DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
DIRECTOR'S OFFICE  
CONSTRUCTION CODE  
(By authority conferred on the director of the department of licensing and regulatory  
affairs by section 4 of the Stille-DeRossett-Hale single state construction code act, 1972  
PA 230, MCL 125.1504, and Executive Reorganization Order Nos. 2003-1, 2008-4, and  
2011-4, MCL 445.2011, 445.2025, and 445.2030)  
PART 5. RESIDENTIAL CODE  
R 408.30500 Applicable code.  
Rule 500. The provisions of the international residential code, 2015 edition, including  
appendices A, B, C, D, E, F, G, J, K, N, O, P, R, and S except for Sections R 104.2, R  
104.3, R 104.5, R 104.7, R 104.8, R 104.8.1, R 105.3, R 105.3.1, R 105.3.2, R 105.6, R  
105.9, R 108.3, R 108.4, R 108.5, R 108.6, R 109.1, R 112.2, R 112.3, R 112.4, R 113.1  
to R 113.3, R 113.4, R 114.1 and R 114.2, R 313.1.1 to R 313.2.1, R 602.11, R 602.12,  
N1102.3.2, tables R 507.2.3, N1101.12.3(3) and figure R 507.2.1(2), R 507.2.3(1), R  
507.2.3(2), and R 507.2.4, sections M1411.8, G2411.1.1.1 to G2411.1.1.5, G2439.7.2,  
P2503.9, P2709.2.3, P2904.1.1 to P2904.8.2, P2905.1, P2905.2, figure P2904.2.4.2, table  
P2904.2.2, tables P2904.6.2(1) to P2904.6.2(9), P3009.1 to P3009.11.1, E3902.15,  
E3902.16, E3902.17, and AJ102.4, the IBC-2015, IECC-2015, IMC-2015, IPC-2015,  
NFPA 70-2014 listed in chapter 44 govern the construction, alteration, relocation,  
demolition, use, and occupancy of buildings and structures, and, with the exceptions  
noted, the international residential code is adopted by reference in these rules. All  
references to the International Building Code, International Residential Code,  
International Energy Conservation Code, National Electrical Code, International Existing  
Building Code, International Mechanical Code, and International Plumbing Code mean  
the Michigan Building Code, Michigan Residential Code, Michigan Energy Code,  
Michigan Electrical Code, Michigan Rehabilitation Code for Existing Buildings,  
Michigan Mechanical Code, and Michigan Plumbing Code, respectively. The code is  
available for inspection and purchase at the Department of Licensing and Regulatory  
Affairs, Bureau of Construction Codes, 611 W. Ottawa St., 1st Floor Ottawa Building,  
Lansing, Michigan 48933. The code may be purchased from the International Code  
of adoption of these rules of $118.00.  
History: 2015 AACS; 2021 AACS; 2022 MR 2, Eff. Feb. 8, 2022.  
R 408.30501 Title.  
Rule 501. Section R101.1 of the code is amended to read as follows:  
Page 1  
R101.1. Title. These provisions shall be known and cited as the Michigan residential  
code for 1-and 2-family dwellings and will be referred to as “the code.”  
History: 2001 AACS; 2010 AACS; 2015 AACS.  
R 408.30501a Scope.  
Rule 501a. Section R101.2 of the code is amended to read as follows:  
R101.2. Scope. The provisions of the Michigan residential code for 1- and 2-family  
dwellings shall apply to the construction, alteration, movement, enlargement,  
replacement, repair, equipment, use and occupancy, location, removal and demolition of  
detached 1- and 2-family dwellings and townhouses not more than 3 stories above grade  
plane in height with a separate means of egress and their accessory structures.  
Exceptions:  
1. Live/work units complying with the requirements of Section 419 of the Michigan  
building code may be built as 1- and 2-family dwellings or townhouses. Fire suppression  
required by Section 419.5 of the Michigan building code when constructed under the  
Michigan residential code for 1- and 2-family dwellings shall conform to Section P2904.  
2. Owner-occupied bed and breakfast and board and room facilities may be  
constructed in accordance with sections 4b and 13c of the Stille-DeRossett-Hale single  
state construction code act, 1972 PA 230, MCL 125.1504b and MCL 125.1513c.  
History: 2015 AACS.  
R 408.30501b Intent.  
Rule 501b. Sections 101.3 and 101.4 of the code are amended to read as follows:  
R101.3. Intent. The purpose of this code is to establish minimum requirements to  
safeguard the public safety, health, and general welfare through affordability, structural  
strength, means of egress facilities, stability, sanitation, light and ventilation, energy  
conservation, and safety to life and property from fire and other hazards attributed to the  
built environment, and to provide safety to fire fighters and emergency responders during  
emergency operations. The Stille-DeRossett-Hale single state construction code act, 1972  
PA 230, MCL 125.1501 to MCL 125.1531 takes precedence over all provisions of this  
code.  
R101.4. Severability. If any section, subsection, sentence, clause, or phrase of this  
code is found to be invalid by a court of competent jurisdiction, such decision will not  
affect the validity of the remaining portions of this code.  
History: 2021 MR 11, Eff. Oct. 4, 2021.  
R 408.30501c Existing structures.  
Rule 501c. Section 102.7 is amended to read as follows:  
R102.7. Existing structures. The legal occupancy of any structure existing on the  
date of adoption of this code shall be permitted to continue without change, except as is  
specifically covered in this code, the international property maintenance code, or the  
Page 2  
international fire code, or as allowed under the Stille-DeRossett-Hale single state  
construction code act, 1972 PA 230, MCL 125.1501 to MCL 125.1531.  
History: 2021 MR 11, Eff. Oct. 4, 2021.  
R 408.30502 Rescinded.  
History: 2001 AACS; 2011 AACS.  
R 408.30503 Approved materials and equipment.  
Rule 503. Sections R104.9 of the code is amended to read as follows:  
R104.9. Approved materials and equipment. Materials, equipment, and devices  
shall be constructed or installed in accordance with approvals granted under the act or by  
the building official. The building official shall review reports prepared by recognized  
evaluation services and determine if the intent of the code is met.  
History: 2001 AACS; 2004 AACS; 2008 AACS.  
R 408.30504 Duties and powers of building official.  
Rule 504. Sections R104.6 of the code are amended to read as follows:  
R104.6. Right of entry. If a building or premises is occupied, the code official shall  
present his or her credentials to the occupant and request entry. If a building or premises  
is unoccupied, the code official shall first make a reasonable effort to locate either the  
owner, the owner’s authorized agent or other person having care or control of the  
building or premises and request entry. If entry is refused, the code official has recourse  
to every remedy provided by law to secure entry.  
When a code official has first obtained a proper inspection warrant or other remedy  
provided by law to secure entry, the owner, owner’s authorized agent or occupant or  
person having charge, care or control of the building or premises shall not fail or neglect,  
after a proper request is made as provided in this rule, to permit the code official prompt  
entry into the building or premises to inspect or examine the building or premises  
pursuant to this code.  
History: 2001 AACS; 2008 AACS; 2010 AACS; 2021 MR 11, Eff. Oct. 4, 2021.  
R 408.30505 Work exempt from permit.  
Rule 505. Section R105.2 of the code is amended to read as follows:  
R105.2. Work exempt from permit. Exemption from the permit requirements of the  
code shall not be deemed to grant authorization for any work to be done in any manner in  
violation of the provisions of the code or any other laws or ordinances of this jurisdiction.  
Permits are not required for any of the following:  
(a) Building permits shall not be required for any of the following:  
(i) One-story detached accessory structures, if the floor area does not exceed 200  
Page 3  
square feet (18.58 m2).  
(ii) A fence that is not more than 7 feet (2 134 mm) high.  
(iii) A retaining wall that is not more than 4 feet (1 219 mm) in height measured  
from the bottom of the footing to the top of the wall, unless supporting a surcharge.  
(iv) A water tank supported directly upon grade if the capacity is not more than  
5,000 gallons (18 927 L) and the ratio of height to diameter or width is not greater  
than 2  
to 1.  
(v) A sidewalk and driveway not more than 30 inches (762 mm) above adjacent  
grade and not over any basement or story below and not part of an accessible route.  
(vi) Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish  
work.  
(vii) A prefabricated swimming pool that is less than 24 inches (610 mm) deep, and  
not greater than 5,000 gallons (18 925 L), and is installed entirely above ground.  
(viii) Swings and other playground equipment accessory to detached 1- or 2-family  
dwellings.  
(ix) Window awnings in group R-3 and U occupancies, supported by an exterior  
wall that do not project more than 54 inches (1 372 mm) from the exterior wall and  
do not require additional support, as applicable in Section 101.2 and group U  
occupancies.  
(x) Decks, porches, patios, landings, or similar structures not exceeding 200 square  
feet (18.58 m2) in area, that are not more than 30 inches (762 mm) above grade at any  
point as prescribed by Section R312.1.1, are not attached to a dwelling or its accessory  
structures, are not within 36 inches (914 mm) of a dwelling or its accessory structures,  
and do not serve any ingress or egress door of the dwelling or its accessory structures.  
(b) Electrical permits shall not be required, as in accordance with the Michigan  
electrical code, R 408.30801 to R 408.30880, for any of the following:  
(i) Repairs and maintenance: Minor repair work, including the replacement of lamps  
or the connection of approved portable electrical equipment to approved permanently  
installed receptacles.  
(ii) Radio and television transmitting stations: The provisions of the code do not  
apply to electrical equipment used for radio and television transmissions, but do apply to  
equipment and wiring for power supply and to the installation of towers and antennas.  
(iii) Temporary testing systems: A permit is not required for the installation of any  
temporary system required for the testing or servicing of electrical equipment or  
apparatus.  
(c) Mechanical permits shall not be required for any of the following:  
(i) A portable heating or gas appliance that has inputs of less than 30,000 BTU’s per  
hour.  
(ii) Portable ventilation appliances and equipment.  
(iii) A portable cooling unit.  
(iv) Steam, hot water, or chilled water piping within any heating or cooling  
equipment or appliances regulated by this code.  
(v) Replacement of any minor part that does not alter the approval of equipment or  
an appliance or make such equipment or appliance unsafe.  
(vi) A portable evaporative cooler.  
Page 4  
(vii) Self-contained refrigeration systems that contain 10 pounds (4.5 kg) or less of  
refrigerant, or that are actuated by motors of 1 horsepower (0.75kW) or less.  
(viii) Portable fuel cell appliances that are not connected to a fixed piping system  
and are not interconnected to a power grid.  
(ix) An oil burner that does not require connection to a flue, such as an oil stove and  
a heater equipped with a wick.  
(x) A portable gas burner that has inputs of less than 30,000 BTU’s per hour.  
(xi) When changing or relocating a gas meter or regulator, a permit is not required  
when installing gas piping which shall be limited to 10 feet (3 005 mm) in length and not  
more than 6 fittings.  
(xii) When installing geothermal vertical closed loops under the supervision of a  
mechanical contractor licensed in HVAC as long as the company meets both the  
following:  
(A) Has obtained a certificate of registration as a well drilling contractor pursuant to  
part 127 of the public health code, 1978 PA 368, MCL 333.12701 to 333.12771.  
(B) Has installed the geothermal vertical closed loops in accordance with the  
department of environment, Great Lakes, and energy's best practices regarding  
geothermal heat pump closed loops. Exemption from the permit requirements of this code  
shall not be deemed to grant authorization for work to be done in violation of the  
provisions of this code or other laws or ordinances of this jurisdiction.  
(d) Plumbing permits shall not be required for either of the following:  
(i) The stopping of leaks in drains, water, soil, waste or vent pipe. If any concealed  
trap, drainpipe, water, soil, waste or vent pipe becomes defective and it becomes  
necessary to remove and replace the same with new material, then the work is considered  
as new work and a permit shall be obtained and inspection made as provided in the code.  
(ii) The clearing of stoppages or the repairing of leaks in pipes, valves, or fixtures,  
and the removal and reinstallation of water closets, if the repairs do not involve or require  
the replacement or rearrangement of valves, pipes, or fixtures.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS; 2015 AACS; 2021 MR 11, Eff. Oct.  
4, 2021.  
R 408.30506 Submittal documents.  
Rule 506. Sections R 106.1.4 and R802.10.1 of the code are amended and  
Section R106.1.4 and figure 802.10.1 are added to the code to read as follows:  
R106.1.4. Truss design data. As an alternative to the submission of truss design  
drawings, figure R802.10.1, the truss design data sheet, may be provided to the building  
official as part of the construction documents at the time of application. Truss design  
drawings shall be submitted to the building official prior to truss installation as required  
by Section R802.10.1.  
R802.10.1 Truss design drawings. Truss design drawings,  
prepared in conformance with Section R802.10.1, shall be provided to the building  
official and approved prior to installation. The truss design data sheet, figure R802.10.1,  
may be provided to the building official at the time of permit application, as an  
alternative to design drawings as permitted in Section R106.1.4. Truss design drawings  
shall include, at a minimum, the information specified below. Truss design drawings  
shall be provided with the shipment of trusses delivered to the jobsite.  
