the requirements of licensure for  
that state or country to be eligible to receive approval from the department.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 46  
R 339.5405 Plumbing inspector registration; qualifications.  
Rule 405. (1) An individual who is applying for registration as a plumbing inspector  
shall comply with all the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the applicable examination fee and pass a required examination, established  
under section 321 of the act, MCL 339.5321.  
Provide documentation supporting that the individual has either of the following:  
A journey plumbers license from this state for at least 2 years immediately preceding  
application for registration.  
A current master plumbing license from this state.  
(2) If the individual does not hold a plumber license from this state, as specified in  
subrule (1)(d) of this rule, he or she shall provide an affidavit of experience to the  
department from previous and current employers. The affidavit must attest that he or she  
was actively engaged in the performance of plumbing work for 5 years under a licensed  
plumbing contractor.  
(3) If an individual holds a license as a plumbing inspector from another state or  
foreign country with inspector experience in plumbing code enforcement, he or she shall  
provide to the department proof of licensure and the requirements of licensure for that  
state or country to be eligible to receive approval from the department.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5406 Plumbing plan reviewer registration; qualifications.  
Rule 406. (1) An individual who is applying for registration as a plumbing plan  
reviewer shall comply with all of the following:  
File a completed application on a form provided by the department.  
Pay the applicable registration fee established under section 1023 of the act, MCL  
339.6023.  
Pay the required examination fee, established under section 407 of the act, MCL  
339.5407.  
Provide documentation proving that the individual has either of the following:  
A journey plumbers license from this state for at least 2 years immediately preceding  
application for registration.  
A master plumber license from this state.  
If the individual does not hold a plumber license from this state, as specified in  
subrule (1)(d) of this rule, he or she shall provide to the department an affidavit of  
experience from previous and current employers. The affidavit must attest to the  
applicant having been actively engaged in the performance of plumbing work for 5 years  
under a licensed plumbing contractor.  
If an individual holds a license as a plumbing plan reviewer from another state or  
foreign country with plan review experience in plumbing code enforcement, he or she  
Page 47  
shall provide to the department proof of licensure and the requirements of licensure for  
that state or country to be eligible to receive approval from the department.  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5408 Provisional registration.  
Rule 408. (1) An individual may apply for a provisional registration as a building  
inspector or building plan reviewer provided, he or she meets the requirements as  
specified in section 219 of the act, MCL 339.5219.  
(2) An applicant may apply for a provisional registration as an inspector or plan  
reviewer in the plumbing trade provided he or she meets the requirements as specified in  
section 219 of the act, MCL 339.5219.  
(3) An applicant may apply for a provisional registration as an inspector or plan  
reviewer in the electrical trade provided, he or she meets the requirements as outlined in  
section 219 of the act, MCL 339.5219.  
(4) An applicant may apply for a provisional registration as an inspector or plan  
reviewer in the mechanical trade provided he or she meets the requirements as  
specified in section 219 of the act, MCL 339.5219.  
(5) If an individual is unable to qualify for a provisional license under section 219  
of the act, MCL 339.5219, he or she shall do all of the following:  
(a) Submit his or her work experience for the previous 6 years detailing work  
performed in the trade related to the trade classification for which he or she is applying.  
(b) Submit all education obtained during the same 6-year period.  
(c) Submit 3 letters of reference from former clients for whom the applicant  
provided services within the 6 years immediately preceding application.  
(6) An individual who is provisionally registered, pursuant to section 1021 of the act,  
MCL 339.6021, shall not perform the duties and responsibilities of an inspector or plan  
reviewer until he or she has met all requirements for full registration.  
History: 2023 MR 8, Eff. May 3, 2023.  
PART 11. PLUMBING AND PLUMBING CONTRACTORS  
R 339.5411 Master plumber and plumbing contractors; changes in employment  
status; license suspension.  
Rule 411. (1) If a master plumber ceases to represent a plumbing contractor, both the  
plumbing contractor and the master plumber who was employed by the plumbing  
contractor shall notify the department immediately of any changes in the employment  
status of the master plumber.  
(2) The contractor license may be summarily suspended pursuant to section 507 of  
the act, MCL 339.5507, until the contractor designates an employee or officer who is a  
licensed master plumber to represent the plumbing contractor license.  
Page 48  
History: 2023 MR 8, Eff. May 3, 2023.  
R 339.5412 Journey plumbing examinations.  
Rule 412. (1) To obtain a journey license, an applicant shall take and pass the 2-part  
examination. The examination includes both a practical skill portion and a written  
examination portion.  
An applicant will have 365 days, beginning the date of receipt of the application, to  
achieve licensure.  
Failure to pass both the written examination and the practical skill portion of the  
examination, within 365 days after receipt of application, will result in forfeiture of any  
fees paid to the department and the application being voided under the act.  
To obtain licensure after the expiration of the 365 days, an applicant shall submit a  
new application and fees and meet the registration requirements in place at the time of the  
new application, including taking the journey plumbing examination and successfully  
passing both parts of the examination that is in effect on the date the department received  
the new application.  
History: 2023 MR 8, Eff. May 3, 2023.  
Page 49  
;