Page 5  
(1) Slope or depth, span, and spacing.  
(2) Location of all joints.  
(3) Required bearing widths.  
(4) Design loads as applicable.  
(a) Top chord live load (including snow loads).  
(b) Top chord dead load.  
(c) Bottom chord live load.  
(d) Bottom chord dead load.  
(e) Concentrated loads and their points of application.  
(f) Controlling wind and earthquake loads.  
(5) Adjustments to lumber and joint connector design values for conditions of use.  
(6) Each reaction force and direction.  
(7) Joint connector type and description (e.g., size, thickness, or gauge) and the  
dimensioned location of each joint connector except where symmetrically located relative  
to the joint interface.  
(8) Lumber size, species, and grade for each member.  
(9) Connection requirements for the following:  
(a) Truss to truss girder.  
(b) Truss ply to ply.  
(c) Field splices.  
(10) Calculated deflection ratio and/or maximum description for live and total load.  
(11) Maximum axial compression forces in the truss members to enable the building  
designer to design the size, connections, and anchorage of the permanent continuous  
lateral bracing. Forces shall be shown on the truss design drawing or on supplemental  
documents.  
(12) Required permanent truss member bracing location.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS; 2015 AACS; 2021 MR 11, Eff. Oct.  
4, 2021.  
R 408.30507 Duct termination.  
Rule 507. Section M1502.3 of the code is amended to read as follows:  
M1502.3. Exhaust ducts shall terminate on the outside of the building. Exhaust duct  
terminations shall be in accordance with the dryer manufacturer’s installation  
instructions. If the manufacturer’s instructions do not specify a termination location, the  
exhaust duct shall terminate no less than 3 feet (914 mm) in any direction from openings  
into buildings or ventilated section in a soffit. Exhaust duct terminations shall be  
equipped with a backdraft damper. Screens shall not be installed at the duct termination.  
History: 2001 AACS; 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30508 Payment of fees.  
Rule 508. Section R108.1 of the code is amended to read as follows:  
R108.1. Fees. The fees prescribed in the act shall be paid to the enforcing agency  
of the jurisdiction before a permit to begin work for new construction, alteration,  
Page 6  
removal, demolition, or other building operation may be issued. In addition, an  
amendment to a permit necessitating an additional fee shall not be approved until the  
additional fee is paid.  
History: 2001 AACS; 2004 AACS.; 2008 AACS.  
R 408.30509 Frame and masonry inspection.  
Rule 509. Section R109.1.4 of the code is amended to read as follows:  
R109.1.4. Frame and masonry inspection. Inspection of framing construction shall  
be made after the roof, all framing, firestopping, draftstopping, and bracing are in place  
and after the plumbing, mechanical, and electrical rough inspections are approved.  
Masonry inspections shall be made after the completed installation of base course  
flashing as specified in section R703.7.5 of the code and water-resistive barrier as  
specified in section R703.2 of the code and after the masonry construction is completed.  
History: 2001 AACS; 2008 AACS.  
R 408.30509a Approval required.  
Rule 509a. Section R109.4 of the code is amended to read as follows:  
R109.4. Approval required. Work shall not be done beyond the point indicated in  
each successive inspection without first obtaining the approval of the building official.  
The building official upon notification shall make the requested inspections and shall  
either indicate the portion of the construction that is satisfactory as completed, or shall  
notify the permit holder or agent of the permit holder wherein portion of the construction  
fails to comply with this code. The notification shall include specific reference to the  
code chapter and section numbers in violation in writing. Any portions that do not  
comply shall be corrected and such portion shall not be covered or concealed until  
authorized by the building official.  
History: 2015 AACS.  
R 408.30510 Use and occupancy.  
Rule 510. Sections R110.1, R110.2, and R110.3 of the code are amended to read as  
follows:  
R110.1. Use and occupancy. A building or structure shall not be used or occupied,  
and a change in the existing occupancy classification of a building or structure or portion  
thereof shall not be made, until a certificate of occupancy has been issued in accordance  
with the act.  
R110.2. Change in use. A change in the character or use of an existing structure  
shall not be made, except as specified in the Michigan building code, R 408.30401 to  
R 408.30499.  
R110.3 Certificate issued. After the building official inspects the building or  
structure and finds no violations of the provisions of this code or other laws that are  
Page 7  
enforced by the department of building safety, the building official shall issue a  
certificate of occupancy which shall contain the following:  
(a) The building permit number.  
(b) The address of the structure.  
(c) A description of that portion of the structure for which the certificate is issued.  
(d) A statement that the described portion of the structure has been inspected for  
compliance with the requirements of this code.  
(e) The name of the building official.  
(f) The edition of the code under which the permit was issued.  
(g) Any special stipulations and conditions of the building permit.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2015 AACS.  
R 408.30510a Fire classification.  
Rule 510a. Section R902.1 is amended and Sections R902.3 and R902.4 of the code  
are added to read as follows:  
R902.1. Roof covering materials. Roofs shall be covered with materials as set forth  
in Sections R904 and R905. Class A, B, or C roofing shall be installed in jurisdictions  
designated by law as requiring their use or where the edge of the roof is less than 3 feet  
(914 mm) from a lot line. Classes A, B, and C roofing required by this section to be  
listed shall be tested in accordance with UL 790 or ASTM E 108.  
Exceptions:  
1. Class A roof assemblies include those with coverings of brick, masonry, and  
exposed concrete roof deck.  
2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal  
sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible decks.  
3. Class A roof assemblies include minimum 16 ounces per square foot copper  
sheets installed over combustible decks.  
4. Class A roof assemblies include slate installed over underlayment over  
combustible decks.  
History: 2015 AACS.  
R 408.30511 Violation penalties.  
Rule 511. Section R113.4 of the code is amended to read as follows:  
R113.4. Violation penalties. It is unlawful for any person, firm, or corporation to  
violate a provision of the code or fail to conform with any of the requirements thereof, or  
erect, construct, alter, extend, repair, move, remove, demolish, or occupy any building,  
structure, or equipment regulated by the code, or cause work to be performed or done in  
conflict with or in violation of the approved construction documents or directive of  
the enforcing agency, or a permit or certificate issued under the code. A violator shall be  
assessed a fine in accordance with the act.  
History: 2001 AACS; 2004 AACS; 2008 AACS.  
Page 8  
R 408.30512 Rescinded.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2015 AACS; 2021 MR 11, Eff. Oct. 4, 2021.  
R 408.30513 Definitions.  
Rule 513. The definitions of attic and sunroom addition in Section R202 of the code  
are amended to read as follows:  
R202. Definitions. “Attic, uninhabitable with limited storage” means uninhabitable  
attics with limited storage where the minimum clear height between joists and rafters is  
42 inches (1 063 mm) or greater or where there are not 2 or more adjacent trusses with  
web configurations capable of accommodating an assumed rectangle 42 inches (1 063  
mm) high by 24 inches (610 mm) in width, or greater, within the plane of the trusses.  
“Attic, uninhabitable without storage” means uninhabitable attics without storage where  
the maximum clear height between joists and rafters is less than 42 inches (1 063 mm), or  
where there are not 2 or more adjacent trusses with web configurations capable of  
accommodating an assumed rectangle 42 inches (1 063 mm) high by 24 inches (610 mm)  
in width, or greater, within the plane of the trusses. Building Inspector” means the  
individual who is responsible for the administration and enforcement of the construction  
of buildings, structures, or appurtenances under the state construction code specified in R  
408.30499 and who is registered in compliance with 2016 PA 407, MCL 339.5101 to  
339.6133. “Building Official” means the person who is appointed and employed by a  
governmental subdivision, who is charged with the administration and enforcement of the  
state codes specified in R 408.30499, and who is registered in compliance with 2016 PA  
407, MCL 339.5101 to 339.6133. “Registered design professional” means an individual  
who is licensed under the occupational code, 1980 PA 299, MCL 339.101 to 339.2919.  
“ Registered inspector” means an individual who is licensed under the occupational  
code, 1980 PA 299, MCL 339.101 to 339.2919."Sunroom addition" means a new  
structure with glazing in excess of 40% of the gross area of the structure's exterior walls  
and roof added to an existing dwelling.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS; 2015 AACS; 2021 MR 11, Eff. Oct.  
4, 2021.  
R 408.30514 Rescinded.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2015 AACS; 2021 MR 11, Eff. Oct. 4, 2021.  
R 408.30515 Ground snow loads.  
Rule 515. Figure R301.2(5) and Table R301.2(1) of the code are amended and  
Table R301.2(5) is added to the code to read as follows:  
Page 9  
Page 10  
Page 11  
Table R301.2(5)  
Michigan Ground Snow Loads by Jurisdiction  
County  
Ground Snow  
Jurisdictions  
ALCONA  
ALGER  
ALLEGAN  
50  
70  
50  
35  
All  
All  
All except:  
CITY OF ALLEGAN  
CITY OF OTSEGO  
CITY OF PLAINWELL  
CITY OF WAYLAND  
VILLAGE OF  
HOPKINS  
VILLAGE OF MARTIN  
TOWNSHIP OF  
ALLEGAN  
TOWNSHIP OF DORR  
TOWNSHIP OF GUN  
PLAIN  
TOWNSHIP OF  
HOPKINS  
TOWNSHIP OF  
LEIGHTON  
TOWNSHIP OF  
MARTIN  
TOWNSHIP OF  
MONTEREY  
TOWNSHIP OF  
OTSEGO  
TOWNSHIP OF SALEM  
TOWNSHIP OF  
TROWBRIDGE  
TOWNSHIP OF  
WATSON  
TOWNSHIP OF  
WAYLAND  
ALPENA  
ANTRIM  
50  
60  
All  
All except  
Page 12  
70  
TOWNSHIP OF BANKS  
TOWNSHIP OF CENTRAL  
LAKE TOWNSHIP OF ECHO  
TOWNSHIP OF JORDAN  
TOWNSHIP OF WARNER  
All  
ARENAC  
BARAGA  
BARRY  
40  
70  
35  
All  
All except:  
30  
VILLAGE OF NASHVILLE  
TOWNSHIP OF  
ASSYRIA  
TOWNSHIP OF BARRY  
TOWNSHIP OF  
JOHNSTOWN  
TOWNSHIP OF MAPLE  
GROVE  
Page 13  
BAY  
35  
40  
All except:  
CITY OF PINCONNING  
TOWNSHIP OF FRASER  
TOWNSHIP OF GARFIELD  
TOWNSHIP OF GIBSON  
TOWNSHIP OF MT.  
FOREST  
TOWNSHIP OF  
PINCONNING  
BENZIE  
BERRIEN  
BRANCH  
60  
50  
25  
20  
All  
All  
All except:  
TOWNSHIP OF ALGANSEE  
TOWNSHIP OF  
CALIFORNIA  
TOWNSHIP OF GILEAD  
TOWNSHIP OF  
KINDERHOOK  
TOWNSHIP OF OVID  
CALHOUN  
25  
All except:  
Page 14  
30  
CITY OF BATTLE CREEK  
CITY OF MARSHALL  
CITY OF SPRINGFIELD  
VILLAGE OF ATHENS  
TOWNSHIP OF  
ATHENS  
TOWNSHIP OF  
BATTLE  
CREEK  
TOWNSHIP OF  
BEDFORD  
TOWNSHIP OF CONVIS  
TOWNSHIP OF EMMET  
TOWNSHIP OF LEE  
TOWNSHIP OF LEROY  
TOWNSHIP OF  
MARENGO  
TOWNSHIP OF  
MARSHALL  
TOWNSHIP OF  
NEWTON  
TOWNSHIP OF  
PENNFIELD  
CASS  
30  
50  
All except:  
CITY OF DOWAGIAC  
VILLAGE OF  
CASSOPOLIS  
Page 15  
VILLAGE OF  
EDWARDSBURG  
TOWNSHIP OF HOWARD  
TOWNSHIP OF LA GRANGE  
TOWNSHIP OF  
MILTON  
TOWNSHIP OF  
POKAGON  
TOWNSHIP  
OF  
SILVER  
CREEK  
TOWNSHIP OF WAYNE  
CHARLEVOIX  
CHEBOYGAN  
70  
70  
60  
All  
All except:  
CITY OF CHEBOYGAN  
VILLAGE OF AFTON  
VILLAGE OF  
WOLVERINE  
TOWNSHIP OF ALOHA  
TOWNSHIP OF  
BENTON  
TOWNSHIP OF ELLIS  
TOWNSHIP OF  
GRANT  
TOWNSHIP OF  
KOEHLER  
TOWNSHIP OF NUNDA  
TOWNSHIP OF  
WALKER  
TOWNSHIP OF  
WAVERLY  
TOWNSHIP OF WILMOT  
50  
TOWNSHIP OF FOREST  
CHIPPEWA  
70  
60  
All except:  
VILLAGE OF DE TOUR  
TOWNSHIP OF  
DETOUR  
TOWNSHIP OF  
RABER  
Page 16  
CLARE  
40  
50  
All except:  
TOWNSHIP OF  
SUMMERFIELD  
TOWNSHIP OF  
WINTERFIELD  
CLINTON  
30  
35  
All except:  
CITY OF ST. JOHNS  
VILLAGE OF FOWLER  
VILLAGE OF MAPLE RAPIDS  
VILLAGE OF  
WESTPHALIA  
TOWNSHIP OF  
BENGAL  
TOWNSHIP OF  
DALLAS  
TOWNSHIP OF ESSEX  
TOWNSHIP OF  
GREENBUSH  
TOWNSHIP OF LEBANON  
TOWNSHIP OF  
WESTPHALIA  
CRAWFORD  
DELTA  
50  
60  
70  
All  
All except:  
TOWNSHIP OF GARDEN  
TOWNSHIP OF  
MASONVILLE  
TOWNSHIP OF NAHMA  
DICKINSON  
EATON  
60  
30  
35  
All  
All except:  
VILLAGE OF MULLIKEN  
VILLAGE OF  
SUNFIELD  
TOWNSHIP OF  
SUNFIELD  
All  
EMMET  
70  
Page 17  
GENESEE  
30  
25  
All except:  
CITY OF DAVISON  
CITY OF FENTON  
CITY OF GRAND  
BLANC  
CITY OF LINDEN  
VILLAGE OF GAINES  
VILLAGE OF  
GOODRICH  
TOWNSHIP OF  
ARGENTINE  
TOWNSHIP OF ATLAS  
TOWNSHIP OF  
DAVISON TOWNSHIP OF  
FENTON TOWNSHIP  
OF GRAND  
GLADWIN  
GOGEBIC  
GRAND  
GRATIOT  
HILLSDALE  
40  
60  
60  
35  
20  
25  
All  
All  
All  
All  
All except:  
CITY OF LITCHFIELD  
TOWNSHIP OF  
LITCHFIELD  
TOWNSHIP OF SCIPIO  
HOUGHTON  
80  
70  
All except:  
TOWNSHIP OF ADAMS  
TOWNSHIP OF CHASSELL  
TOWNSHIP OF DUNCAN  
TOWNSHIP OF ELM RIVER  
TOWNSHIP OF LAIRD  
TOWNSHIP OF PORTAGE  
Page 18  
HILLSDALE  
20  
90  
All except:  
VILLAGE OF CALUMET  
VILLAGE OF COPPER  
CITY  
VILLAGE OF  
LINDEN  
VILLAGE OF  
LAURIUM  
TOWNSHIP OF  
CALUMET  
TOWNSHIP OF  
LAKE  
SCHOOLCRAFT  
HURON  
INGHAM  
35  
25  
30  
All  
All except:  
CITY OF EAST LANSING  
CITY OF LANSING  
CITY OF MASON  
TOWNSHIP OF  
ALAIEDON  
TOWNSHIP OF  
AURELIUS  
TOWNSHIP OF DELHI  
TOWNSHIP OF  
LANSING  
TOWNSHIP OF  
MERIDIAN  
TOWNSHIP OF  
WILLIAMSTOWN  
IONIA  
IOSCO  
IRON  
35  
40  
60  
40  
35  
All  
All  
All  
All except:  
ISABELLA  
VILLAGE OF SHEPHERD  
TOWNSHIP OF  
CHIPPEWA  
TOWNSHIP OF COE  
Page 19  
TOWNSHIP OF FREMONT  
TOWNSHIP OF  
LINCOLN  
TOWNSHIP OF  
UNION  
JACKSON  
25  
20  
All except:  
VILLAGE OF BROOKLYN  
TOWNSHIP OF  
COLUMBIA  
TOWNSHIP OF NORVELL  
KALAMAZOO  
30  
35  
All except:  
CITY OF PARCHMENT  
TOWNSHIP OF  
ALAMO  
TOWNSHIP OF  
COOPER  
TOWNSHIP OF  
OSHTEMO  
KALKASKA  
KENT  
60  
35  
40  
All  
All except:  
CITY OF CEDAR SPRINGS  
VILLAGE OF  
CASNOVIA  
VILLAGE OF KENT  
CITY  
VILLAGE OF SAND  
LAKE  
VILLAGE OF SPARTA  
TOWNSHIP OF  
NELSON  
TOWNSHIP OF  
SOLON  
TOWNSHIP OF  
SPARTA  
TOWNSHIP OF  
TYRONE  
KEWEENAW  
90  
All except:  
100  
TOWNSHIP OF EAGLE  
HARBOR  
TOWNSHIP OF GRANT  
TOWNSHIP OF  
HOUGHTON  
LAKE  
60  
All except:  
Page 20  
50  
TOWNSHIP OF CHASE  
TOWNSHIP OF  
CHERRY VALLEY  
TOWNSHIP OF  
ELLSWORTH  
TOWNSHIP OF PINORA  
TOWNSHIP OF  
PLEASANT PLAINS  
TOWNSHIP OF YATES  
LAPEER  
25  
30  
All except:  
VILLAGE OF CLIFFORD  
VILLAGE OF  
COLUMBIAVILLE  
VILLAGE OF NORTH  
BRANCH  
VILLAGE OF OTTER  
LAKE  
TOWNSHIP  
BURLINGTON  
TOWNSHIP  
OF  
OF  
OF  
BURNSIDE  
TOWNSHIP  
DEERFIELD  
TOWNSHIP  
MARATHON  
OF  
TOWNSHIP OF NORTH  
BRANCH  
TOWNSHIP OF OREGON  
TOWNSHIP OF RICH  
Page 21  
LEELANAU  
LENAWEE  
LIVINGSTON  
LUCE  
60  
20  
25  
70  
60  
70  
All  
All  
All  
All  
MACKINAC  
All except:  
TOWNSHIP OF  
NEWTON  
TOWNSHIP OF  
MACOMB  
MANISTEE  
MARQUETTE  
25  
60  
70  
60  
All  
All  
All except:  
TOWNSHIP OF EWING  
TOWNSHIP OF WELLS  
TOWNSHIP OF  
REPUBLIC  
MASON  
60  
40  
60  
35  
40  
All  
All  
All  
All except:  
MECOSTA  
MENOMINEE  
MIDLAND  
CITY OF COLEMAN  
VILLAGE OF SANFORD  
TOWNSHIP OF  
EDENVILLE  
TOWNSHIP OF  
GENEVA  
TOWNSHIP OF HOPE  
TOWNSHIP OF MILLS  
TOWNSHIP OF  
WARREN  
MISSAUKEE  
50  
60  
All except:  
TOWNSHIP OF  
BLOOMFIELD  
TOWNSHIP OF  
CALDWELL  
TOWNSHIP OF PIONEER  
Page 22  
MONROE  
MONTCALM  
20  
35  
40  
All  
All except:  
VILLAGE OF HOWARD CITY  
VILLAGE OF  
LAKEVIEW  
VILLAGE OF PIERSON  
TOWNSHIP OF CATO  
TOWNSHIP OF MAPLE  
VALLEY  
TOWNSHIP OF  
PIERSON  
TOWNSHIP OF  
REYNOLDS  
TOWNSHIP OF WINFIELD  
MONTMORENCY  
MUSKEGON  
50  
40  
50  
All  
All except  
TOWNSHIP OF HOLTON  
TOWNSHIP OF BLUE LAKE  
60  
CITY OF MONTAGUE  
CITY OF MUSKEGON  
CITY OF MUSKEGON  
HEIGHTS CITY OF NORTH  
MUSKEGON CITY OF NORTON  
SHORES CITY OF ROOSEVELT  
PARK CITY OF WHITEHALL  
TOWNSHIP OF DALTON  
TOWNSHIP OF FRUITLAND  
TOWNSHIP OF FRUITPORT  
TOWNSHIP OF LAKETON  
TOWNSHIP OF MONTAGUE  
TOWNSHIP OF MUSKEGON  
TOWNSHIP OF SULLIVAN  
TOWNSHIP OF WHITEHALL  
TOWNSHIP OF WHITE RIVER  
VILLAGE OF FRUITPORT  
VILLABE OF LAKEWOOD  
CLUB  
Page 23  
NEWAYGO  
40  
50  
All except:  
VILLAGE OF HESPERIA  
TOWNSHIP OF BARTON  
TOWNSHIP OF BEAVER  
TOWNSHIP OF DENVER  
TOWNSHIP OF HOME  
TOWNSHIP OF  
LILLEY TOWNSHIP OF  
MERRILL  
TOWNSHIP OF TROY  
OAKLAND  
OCEANA  
25  
60  
50  
All  
All except  
VILLAGE OF HESPERIA  
VILLAGE OF  
WALKERVILLE  
TOWNSHIP OF  
COLFAX  
TOWNSHIP OF  
CRYSTAL  
TOWNSHIP OF  
ELBRIDGE  
TOWNSHIP OF FERRY  
TOWNSHIP OF  
GREENWOOD  
TOWNSHIP OF  
LEAVITT  
TOWNSHIP OF  
NEWFIELD  
TOWNSHIP OF OTTO  
Page 24  
OGEMAW  
40  
50  
All except  
CITY OF ROSE CITY  
TOWNSHIP OF  
CUMMINGS  
TOWNSHIP OF FOSTER  
TOWNSHIP OF  
GOODAR  
TOWNSHIP OF HILL  
TOWNSHIP OF  
KLACKING  
TOWNSHIP OF  
OGEMAW  
TOWNSHIP OF ROSE  
ONTONAGON  
OSCEOLA  
70  
60  
All except:  
TOWNSHIP OF HAIGHT  
TOWNSHIP OF  
INTERIOR  
TOWNSHIP OF  
MCMILLAN  
50  
40  
All except:  
CITY OF EVART  
VILLAGE OF HERSEY  
TOWNSHIP OF EVART  
TOWNSHIP OF HERSEY  
TOWNSHIP OF ORIENT  
TOWNSHIP OF OSCEOLA  
TOWNSHIP OF SYLVAN  
OSCODA  
OTSEGO  
50  
50  
All  
All except:  
60  
VILLAGE OF ELMIRA  
VILLAGE OF  
VANDERBILT  
TOWNSHIP OF  
CORWITH TOWNSHIP OF  
ELMIRA  
TOWNSHIP OF HAYES  
TOWNSHIP OF  
LIVINGSTON  
Page 25  
OTTAWA  
50  
35  
All except:  
TOWNSHIP OF  
GEORGETOWN  
TOWNSHIP OF JAMESTOWN  
TOWNSHIP OF  
TALLMADGE  
TOWNSHIP OF ZEELAND  
40  
CITY OF COOPERSVILLE  
TOWNSHIP OF  
ALLENDALE  
TOWNSHIP OF  
BLENDON  
TOWNSHIP OF  
CHESTER  
TOWNSHIP OF  
POLKTON  
TOWNSHIP OF  
WRIGHT  
PRESQUE ISLE  
ROSCOMMON  
50  
60  
50  
All except  
TOWNSHIP OF BEARINGER  
All except  
40  
TOWNSHIP OF NESTER  
SAGINAW  
35  
All except:  
Page 26  
30  
CITY OF FRANKENMUTH  
VILLAGE OF BIRCH  
RUN VILLAGE OF  
CHESANING VILLAGE OF  
OAKLEY TOWNSHIP OF  
ALBEE TOWNSHIP OF  
BIRCH RUN  
TOWNSHIP OF BRADY  
TOWNSHIP OF  
BRIDGEPORT  
TOWNSHIP OF CHAPIN  
TOWNSHIP OF  
CHESANING  
TOWNSHIP OF  
FRANKENMUTH  
TOWNSHIP OF MAPLE  
GROVE  
TOWNSHIP OF  
ST.CHARLES  
Page 27  
TOWNSHIP OF  
TAYMOUTH  
SANILAC  
30  
25  
All except:  
VILLAGE OF MELVIN  
TOWNSHIP OF  
FREMONT TOWNSHIP OF  
WORTH  
35  
VILLAGE OF MINDEN CITY  
TOWNSHIP OF AUSTIN  
TOWNSHIP OF  
GREENLEAF  
TOWNSHIP OF MINDEN  
SCHOOLCRAFT  
SHIAWASSEE  
70  
30  
25  
All  
All except:  
VILLAGE OF BYRON  
TOWNSHIP OF BURNS  
ST. CLAIR  
ST. JOSEPH  
25  
30  
25  
All  
All except:  
CITY OF STURGIS  
VILLAGE OF BURR  
OAK VILLAGE OF COLON  
VILLAGE OF WHITE  
PIGEON  
TOWNSHIP OF BURR  
OAK  
TOWNSHIP OF COLON  
TOWNSHIP OF FAWN  
RIVER  
TOWNSHIP OF  
SHERMAN TOWNSHIP OF  
STURGIS TOWNSHIP OF  
WHITE PIGEON  
TUSCOLA  
30  
All except:  
Page 28  
35  
VILLAGE OF CARO  
VILLAGE OF CASS  
CITY VILLAGE OF  
FAIRGROVE VILLAGE OF  
GAGETOWN VILLAGE OF  
REESE VILLAGE OF  
UNIONVILLE  
TOWNSHIP OF AKRON  
TOWNSHIP OF ALMER  
TOWNSHIP OF  
COLUMBIA  
TOWNSHIP OF  
ELKLAND TOWNSHIP OF  
ELMWOOD  
TOWNSHIP OF  
FAIRGROVE  
TOWNSHIP OF  
GILFORD  
TOWNSHIP OF WISNER  
VAN BUREN  
50  
30  
All except:  
TOWNSHIP OF PORTER  
35  
CITY OF GOBLES  
VILLAGE OF  
DECATUR VILLAGE OF  
LAWTON VILLAGE OF  
MATTAWAN  
VILLAGE OF PAW  
PAW TOWNSHIP OF  
ALMENA TOWNSHIP OF  
ANTWERP TOWNSHIP OF  
BLOOMINGDALE  
TOWNSHIP OF DECATUR  
TOWNSHIP OF PAW PAW  
TOWNSHIP OF PINE  
GROVE  
TOWNSHIP OF WAVERLY  
Page 29  
WASHTENAW  
25  
20  
All except:  
CITY OF ANN ARBOR  
CITY OF SALINE  
CITY OF YPSILANTI  
VILLAGE OF  
MANCHESTER  
TOWNSHIP OF  
AUGUSTA TOWNSHIP OF  
BRIDGEWATER  
TOWNSHIP OF LODI  
TOWNSHIP OF  
MANCHESTER  
TOWNSHIP OF  
PITTSFIELD  
TOWNSHIP OF SALINE  
TOWNSHIP OF SUPERIOR  
TOWNSHIP OF YORK  
TOWNSHIP OF YPSILANTI  
WAYNE  
20  
25  
All except  
Northville  
All except  
WEXFORD  
60  
50  
TOWNSHIP OF CLAM  
LAKE  
History: 2001 AACS; 2004 AACS; 2010 AACS.  
Page 30  
R 408.30516 Design criteria.  
Rule 516. Table R301.2(1) of the code is amended and figures R301.2(7) and R301.2(8) are added to the code to read as follows:  
TABLE R 301.2(1)  
CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA  
Wi  
nd  
Sp  
eedd  
(m  
ph)  
Seismic  
Design  
Categor  
yf  
Subject to Damage From  
Winter  
Design  
Tempe  
Ice Barrier  
Underlaym  
ent  
Flood  
Hazard  
sg  
Air  
Mean  
Annual  
Tempj  
Ground  
Snow  
Load  
Freezing  
Indexi  
Requiredh  
Weatheri  
Frostli  
Termit  
nga  
ne depthb  
ec  
See  
Table  
R301.2(  
5)  
Sec.R301.2.  
90 2.1 & Figure  
42”  
See  
Note b  
Figure  
R301.2(6)  
See  
Note e  
See  
Note g  
Figure  
R403.3(2)  
See  
footnote J  
Severe  
Yes  
R301.2(  
2)  
For SI: 1 pound per square foot = 0.0479 kN/m2, 1 mile per hour = 1.609 km/h.  
(a) Weathering may require a higher strength concrete or grade of masonry than necessary to satisfy the structural requirements  
of this code. The weathering column shall be filled in with the weathering index (i.e., “negligible”, “moderate,” or “severe”) for  
concrete as determined from the weathering probability map [figure R301.2(3)]. The grade of masonry units shall be determined from  
ASTM C 34, C 55, C 62, C 73, C 90, C 129, C 145, C 216 or C 652 as listed in chapter 44.  
(b) The frost line depth may be modified as provided in section R403.1.4 of the code.  
(c) The jurisdiction shall fill in this part of the table to indicate the need for protection depending on whether there has been a  
history of local damage.  
(d) The jurisdiction shall fill in this part of the table with the wind speed from the basic wind speed map [figure R301.2(4)].  
Wind exposure category shall be determined on a site-specific basis in accordance with section R301.2.1.4 of the code.  
(e) The winter design temperature criteria shall be taken from appendix D of the Michigan plumbing code, R 408.30701 to R  
408.30796.  
(f) Design category determined from section R301.2.2.1 of the code.  
(g) The jurisdiction shall fill in this part of the table with both of the following:  
Page 31  
(i) The date of the jurisdiction’s entry into the national flood insurance program (date of adoption of the first code or ordinance  
for management of flood hazard areas).  
(ii) The date(s) of the currently effective FIRM and FBFM or other flood hazard map adopted by the community, as may be  
amended. Absent (i) or (ii), flood hazard areas as determined by the state under its administration of the Part 31, floodplain regulatory  
authority of the natural resources and environmental protection act, 1994 PA 451, MCL 324.101 to 324.90106, shall become the basis  
for regulation of floodplain development within the community and section R408.7 of the code shall apply to buildings and structures  
within those areas.  
(h) In accordance with sections R905.2.7, R905.4.3.1, R905.5.3.1, R905.6.3.1, R905.7.3.1 and R905.8.3.1 of the code, for areas  
where the average daily temperature in January is 25 degrees Fahrenheit (-4 degrees Celsius) or less, or where there has been a history  
of local damage from the effects of ice damming, the jurisdiction shall fill in this part of the table with “YES”. Otherwise, the  
jurisdiction shall fill in this part of the table with “NO”.  
(i) The jurisdiction shall fill in this part of the table with the 100-year return period air freezing index (bf-days) from figure  
R403.3(2) or from the 100-year (99%) value on the national climatic data center data table “air freezing index-USA method (base 32  
degrees Fahrenheit).  
(j) The jurisdiction shall fill in this part of the table with the mean annual temperature from the national climatic data center data  
table “air freezing index-USA method (base 32 degrees Fahrenheit)” at www.ncdc.noaa.gov/fpsf.html  
History: 2001 AACS; 2008 AACS; 2010 AACS; 2015 AACS.  
Page 32  
R 408.30517 Rescinded.  
History: 2001 AACS; 2004 AACS.  
R 408.30517a Sanitary facilities.  
Rule 517a. Section R306.1 of the code is amended to read as follows:  
R306.1. Sanitary facilities. Every dwelling unit shall be provided with a water  
closet, lavatory, bathtub or shower, and automatic clothes washer connection.  
History: 2010 AACS.  
R 408.30518 Means of egress.  
Rule 518. Sections R311.6.4 and R311.2.1 are added to the code and R311.2 of the  
code is amended to read as follows:  
R311.6.4 Modular ramps. Modular ramp systems approved pursuant to the act are  
not required to comply with the requirements of section R403.1.4 of the code.  
R311.2. Door type and size. The required exit door shall be a side-hinged door not  
less than 3 feet (914 mm) in width and 6 feet, 8 inches (2 032 mm) in height. Other  
exterior hinged or sliding doors shall not be less than 24 inches (6096 mm) in width and 6  
feet, 6 inches (1 981 mm) in height.  
R311.2.1. Interior doors. Interior doors shall be not less than 24 inches (6096 mm) in  
width and 6 feet, 6 inches (1524 mm) in height.  
Exception: Doors to areas less than 10 square feet of floor area.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30519 Treads and risers.  
Rule 519. Sections R311.7.4.1 and R 311.7.4.2 of the code are amended to read as  
follows:  
R311.7.5.1. Riser height. The maximum riser height shall be 8 1/4 inches (210 mm).  
The riser shall be measured vertically between leading edges of the adjacent treads. The  
greatest riser height within any flight of stairs shall not exceed the smallest by more than  
3/8 inch (9.5 mm)  
R311.7.5.2. Tread depth. The minimum tread depth shall be 9 inches (229 mm).  
The tread depth shall be measured horizontally between the vertical planes of the  
foremost projection of adjacent treads and at a right angle to the tread's leading edge.  
The greatest tread depth within any flight of stairs shall not exceed the smallest by more  
than 3/8 inch (9.5 mm). Winder treads shall have a minimum tread depth of 10 inches  
(254 mm) measured as above at a point 12 inches (305 mm) from the side where the  
treads are narrower. Winder treads shall have a minimum tread depth of 6 inches (152  
mm) at any point. Within any flight of stairs, the greatest winder tread depth at the 12-  
inch (305 mm) walk line shall not exceed the smallest by more than 3/8 inch (9.5 mm).  
Page 33  
History: 2001 AACS; 2004 AACS; 2010 AACS.  
Editor's Note: An obvious error in R 408.30519 was corrected at the request of the promulgating  
agency, pursuant to Section 56 of 1969 PA 306, as amended by 2000 PA 262, MCL 24.256. The rule  
containing the error was published in Annual Administrative Code Supplement, 2010. The memorandum  
requesting the correction was published in Michigan Register, 2016 MR 3.  
R 408.30520 Where required in existing dwellings.  
Rule 520. Section R315.3 of the code is amended to read as follows:  
R315.3. Where required in existing dwellings. Where work requiring a building  
permit occurs in existing dwellings that have attached garages or in existing dwellings  
within which fuel-fired appliances exist, carbon monoxide alarms shall be provided in  
accordance with Section R315.1.  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30521 Elevation requirements.  
Rule 521. Section R322.2.1 of the code is amended to read as follows;  
R322.2.1. Elevation requirements. (1) Buildings and structures shall have the  
lowest floor including basements elevated so the lowest point of the floor's concrete or  
subfloor surface is 1 foot (305 mm) or more above the design flood elevation. The  
bottom of the lowest horizontal structural member of the floor system shall not be lower  
than the design flood elevation. Compliance with this elevation requirement shall be  
based upon measurement taken from the floor surface without the final floor covering  
and from the bottom of the lowest horizontal structural member of the floor system.  
(2) Crawl space interior floor grade elevation shall comply with R408.6 of the code.  
(3) Basement floors that are below grade on all sides shall be considered lowest  
floors and shall be elevated so that the lowest point of the floor surface is 1 foot (305  
mm) or more above the design flood elevation.  
Compliance with this elevation requirement shall be based upon measurement taken  
from the floor surface without the final floor covering.  
Exception: Enclosed areas below the design flood elevation, including basements  
that have floors which are not below grade on all sides, shall meet the requirements of  
section R322.2.2 of the code.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2010 AACS.  
R 408.30521a Rooftop mounted photovoltaic panel systems.  
Rule 521a. Sections R909.1, R909.2, and R909.3 of the code are added to read as  
follows:  
R909.1. General. The installation of photovoltaic panel systems that are mounted  
on or above the roof covering shall comply with the provisions of this code, Section  
R324, and NFPA 70.  
Page 34  
R909.2. Structural requirements. Rooftop mounted photovoltaic panel systems  
shall be designed to structurally support the system and withstand gravity loads in  
accordance with chapter 3. The roof upon which these systems are installed shall be  
designed and constructed to support the loads imposed by such systems in accordance  
with chapter 8.  
R909.3. Installation. Rooftop mounted photovoltaic systems shall be installed in  
accordance with the manufacturer’s instructions. Roof penetrations shall be flashed and  
sealed in accordance with this chapter.  
History: 2015 AACS.  
R 408.30522 Minimum depth.  
Rule 522. Section R403.1.4 of the code is amended to read as follows:  
R403.1.4. Minimum depth. All exterior footings and foundation systems shall  
extend 42 inches below actual grade. Where applicable, the depth of the footings shall  
also conform to section R403.1.4.1 of the code.  
Exception:  
Upon evidence of the existence of any of the following conditions, the building  
official may modify the footing depth accordingly:  
(a) Freezing temperatures (freezing degree days).  
(b) Soil type.  
(c) Ground water conditions.  
(d) Snow depth experience.  
(e) Exposure to the elements.  
(f) Other specific conditions identified by the building official that may affect the  
foundation system.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2015 AACS.  
R 408.30522a Vapor retarders.  
Rule 522a. Section R601.3 of the code is amended to read as follows:  
R601.3. Vapor retarders. Class I or II vapor retarders shall be provided on the  
interior side of frame walls in zones 5, 6, 7, 8, and marine 4.  
Exceptions:  
1. As permitted in table R702.7.1.  
2. Class III or no vapor retarder shall be permitted on the interior side of below  
grade wall assemblies. Class I or II vapor retarders shall be permitted on the interior side  
of the wall assembly when no air permeable insulation is installed in the below grade  
wall assemblies.  
3. Construction where moisture or its freezing will not damage the materials.  
History: 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30522b Air freezing index.  
Page 35  
Rule 522b. Table R403.3(2) of the code is amended to read as follows:  
Table R403.3(2)  
Air Freezing Index for Michigan Locations by County  
1500 or  
Berrien  
2000  
All  
2500  
Alger  
3000  
Baraga  
3500  
Gogebic  
4000  
Branch  
Cass  
counties not Charlevoix  
Dickinson  
Iron  
Keweenaw  
Marquette  
Houghton  
Ontonagon  
listed  
Cheboygan  
Chippewa  
Crawford  
Kalamazoo  
Macomb  
Ottawa  
St. Clair  
St. Joseph  
Delta Emmet  
Iosco Kalkaska  
Lake Luce  
Mackinac  
Menominee  
Missaukee  
Montmorency  
Ogemaw  
Osceola  
Otsego  
Roscommon  
Schoolcraft  
Wexford  
History: 2010 AACS.  
R 408.30523 Rescinded.  
History: 2001 AACS; 2004 AACS.  
R 408.30523 Placement of lag screws or bolts in deck ledgers and band joists.  
Rule 523. Figure R507.2.1(1) of the code is amended to read as follows:  
Page 36  
FIGURE R507.2.1(1)  
PLACEMENT OF LAG SCREWS AND BOLTS IN LEDGERS  
History: 2015 AACS.  
R408.30523a Flashing.  
Rule 523a. Section R507.2.4 is added and figure R507.2.1(2) is amended to read as  
follows:  
R507.2.4. Flashing. An approved corrosion resistant flashing as required by Section  
R703.8 shall be installed above the attached ledger as shown in figure R507.2.1(2) or as  
approved.  
Page 37  
History: 2015 AACS.  
R 408.30524 Michigan uniform energy code.  
Rule 524. Buildings shall be designed and constructed in accordance with the  
Michigan uniform energy code part 10 rules, R 408.31001 to R 408.31099.  
History: 2001 AACS; 2004 AACS.  
R 408.30525 Scope.  
Rule 525. Section M1301.1 of the code is amended to read as follows:  
M1301.1. Scope. The provisions of this chapter shall govern the installation of  
mechanical systems not specifically covered in other chapters applicable to mechanical  
systems. Installations of mechanical appliances, equipment, and systems not addressed  
by the code shall comply with the applicable provisions of the Michigan mechanical  
code, R 408.30901 to R 408.30998 and the international fuel gas code.  
History: 2001 AACS; 2008 AACS.  
R 408.30525a Simplified wall bracing.  
Rule 525a. Section R 602.10.9 is amended to read as follows:  
R602.10.9. Braced wall panel support. Braced wall panel support shall be provided  
as follows:  
1. Cantilevered floor joists complying with section R502.3.3 shall be permitted to  
support braced wall panels.  
2. Raised floor system post or pier foundations supporting braced wall panels shall  
be designed in accordance with accepted engineering practice.  
3. Masonry stem walls with a length of 48 inches (1 219 mm) or less supporting  
braced wall panels shall be reinforced in accordance with figure R602.10.9. Masonry  
stem walls with a length greater than 48 inches (1 219 mm) supporting braced wall panels  
shall be constructed in accordance with section R403.1. Methods ABW and PFH shall  
not be permitted to attach to masonry stem walls.  
4. Concrete stem walls with a length of 48 inches (1 219 mm) or less, greater than  
12 inches (305 mm) tall shall have reinforcement sized and located in accordance with  
figure R602.10.9.  
History: 2015 AACS.  
R 408.30526 Rescinded.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2015 AACS.  
Page 38  
R 408.30527 Standards.  
Rule 527. Section M2001.1.1 of the code is amended to read as follows:  
M2001.1.1. Standards. Oil-fired boilers and their control systems shall be listed  
and labeled in accordance with UL 726. Electric boilers and their control systems shall  
be listed in accordance with UL 834. Solid-fuel-fired boilers shall be listed and labeled  
in accordance with UL 2523. Boilers shall be designed, constructed, installed, and  
maintained in accordance with the requirements of ASME CSD-1 and ASME boiler and  
pressure vessel code, Sections I and IV, except part CE-110(a) of the CSD-1. Gas-fired  
boilers shall conform to the requirements listed in chapter 24. It shall be the  
homeowner’s responsibility to maintain and operate the boiler in accordance with ASME  
CSD-1.  
History: 2001 AACS; 2010 AACS; 2015 AACS.  
R 408.30528 Terms defined in other codes.  
Rule 528. Section G2402.3 of the code is amended to read as follows:  
G2402.3. Terms defined in other codes. Where terms are not defined in the code  
and are defined in the Michigan electrical code, R 408.30801 to R 408.30880, Michigan  
building code, R 408.30401 to R 408.30547, international fire code and international fuel  
gas code listed in chapter 44, Michigan mechanical code, R 408.30901 to R 408.30998 or  
Michigan plumbing code, R 408.30701 to R 408.30796, the terms shall have the  
meanings ascribed to them as in those codes.  
History: 2001 AACS; 2008 AACS; 2010 AACS.  
R 408.30528a CSST.  
Rule 528a. Section G2411.1.1 (310.1.1) of the code is amended to read as follows:  
G2411.1.1. CSST. Corrugated stainless steel tubing (CSST) gas piping systems  
shall be bonded to the electrical service grounding electrode system or where provided,  
lightening protection electrode system. The bonding jumper shall connect to a metallic  
pipe, pipe fitting, or CSST fitting between the point of delivery and the CSST utilizing a  
device listed for the application. The bonding jumper shall be not smaller than 6 AWG  
copper wire or equivalent, not longer than 75 feet and accessible. Gas piping systems  
that are bonded in accordance with this section shall be considered effectively bonded  
regardless of the amount of CSST in the system. Any additional grounding electrodes  
used shall be bonded to the electrical service grounding electrode system, or where  
provided, the lighting protection grounding electrode system.  
Exception: CSST piping systems tested and listed by the manufacturer for  
installation without additional bonding when installed in accordance with the listing.  
History: 2010 AACS; 2015 AACS.  
R 408.30529 Lining required.  
Rule 529. Section P2709.2 of the code is amended to read as follows:  
Page 39  
P2709.2. Lining required. The adjoining walls and floor framing enclosing on-site  
built-up shower receptors shall be lined with 1 of the following:  
1. Sheet lead.  
2. Sheet copper.  
3. Plastic liner material that complies with ASTM D 4068 or ASTM D 4551.  
4. Sheet-applied load-bearing, bonded waterproof membranes that comply with  
ANSI A118.10.  
The lining material shall extend not less than 3 inches (76 mm) beyond or around  
the rough jambs and not less than 3 inches (76 mm) above finished thresholds. Sheet-  
applied load bearing, bonded waterproof membranes shall be applied in accordance with  
the manufacturer’s instructions.  
History: 2001 AACS; 2008 AACS; 2015 AACS.  
R 408.30530 Requirements for discharge pipe.  
Rule 530. Section P2803.6.1 of the code is amended to read as follows:  
P2803.6.1. Requirements for discharge pipe. Relief valves shall not discharge so as  
to be a hazard, a potential cause of damage, or a nuisance.  
A relief valve discharge pipe shall be provided for each individual relief valve and  
shall meet all of the following:  
(a) Shall terminate atmospherically not more than 4 inches (102 mm) from the floor  
with an unthreaded end.  
(b) Shall not be interconnected.  
(c) Valves shall not be connected in the relief valve discharge pipe.  
(d) Shall be rigid pipe approved for water distribution, with a minimum temperature  
rating of 210 degrees Fahrenheit.  
(e) Shall have the same nominal inside diameter as the relief valve outlet and shall  
drain by gravity flow.  
(f) Shall discharge to the floor, or to the pan serving the water heater or storage  
tank, or to a waste receptor.  
The outlet of a pressure, temperature, or other relief valve shall not be directly  
connected to the drainage system.  
History: 2001 AACS; 2008 AACS; 2010 AACS.  
R 408.30531 Rescinded.  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2015 AACS.  
R 408.30532 Roof extension.  
Rule 532. Section P3103.1 of the code is amended to read as follows:  
P3103.1. Roof extension. All open vent pipes that extend through a roof shall  
terminate at least 1 foot (305 mm) above the roof, except that if a roof is to be used for  
Page 40  
any purpose other than weather protection, then the vent extension shall be run not less  
than 7 feet (2134 mm) above the roof.  
History: 2001 AACS.  
R 408.30533 Frost closure.  
Rule 533. Section P3103.2 of the code is amended to read as follows:  
P3103.2. Frost closure. To prevent frost closure, every vent extension through a  
roof shall be not less than 3 inches (76 mm) in diameter. Any increase in the size of the  
vent shall be made inside the building with a minimum of 1 foot (305 mm) below the  
roof or inside the wall.  
History: 2001 AACS.  
R 408.30533a Rough plumbing.  
Rule 533a. Section P2503.5.1 of the code is amended to read as follows:  
P2503.5.1. Rough plumbing. DWV systems shall be tested on completion of the  
rough piping installation by water or air with no evidence of leakage. Either test shall be  
applied to the drainage system in its entirety or in sections after rough piping has been  
installed, as follows:  
1. Water test. Each section shall be filled with water to a point not less than 10 feet  
(3 048 mm) above the highest fitting connection in that section, or to the highest point in  
the completed system. Water shall be held in the section under test for a period of 15  
minutes. The system shall prove leak free by visual inspection.  
2. Air test. The portion under test shall be maintained at a gauge pressure of 5  
pounds per square inch (psi) (34 kPa) or 10 inches (254 mm) of mercury column (34  
kPa). This pressure shall be held without introduction of additional air for a period of 15  
minutes.  
History: 2015 AACS.  
R 408.30533b Sewer depth.  
Rule 533b. Section P2603.5.1 of the code is amended to read as follows:  
P2603.5.1. Sewer depth. A building sewer that connects to a private disposal system  
shall be a minimum of 8 inches (203 mm) to the top of the pipe below finished grade at  
the point of septic tank connection. Building sewers shall be installed a minimum of 42  
inches (1 067 mm) below grade.  
Exception: When permitted by the code official.  
History: 2015 AACS.  
Page 41  
R 408.30534 Venting.  
Rule 534. Section P3105.1 is amended and section 3105.4 and figure P3105.4 are  
added to the code and figure N3 in appendix N of the code is amended to read as follows:  
P3105.1. Distance of trap from vent. Each fixture trap shall have a protecting vent  
located so that the slope and the developed length in the fixture drain from the trap weir  
to the vent fitting are within the requirements in table P3105.1 of the code.  
P3105.4. Vertical leg for waste fixture drains. A vertical leg (see figure P3105.4) is  
permitted within a fixture drain of a waste fixture in accordance with the following  
criteria:  
(1) Minimum trap diameter shall be in accordance with table P3201.7 of the code.  
(2) The diameter of section A shall be equal to the diameter of the trap.  
(3) The length of section A shall not be less than 8 inches (2032 mm) and in  
accordance with table P3105.1 of the code.  
(4) The diameter of section B shall be 1 pipe size larger than the diameter of  
Section A.  
(5) The length of section B shall not be more than 36 inches (9144 mm).  
(6) The diameter of section C shall be 1 pipe size larger than the diameter of section  
B.  
(7) The total length of section A and section C shall not exceed the distance allowed  
in table P3105.1 of the code.  
(8) Bends shall be the diameter of the largest connected section.  
Page 42  
History: 2001 AACS; 2004 AACS.; 2008 AACS; 2010 AACS.  
R 408.30535 Connection.  
Rule 535. Section P3111.2.2 of the code is amended to read as follows:  
Page 43  
P3111.2.2. Connection. The combination waste and vent systems shall be provided  
with a dry vent connected to a point within the system or the system shall connect to a  
horizontal drain that is vented in accordance with one of the methods specified in this  
chapter. Combination waste and vent systems connecting to building drains receiving  
only the discharge from a stack or stacks shall be provided with a dry vent. The vent  
connecting the combination waste and vent pipe shall extend vertically not less than 6  
inches (152 mm) above the flood level rim of the highest fixture being vented before  
offsetting horizontally.  
History: 2001 AACS.  
R 408.30536 Electrical; general; electrical conductors; connections and electrical  
grounding.  
Rule 536. Sections E3401.1, E3401.2, E3401.3, E3705.4.1, E3908.8.1, and  
E3908.8.2 of the code are amended and E3401.5, E3401.6, E3401.6.1, E3401.6.2,  
E3401.6.3, E3401.7, and E3401.8 are added to read as follows:  
E3401.1. Applicability. The provisions of chapters 34 to 43 of the code shall  
establish the general scope of the electrical system and equipment requirements of the  
code. Chapters 34 to 43 of the code cover those wiring methods and materials most  
commonly encountered in the construction of 1- and 2-family dwellings and structures  
regulated by the code. Other wiring methods, materials, and subject matter covered in  
the Michigan electrical code, R 408.30801 to R 408.30880 are also allowed by the code.  
E3401.2. Scope. Chapters 34 to 43 of the code shall cover the installation of  
electrical systems, equipment, and components indoors and outdoors that are within the  
scope of the code, including services, power distribution systems, fixtures, appliances,  
devices, and appurtenances. Services within the scope of the code shall be limited to  
120/240 volt, 0- to 400- ampere, single-phase systems. These chapters specifically cover  
the equipment, fixtures, appliances, wiring methods, and materials that are most  
commonly used in the construction or alteration of 1- and 2-family dwellings and  
accessory structures regulated by the code. The omission from these chapters of any  
material or method of construction provided by the Michigan electrical code, R  
408.30801 to R 408.30880, shall not be construed as prohibiting the use of such material  
or method of construction. Electrical systems, equipment, or components not specifically  
covered in these chapters shall comply with the applicable provisions of the Michigan  
electrical code, R 408.30801 to R 408.30880.  
E3401.3. Not covered. Chapters 34 to 43 do not cover the following:  
(1) Installations under the exclusive control of communications utilities and electric  
utilities.  
(2) Services over 400 amperes.  
E3401.5. General. This section provides for the design, construction, installation,  
alteration, and repair of photovoltaic equipment and systems. [690.1]  
E3401.6. Requirements. The installation, inspection, maintenance, repair, and  
replacement of photovoltaic systems and all system components shall comply with the  
manufacturer’s instructions, Sections E3401.6.1 through E3401.6.3 and NFPA 70.  
[690.3]  
Page 44  
E3401.6.1. Roof-mounted panels and modules. Where photovoltaic panels and  
modules are installed on roofs, the roof shall be constructed to support the loads imposed  
by such modules. Roof-mounted photovoltaic panels and modules that serve as roof  
covering shall conform to the requirements for roof coverings in chapter 9. Where  
mounted on or above the roof coverings, the photovoltaic panels and modules and  
supporting structure shall be constructed of noncombustible materials or fire-retardant  
treated wood equivalent to that required for the roof construction.  
E3401.6.2. Roof and wall penetrations. Roof and wall penetrations shall be flashed  
and sealed in accordance with chapter 9 to prevent entry of water, rodents, and insects.  
E3401.6.3. Ground-mounted panels and modules. Ground-mounted panels and  
modules shall be installed in accordance with the manufacturer’s instructions. [110.3(B)]  
E3401.7. Photovoltaic panels and modules. Photovoltaic panels and modules shall  
be listed and labeled in accordance with UL 1703. [690.4(B)]  
E3401.8. Inverters. Inverters shall be listed and labeled in accordance with UL  
1741. Systems connected to the utility grid shall use inverters listed for utility interaction.  
[690.4(B)]  
E3705.4.1. Conductors rated 60C. Except where the equipment is marked  
otherwise, termination provisions of equipment for circuits rated 100 amperes or less, or  
marked for 14 AWG through 1 AWG conductors, shall be used only for 1 of the  
following:  
1. Conductors rated 60C (140F).  
2. Conductors with higher temperature ratings, provided that the ampacity of such  
conductors is determined based on the 60C (140F) ampacity of the conductor size used.  
3. Conductors with higher temperature ratings where the equipment is listed and  
identified for use with such conductors. [110.14(C)(1)(a)]  
E3908.8.1. Grounding of flexible metal conduit. Flexible metal conduit shall not be  
permitted as an equipment grounding conductor. [Michigan Electrical Code Rules Part 8  
250.118 amended]  
E3908.8.2. Grounding of liquid-tight flexible metal conduit. Liquid-tight flexible  
metal conduit shall not be permitted as an equipment grounding conductor. [Michigan  
Electrical Code Rules Part 8 250.118 amended]  
History: 2001 AACS; 2004 AACS; 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30536a General requirements.  
Rule 536a. Sections E3402.2, E3405.2 and E3407.5 are amended to read as follows:  
E3402.2. Penetrations of fire-resistance-rated assemblies. Electrical installations in  
hollow spaces, vertical shafts, and ventilation or air-handling ducts shall be made so that  
the possible spread of fire or products of combustion will not be substantially increased.  
Electrical penetrations through fire-resistance-rated walls, partitions, floors, or ceilings  
shall be protected by approved methods to maintain the fire-resistance-rating of the  
element penetrated. Penetrations of fire-resistance-rated walls shall be limited as  
specified in Section R302.4.  
E3405.2. Working clearances for energized equipment and panelboards. Except as  
otherwise specified in chapters 34 through 43, the dimension of the working space in the  
direction of access to panelboards and live parts likely to require examination,  
Page 45  
adjustment, servicing, or maintenance while energized shall be not less than 36 inches  
(914 mm) in depth. Distances shall be measured from the energized parts where such  
parts are exposed or from the enclosure front or opening where such parts are enclosed.  
In addition to the 36-inch dimension (914 mm), the work space shall not be less than 30  
inches (762 mm) wide in front of the electrical equipment and not less than the width of  
such equipment. The work space shall be clear and shall extend from the floor or  
platform to a height of 6.5 feet (1 981 mm) or the height of the equipment, whichever is  
greater. In all cases, the work space shall allow at least a 90-degree (1.57 rad) opening of  
equipment doors or hinged panels. Equipment associated with the electrical installation  
located above or below the electrical equipment shall be permitted to extend not more  
than 6 inches (152 mm) beyond the front of the electrical equipment. [110.26(A)]  
Exception:  
1. In existing dwelling units, service equipment, and panelboards that are not rated  
in excess of 200 amperes may be in spaces where the height of the working space is less  
than 6.5 feet (1 981 mm), but greater than 5 feet (1 524 mm). [110.26(A)(3) Exception 1  
amended]  
2. Meters that are installed in meter sockets may extend beyond the other equipment.  
Meter sockets shall not be exempt from the requirements of this section. [110.26(A)(3)  
Exception 2]  
E3407.5. Polarity of connections. No grounded conductor shall be attached to any  
terminal or lead so as to reverse the designated polarity.  
History: 2010 AACS; 2015 AACS.  
R 408.30537 Separate outdoor electric space conditioning equipment.  
Rule 537. Section E3601.6.3, E3601.6.4, and E3608.1.2.1 are added to the code and  
Sections E3604.2.1, and E3609.7.1 are amended to read as follows:  
E3601.6.3. Separate outdoor electric space conditioning equipment. A service  
disconnect for separately metered outdoor electric space conditioning equipment shall be  
grouped with the service disconnecting means for the structure or immediately adjacent  
to the outdoor meter cabinet. A permanent plaque or directory shall be installed at each  
service disconnect location denoting the other services, feeders, and branch circuits  
supplying a building or structure and area served by each service, feeder, and branch  
circuit. Grounding shall be in accordance with Sections E3607 and E3608.  
E3601.6.4. Electric vehicle charging system service disconnect. A service  
disconnect for electric vehicle charging systems shall be grouped with the service  
disconnecting means for the structure or immediately adjacent to the outdoor meter  
cabinet. A permanent plaque or directory shall be installed at each service disconnect  
location identifying the other services, feeders, and branch circuits supplying a building  
or structure and area served by each service, feeder, and branch circuit. Grounding shall  
be in accordance with Section E3607 and E3608.  
E3604.2.1. Above roofs. Conductors shall have a vertical clearance of not less than  
8 feet (2438 mm) above the roof surface. The vertical clearance above the roof level  
shall be maintained for a distance of not less than 3 feet (914 mm) in all directions from  
the edge of the roof. See figure E3604.2.1. [230.24(A)]  
Exceptions:  
Page 46  
1. Conductors above a roof surface subject to pedestrian traffic shall have a vertical  
clearance from the roof surface in accordance with Section E3604.2.2. [230.24(A)  
Exception 1]  
2. Where the roof has a slope of 4 inches (102 mm) in 12 inches (305 mm) or  
greater and is not accessible from an operable window, the minimum clearance shall be 3  
feet (914 mm). [230.24(A) Exception 2 amended]  
3. The minimum clearance above only the overhanging portion of the roof shall not  
be less than 18 inches (457 mm) where not more than 6 feet (1 829 mm) of conductor  
length passes over 4 feet (1 219 mm) or less of roof surface measured horizontally and  
such conductors are terminated at a through-the-roof raceway or approved support.  
[230.24(A) Exception 3]  
4. The requirement for maintaining the vertical clearance for a distance of 3 feet  
(914 mm) from the edge of the roof shall not apply to the final conductor span where the  
service drop is attached to the side of a building. [230.24(A) Exception 4]  
5. Where the voltage between conductors does not exceed 300 and the roof area is  
guarded or isolated, a reduction in clearance to 3 feet (914 mm) shall be permitted.  
[230.24(A) Exception 5]  
E3608.1.2.1. Verification of the installation of the concrete encased electrode  
specified for in E3608.1.2. The inspection of a concrete incased electrode meeting the  
requirements of E3608.1.2 except for the connection of the grounding electrode  
conductor to the electrode shall be completed by 1 of the following:  
1. The electrical inspector for the enforcing agency.  
2. The building inspector for the enforcing agency if all of the following conditions  
are met:  
a. Both the electrical and building inspectors for the enforcing agency(s) shall sign a  
written agreement which shall remain on file with the enforcing agency that designates  
authority to the building inspector for that agency to inspect a concrete encased electrode.  
b. Upon inspection and verification by the building inspector of a concrete encased  
electrode, the building inspector shall provide written documentation to the electrical  
inspector that the installation of the concrete encased electrode meets the requirements set  
forth in E3608.1.2. Electrode shall be ½” diameter (13mm) reinforcing bar or larger, a  
minimum of 20 feet (6 096 mm) long including usual tie wire connections, and encased  
in 2 inches (51 mm) of concrete except for the end of the electrode which shall be in an  
accessible location and not subject to deteriorating conditions (i.e. backfill).  
c. Verification of approval of the concrete encased electrode shall be made at the  
construction site by signature of the field copy of the building permit noting that the  
concrete encased electrode was approved along with the footing inspection or by a  
readily available inspection tag attached to the accessible grounding electrode reinforcing  
bar.  
d. The grounding electrode conductor connection to the concrete encased electrode  
shall be inspected by the electrical inspector for the enforcing agency.  
E3609.7.1. Corrugated stainless steel tubing (CSST). Corrugated stainless steel  
tubing gas piping systems shall be bonded to the electrical service grounding electrode  
system or where provided, lightening protection electrode system. The bonding jumper  
shall connect to a metallic pipe, pipe fitting, or CSST fitting between the point of delivery  
and the CSST utilizing a device listed for the application. The bonding jumper shall be  
Page 47  
not smaller than 6 AWG copper wire or equivalent, not longer than 75 feet and  
accessible. Gas piping systems that are bonded in accordance with this section shall be  
considered effectively bonded regardless of the amount of CSST in the system. Any  
additional grounding electrodes used shall be bonded to the electrical service grounding  
electrode system, or where provided, the lighting protection grounding electrode system.  
Exception: CSST piping systems tested and listed by the manufacturer for  
installation without additional bonding when installed in accordance with the listing.  
History: 2001 AACS; 2004 AACS; 2010 AACS; 2015 AACS.  
R 408.30537a Wiring methods.  
Rule 537a. Section E3803.6 and tables E3801.4, and E3802.1 are amended to read  
as follows:  
E3803.6. Raceway seals. Conduits or raceways shall be sealed or plugged at either  
or both ends where moisture will enter and contact live parts. Sealants shall be identified  
for use with the cable insulation, shield, or other components.  
Page 48  
Table E3801.4  
ALLOWABLE APPLICATIONS FOR WIRING METHODSa, b, c, d, e, f, g, h, i, j, k, l  
IM  
ALLOWABLE APPLICATIONS  
(application allowed where marked with an “A”)  
A
E
MT  
E
NT  
F
MC  
C
RM  
LFCa  
M
N
S
SE  
U
U
C
C
M
R
F
SEl  
C
PV  
C
Services  
A
A
A
A
Ai  
A
A
A
Ai  
A
A
A
A
A
A
h
Feeders  
A
A
Ab  
A
b
e
Branch circuits  
Inside a building  
Wet locations exposed to sunlight  
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Ac  
A
A
A
A
A
A
h
e
Damp locations  
A
A
A
A
A
A
A
A
A
d
Embedded in noncinder concrete in dry location  
In noncinder concrete in contact with grade  
A
A
A
A
A
Aj  
Aj  
Af  
f
f
Embedded in plaster not exposed to dampness  
Embedded in masonry  
In masonry voids and cells exposed to dampness or  
A
A
A
A
A
A
A
A
A
A
Af  
Af  
A
A
A
A
A
A
A
A
A
A
d
below grade line  
Fished in masonry voids  
In masonry voids and cells not exposed to dampness  
Run exposed  
Run exposed and subject to physical damage  
For direct burial  
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
Ag  
Af  
A
A
A
A
f
f
For SI: 1 foot = 304.8 mm.  
a. Liquid-tight flexible nonmetallic conduit without integral reinforcement within the conduit wall shall not exceed 6 feet in length.  
b. Type USE cable shall not be used inside buildings.  
c. The grounded conductor shall be insulated.  
d. Conductors shall be a type approved for wet locations and the installation shall prevent water from entering other raceways.  
Page 49  
e. Shall be listed as “sunlight resistant.”  
f. Metal raceways shall be protected from corrosion and approved for the application. Aluminum RMC requires approved supplementary corrosion protection.  
g. RNC shall be Schedule 80.  
h. Shall be listed as “sunlight resistant” where exposed to the direct rays of the sun.  
i. Conduit shall not exceed 6 feet in length.  
j. Liquid-tight flexible nonmetallic conduit may be encased in concrete where listed for direct burial and only straight connectors listed for use with LFNC are used.  
k. In wet locations under any of the following conditions.  
(i) The metallic covering is impervious to moisture.  
(ii) A lead sheath or moisture-impervious jacket is provided under the metal covering.  
(iii) The insulated conductors under the metallic covering are listed for use in wet locations and a corrosion-resistant jackets is provided over the metallic sheath.  
l. Type USE cable not permitted above ground except to terminate at the exterior of a building in an approved enclosure and protected in accordance with Section  
E3803.3.  
TABLE E3802.1  
GENERAL INSTALLATION AND SUPPORT REQUIREMENTS FOR WIRING METHODSa, b, c, d, e, f, g, h, i, j, k  
INSTALLATION REQUIREMENTS  
EM  
(Requirement applicable only to wiring methods marked “A”)  
A
T
IM  
C
RM  
FM  
C
LF  
C
N
U
C
C
E
NT  
M
F
P
S
S
M
VC  
E
Ra  
C
Where run parallel with the framing member or furring strip, the wiring  
shall be not less than 1 ¼ inches from the edge of a furring strip or a framing  
member such as a joist, rafter, or stud or shall be physically protected.  
Bored holes in framing members for wiring shall be located not less than 1  
¼ inches from the edge of the framing member or shall be protected with a  
minimum 0.0625-inch steel plate or sleeve, a listed steel plate, or other  
physical protection.  
A
A
A
A
A
A
A
A
A
Ak  
k
k
k
k
Where installed in grooves, to be covered by wallboard, siding, paneling,  
carpeting, or similar finish, wiring methods shall be protected by 0.0625-inch-  
thick steel plate, sleeve, or equivalent, a listed steel plate or by not less than 1  
¼-inch free space for the full length of the groove in which the cable or  
raceway is installed.  
A
A
A
A
A
A
Securely fastened bushings or grommets shall be provided to protect  
wiring run through openings in metal framing members.  
A
A
A
A
j
j
j
The maximum number of 90-degree bends shall not exceed 4 between  
junction boxes.  
A
A
A
Page 50  
Bushings shall be provided where entering a box, fitting, or enclosure  
unless the box or fitting is designed to afford equivalent protection.  
Ends of raceways shall be reamed to remove rough edges.  
A
4
A
A
A
A
3
A
A
4
A
A
3
2
A
A
Maximum allowable on center support spacing for the wiring method in  
feet.  
10l  
4.5b  
b
d, l  
.5b,c  
.5i  
.5e  
2
Maximum support distance in inches from box or other terminations.  
1
36  
3
12b,  
1
3
1
2b, f  
6
2h, i  
6
g
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.  
a. Installed in accordance with listing requirements.  
b. Supports not required in accessible ceiling spaces between light fixtures where lengths do not exceed 6 feet.  
c. Six feet for MC cable.  
d. Five feet for trade sizes greater than 1 inch.  
e. Two and one-half feet where used for service or outdoor feeder and 4.5 feet where used for branch circuit or indoor feeder.  
f. Twenty-four inches for Type AC cable and 36 inches for interlocking Type MC cable where flexibility is necessary.  
g. Where flexibility after installation is necessary, lengths of flexible metal conduit and liquidtight flexible metal conduit measured from the last point where  
the raceway is securely fastened shall not exceed: 36 inches for trade sizes ½ through 1 ¼, 48 inches for trade sizes 1 ½ through 2 and 5 feet for trade sizes 2 ½  
and larger.  
h. Within 8 inches (203 mm) of boxes without cable clamps.  
i. Flat cables shall not be stapled on edge.  
j. Bushings and grommets shall remain in place and shall be listed for the purpose of cable protection.  
k. See Section R502.8 and R802.7 for additional limitations on the location of bored holes in horizontal framing members.  
l. Raceways may be unsupported where the raceway is not more than 900 millimeters (36 inches) long and remains in unbroken lengths (without coupling).  
Such raceways shall terminate in an outlet box, junction box, device box, cabinet, or other termination at each end of the raceway.  
History: 2010 AACS; 2015 AACS.  
Page 51  
R 408.30537b Power and lighting distribution.  
Rule 537b. Sections E3901.11, E3905.3.2, E3908.9, and E3908.10, are amended and  
E3908.9.1, E3908.9.1.1 and E3908.9.1.2 are added to read as follows:  
E3901.11. Foyers. Foyers that are not part of a hallway in accordance with Section  
E3901.10 and that have an area that is greater than 100 feet2 (9.2903 m2) shall have a  
receptacle(s) located in each wall space that is 3 feet (914 mm) or more in width.  
Doorways, door-side windows that extend to the floor and similar openings shall not be  
considered as wall space. [210.52(I) amended]  
E3905.3.2. Securing to box. All permitted wiring methods shall be secured to the  
boxes.  
Exception: Where nonmetallic-sheathed cable is used with boxes not larger than a  
nominal size of 2 ¼ inches by 4 inches (57 mm by 102 mm) mounted in walls or ceilings,  
and where the cable is fastened within 8 inches (2 032 mm) of the box measured along the  
sheath, and where the sheath extends through a cable knockout not less than ¼ inch (6.4  
mm), securing the cable to the box shall not be required. Multiple cable entries shall be  
permitted in a single cable knockout opening. [314.17(c) Exception amended]  
E3908.9. Equipment fastened in place or connected by permanent wiring methods.  
Noncurrent-carrying metal parts of equipment, raceways, and other enclosures, where  
required to be grounded, shall be grounded by 1 of the following methods: [250.134]  
(a) By any of the equipment grounding conductors permitted by Sections E3908.8 and  
E3908.8.3. [250.134(A)]  
(b) By an equipment grounding conductor contained within the same raceway, cable,  
or cord, or otherwise run with the circuit conductors. Equipment grounding conductors  
shall be identified in accordance with Section E3407.2. [250.134(B) Exception]  
E3908.9.1. Cord-and-plug-connected equipment. Non-current-carrying metal parts of  
the cord-and-plug-connected equipment, if grounded, shall be connected to an equipment  
grounding conductor by 1 of the methods in E3908.9.1.1 and E3908.9.1.2. [250.138]  
E3908.9.1.1. By means of an equipment grounding conductor. By means of an  
equipment grounding conductor run with the power supply conductors in a cable assembly  
or flexible cord properly terminated in a grounding-type attachment plug with 1 fixed  
grounding contact. [250.138(A)]  
Exception: The grounding contacting pole of grounding-type plug-in ground-fault  
circuit interrupters may be of the movable, self-restoring type on circuits operating at not  
over 150 volts between any 2 conductors or over 150 volts between any conductor and  
ground. [250.138(A) Exception]  
E3908.9.1.2. By means of a separate flexible wire or strap. By means of a separate  
flexible wire or strap, insulated or bare, connected to an equipment grounding conductor,  
and protected as well as practicable against physical damage, where part of the equipment.  
[250.138(B)]  
E3908.10. Methods of equipment grounding. Fixtures and equipment shall be  
considered grounded where mechanically connected to an equipment grounding conductor  
as specified in Sections E3908.8 and E3908.8.3. Wire type equipment grounding  
conductors shall be sized in accordance with Section E3908.12.  
History: 2010 AACS; 2015 AACS.  
R 408.30537c Devices and luminaires.  
Rule 537c. Sections E4002.2, and E4002.16, are amended to read as follows:  
E4002.2. Grounding type. Receptacles installed on 15- and 20-ampere-rated branch  
circuits shall be of the grounding type and connected to an equipment grounding conductor.  
Exception: Replacement receptacles as permitted by Section E4002.16.  
E4002.16. Replacements. Replacement of receptacles shall comply with the  
following as applicable. [406.4(D) amended]  
(1) Grounding-type receptacles. Where a grounding means exists in the receptacle  
enclosure or an equipment grounding conductor is installed grounding type receptacles  
shall be used and shall be connected to the equipment grounding conductor. [406.4(D)(1)  
amended]  
(2) Non-grounding-type receptacles. Where attachment to an equipment grounding  
conductor does not exist in the receptacle enclosure, the installation shall comply with 1 of  
the following: [406.4(D)(2) amended]  
(a) A non-grounding-type receptacle may be replaced with another non-grounding-  
type receptacle. [406.4(D)(2)(a)]  
(b) A non-grounding-type receptacle may be replaced with a ground-fault circuit  
interrupter-type of receptacle. These receptacles shall be marked “no equipment ground.”  
An equipment grounding conductor shall not be connected from the ground-fault circuit-  
interrupter-type receptacle to any outlet supplied from the ground-fault circuit-interrupter  
receptacle. [406.4(D)(2)(b)]  
(c) A non-grounding type receptacle may be replaced with a grounding-type  
receptacle where supplied through a ground-fault circuit interrupter. Grounding-type  
receptacles supplied through the ground-fault circuit interrupter shall be marked “GFCI  
protected” and “no equipment ground.” An equipment grounding conductor shall not be  
connected between the grounding-type receptacles. [406.4(D)(2)(c)]  
(3) Ground-fault circuit interrupters. Ground-fault circuit-interrupter protected  
receptacles shall be provided where replacements are made at receptacle outlets that are  
required to be so protected elsewhere in this code. [406.4(D)(3)]  
Exception: Where replacement of the receptacle type is impracticable, such as where  
the outlet box size will not permit the installation of the GFCI receptacle, the receptacle  
may be replaced with a new receptacle of the existing type, where GFCI protection is  
provided and the receptacle is marked “GFCI protected” and “no equipment ground” in  
accordance with E4002.16 (2)(a), (b),or (c). [406.4(D)(3) Exception]  
History: 2010 AACS; 2015 AACS.  
R 408.30537d Frames of ranges and clothes dryers.  
Rule 537d. Section E4101.8 of the code is added to read as follows:  
E4101.8. Frames of ranges and clothes dryers. Frames of electric ranges, wall-  
mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or junction boxes  
that are part of the circuit for these appliances shall be connected to the equipment  
grounding conductor in the manner specified in E3908.9. [250.140 amended]  
Page 53  
Exception: For existing branch-circuit installations only where an equipment  
grounding conductor is not present in the outlet or junction box, the frames of electric  
ranges, wall-mounted ovens, counter-mounted cooking units, clothes dryers, and outlet or  
junction boxes that are part of the circuit for these appliances may be connected to the  
grounded circuit conductor if all of the following conditions are met: [250.140 Exception]  
1. The supply circuit is 120/240-volt single-phase, 3-wire connected system. [250.140  
Exception (1)]  
2. The grounded conductor is not smaller than 10 AWG copper or 8 AWG aluminum.  
[250.140 Exception (2)]  
3. The grounded conductor is insulated, or the grounded conductor is uninsulated and  
part of a type SE service-entrance cable and the branch circuit originates at the service  
equipment. [250.140 Exception (3)]  
4. Grounding contacts of the receptacles furnished as part of the equipment are  
bonded to the equipment. [250.140 Exception (4)]  
History: 2015 AACS.  
R 408.30538 Combustible insulation.  
Rule 538. Section 302.13 of the code is amended to read as follows:  
302.13. Combustible insulation. Combustible insulation shall be separated a minimum  
of 3 inches (76 mm) from recessed lighting fixtures, fan motors, and other heat-producing  
devices.  
Exception: When heat-producing devices are listed for lesser clearances, combustible  
insulation complying with the listing requirements shall be separated in accordance with  
the conditions stipulated in the listing.  
Recessed lighting fixtures installed in the building thermal envelope shall be installed  
in accordance with the manufacturer's installation instructions.  
History: 2001 AACS; 2010 AACS.  
R 408.30539 Solvent cementing.  
Rule 539. Section P3003.14.2 of the code is amended to read as follows:  
P3003.14.2 Solvent cementing. Joint surfaces shall be clean and free from moisture.  
A primer that conforms to ASTM F 656, as listed in chapter 43, shall be applied. Solvent  
cement not purple in color and conforming to ASTM D 2564, CSA B137.3 or CSA B181.2,  
as listed in chapter 43, shall be applied to all joint surfaces. The joint shall be made while  
the cement is wet, and shall be in accordance with ASTM D 2855, as listed in chapter 43.  
Solvent-cement joints shall be permitted above or below ground.  
History: 2004 AACS; 2008 AACS.  
R 408.30539a Automatic fire sprinkler systems.  
Rule 539a. Sections R313.1, P2902.5.4 and P2904.1 of the code are amended to read  
as follows:  
Page 54  
R313.1. Design and installation. Where installed, automatic residential fire sprinkler  
systems shall conform to the design and installation requirements of the national fire  
protection association (NFPA) standard 13D or P2904.1.  
P2902.5.4. Connections to automatic fire sprinkler systems. The potable water supply  
to automatic fire sprinkler systems shall be protected against backflow by a double check-  
valve assembly or a reduced pressure principle backflow preventer.  
Exception: Isolation of the water distribution system is not required for deluge,  
preaction, or dry pipe system.  
P2904.1. General. Where installed, residential fire sprinkler systems, or portions  
thereof, shall be in accordance with NFPA 13D.  
History: 2010 AACS.  
R 408.30540 Elevators and platform lifts.  
Rule 540. Sections R321.1, R321.2, and R321.3 of the code are amended to read as  
follows:  
R321.1. Elevators. Where provided, passenger elevators, limited-use/limited-  
application elevators or private residence elevators shall comply with the Michigan  
elevator rules R 408.7001 to R 408.8695.  
R321.2. Platform lifts. Where provided, platform lifts shall comply with the Michigan  
elevator rules R 408.7001 to R 408.8695.  
R321.3. Accessibility. Elevators or platform lifts that are part of an accessible route  
required by chapter 11 of the Michigan building code, shall comply with ICC A117.1, as  
listed in chapter 44, and 1966 PA 1, MCL125.1354 to MCL 125.1356.  
History: 2004 AACS; 2008 AACS; 2010 AACS.  
R 408.30541a Duct Installation.  
Rule 541a. Section M1502.4.2 of the code is amended to read as follows:  
M1502.4.2. Duct Installation. Dryer exhaust ducts shall be supported at 4 foot (1 219  
mm) intervals and secured in place. The insert end of the duct shall extend into the  
adjoining duct or fitting in the direction of airflow. Ducts shall not be joined with screws or  
similar fasteners that protrude into the inside of the duct.  
History: 2004 AACS; 2010 AACS; 2015 AACS.  
R 408.30542 Floor register location.  
Rule 542. Section M1601.4.10 is added to the code to read as follows:  
M1601.4.10. Floor register location. Floor registers located in room or spaces  
containing water closets shall be located a minimum of 3 feet (914 mm) from the water  
closet.  
History: 2004 AACS; 2010 AACS; 2015 AACS.  
Page 55  
R 408.30543 Rescinded.  
History: 2004 AACS; 2008 AACS; 2015 AACS.  
R 408.30544 Light, ventilation, and heating.  
Rule 544. Section R303.5.2 of the code is amended to read as follows:  
R303.5.2. Exhaust openings. Outside exhaust openings shall be located as not to  
create a nuisance. Exhaust openings shall not be directed onto walkways. Exhaust openings  
shall not terminate within 3 feet of a ventilated section in a soffit.  
History: 2004 AACS; 2008 AACS; 2010 AACS; 2015 AACS.  
R 408.30544a Townhouses.  
Rule 544a. Section R302.2 of the code is amended to read as follows:  
R302.2. Townhouses. Each townhouse shall be considered a separate building and  
shall be separated b A 2-hour fire-resistance-rated wall assembly tested in accordance with  
ASTME E 119 or UL 263 with exposure from both sides.  
Exception: Where the building is provided with an automatic fire sprinkler system  
installed in accordance with NFPA 13D or P2904.1, a common 1-hour fire-resistance-rated  
wall assembly tested in accordance with ASTM E 119 or UL 263, as listed in chapter 44, is  
permitted for townhouses if such walls do not contain plumbing or mechanical equipment,  
ducts, or vents in the cavity of the common wall. The wall shall be rated for fire exposure  
from both sides and shall extend to and be tight against exterior walls and the underside of  
the roof sheathing. Electrical installations shall be installed in accordance with chapters 34  
to 43. Penetrations of electrical outlet boxes shall be in accordance with section R302.4.  
History: 2010 AACS.  
R 408.30544b Exterior walls.  
Rule 544b. Section R302.5.1 of the code is amended and table R302.1(1) is added to  
read as follows:  
R302.5.1. Opening protection. Openings from a private garage directly into a room  
used for sleeping purposes shall not be permitted. Other openings between the garage and  
residence shall be equipped with solid wood doors not less than 1 3/8 inches (35 mm) in  
thickness, solid or honeycomb-core steel doors not less than 1 3/8 inches (35 mm) thick, or  
20-minute fire-rated doors.  
TABLE R302.1(1)  
EXTERIOR WALLS  
EXTERIOR WALL ELEMENT  
MINIMUM FIRE-  
RESISTANCE RATING  
MINIMUM FIRE  
SEPARATION  
DISTANCE  
Walls  
Fire-resistance rated  
1 hour-tested in accordance  
with ASTM E 119 or UL 263  
< 5 feet  
Page 56  
with exposure from both sides  
0 hours  
Not fire-resistance  
rated  
≥ 5 feet  
Not alloweda  
Fire-resistance rated  
Not fire-resistance  
rated  
NA  
1 hour on the underside  
0 hours  
< 2 feet  
≥ 2 feet to < 5 feet  
≥ 5 feet  
Projections  
Opening in walls  
Not allowed  
25% maximum of wall  
area  
N/A  
0 hours  
< 3 feet  
3 feet  
Unlimited  
0 hours  
Comply with Section R302.4  
None required  
5 feet  
< 5 feet  
5 feet  
Penetrations  
All  
For SI: 1 foot = 304.8 mm  
N/A = Not applicable  
a. except as allowed as per Section R302.1 exceptions 3 and 4  
History: 2004 AACS; 2010 AACS; 2015 AACS.  
R 408.30544c Polyethylene plastic.  
Rule 544c. Sections P2906.3.1, P2906.10.1, P3003.11.1 and P3003.12.1 of the code  
are amended to read as follows:  
P2906.3.1. Heat-fusion joints. Joint surfaces shall be clean and free from moisture.  
Joint surfaces shall be heated to melting temperature and joined. The joint shall be  
undisturbed until cool. Joints shall be made in accordance with ASTM F 2620 and the  
manufacturer’s instructions.  
P2906.10.1. Heat-fusion joints. Heat fusion joints for polypropylene pipe and tubing  
joints shall be installed with socket-type heat-fused polypropylene fittings, butt-fusion  
polypropylene fittings, or electrofusion polypropylene fittings. Joint surfaces shall be clean  
and free from moisture. The joint shall be undisturbed until cool. Joints shall be made in  
accordance with ASTM D 2657 and the manufacturer’s instructions.  
P3003.11.1. Heat-fusion joints. Heat-fusion joints for polyolefin pipe and tubing  
joints shall be installed with socket-type heat-fused polyolefin fittings or electrofusion  
polyolefin fittings. Joint surfaces shall be clean and free from moisture. The joint shall be  
undisturbed until cool. Joints shall be made in accordance with ASTM D 2657, ASTM F  
1290, or CSA B181.3, and the manufacturer’s instructions.  
P3003.12.1. Heat-fusion joints. Joint surfaces shall be clean and free from moisture.  
All joint surfaces shall be cut, heated to melting temperature, and joined using tools  
specifically designed for the operation. Joints shall be undisturbed until cool. Joints shall  
be made in accordance with ASTM F 2620 and the manufacturer’s instructions.  
History: 2015 AACS.  
R 408.30545 Masonry veneer wall covering.  
Rule 545. Figures R703.8, R703.8.2.1, and R703.8.2.2, of the code are amended to  
read as follows:  
Page 57  
Page 58  
Page 59  
History: 2015 AACS.  
R 408.30545a Masonry heater clearance.  
Rule 545a. Section R1002.5 of the code is amended to read as follows:  
R1002.5. Masonry heater clearance. Combustible materials shall not be placed within  
36 inches (914 mm) of the outside surface of a masonry heater unless installed in  
Page 60  
accordance with NFPA 211, and the required space between the heater and combustible  
material shall be fully vented to permit the free flow of air around all heater surfaces.  
Exceptions:  
1. When the masonry heater wall is at least 8 inches (203 mm) thick of solid masonry  
and the wall of the heat exchange channels is at least 5 inches (127 mm) thick of solid  
masonry, combustible materials shall not be placed within 4 inches (102 mm) of the outside  
surface of a masonry heater. A clearance of at least 8 inches (203 mm) shall be provided  
between the gas-tight capping slab of the heater and a combustible ceiling.  
2. Masonry heaters listed and labeled in accordance with UL 1482 may be installed in  
accordance with the listing specifications and the manufacturer’s written instructions.  
History: 2010 AACS; 2015 AACS.  
R 408.30546 Smoke alarm locations for existing buildings.  
Rule 546. Sections R314.2.2, R314.3, R314.3.2, and R314.3.3, R314.4, are amended  
to the code to read as follows:  
R314.2.2. Alterations, repairs, and additions. When  
alterations, repairs, or additions requiring a permit occur, or when 1 or more sleeping rooms  
are added or created in existing dwellings, the individual dwelling unit shall be equipped  
with smoke alarms located as required for new dwellings.  
Exceptions:  
1. Work involving the exterior surfaces of dwellings, such as the replacement of  
roofing or siding, or the addition or replacement of windows or doors, or the addition of a  
porch or deck, are exempt from the requirements of this section.  
2. Installations, alteration, or repairs of electrical, plumbing, or mechanical systems  
are exempt from the requirements of this section.  
R314.3. Location. Smoke alarms shall be installed in the following locations:  
1. In each sleeping room or in the immediate vicinity of the sleeping room.  
2. On each additional story of the dwelling, including basements and habitable attics  
and not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with  
split levels and without an intervening door between the adjacent levels, a smoke alarm  
installed on the upper level shall suffice for the adjacent lower level provided that the lower  
level is less than 1 full story below the upper level. R314.3.2. Smoke alarms in existing  
buildings constructed before November 6, 1974, not undergoing an alteration, addition, or  
change in occupancy requiring a building permit, shall be installed in the following  
locations in each dwelling unit or sleeping unit:  
(1) In each sleeping room.  
(2) On each floor level including the basement level.  
For sleeping units with split levels and without an intervening door between the  
adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent  
lower level provided that the lower level is less than 1 full story below the upper level.  
R314.3.3. Equipment requirements. The required equipment for smoke alarms  
required by R314.3.2 shall consist of the following:  
(1) Installation. Smoke alarm devices shall be listed and installed in accordance with  
the manufacturer’s installation requirements, the provisions of the code and the provisions  
of NFPA 72 as listed in chapter 44.  
Page 61  
(2) Power Source. The equipment shall be operable by power from 1 of the following  
primary sources:  
(a) The building wiring provided that such wiring is served from a commercial source  
and the smoke alarm is equipped with a battery backup. Wiring shall be permanent and  
without a disconnecting switch other than as required for overcurrent protection.  
(b) A battery operated smoke alarm.  
(c) A rechargeable battery operated smoke alarm shall be automatically recharged by  
an AC circuit of the commercial light and power source.  
(d) A household use alarm system with battery backup listed and approved in  
accordance with the household fire warning equipment provisions of NFPA 72, as  
referenced in Section R314.1 of the code.  
(3) Audible alarm notification. The activation of the alarm signal shall produce a  
sound that is audible in all occupiable dwelling areas.  
(4) Testing and maintenance. The owner of a dwelling unit, in which required or  
optional fire detection or fire protection systems equipment is installed, shall be responsible  
for the proper operation, testing, and maintenance of the equipment in accordance with the  
manufacturer’s instructions included with the equipment. The occupant of rental dwelling  
units shall be responsible for the periodic operational testing and periodic cleaning of the  
installed equipment within the rental unit in accordance with the testing instructions  
provided in the manufacturer’s instructions for the equipment. If the system fails, breaks,  
or is out of service, it shall be repaired and functional within 30 days.  
Exception: Smoke alarms and devices installed in buildings constructed before  
November 6, 1974, where an installation was approved by the appropriate enforcing agency  
under regulations in effect at the time of the installation shall be considered to comply with  
the provisions of the code.  
R314.4. Interconnection. Where more than 1 smoke alarm is required to be installed  
within an individual dwelling unit in accordance with Section R314.3, the alarm devices  
shall be interconnected in such a manner that the actuation of 1 alarm will activate all of the  
alarms in the individual unit. Physical interconnection of smoke alarms shall not be  
required where listed wireless alarms are installed and all alarms sound upon activation of 1  
alarm.  
Exception: Interconnection of smoke alarms in existing areas shall not be required.  
History: 2005 AACS; 2008 AACS; 2010 AACS; 2015 AACS.  
Editor's Note: An obvious error in R 408.30546 was corrected at the request of the promulgating agency,  
pursuant to Section 56 of 1969 PA 306, as amended by 2000 PA 262, MCL 24.256. The rule containing the  
error was published in Michigan Register, 2015 MR 19. The memorandum requesting the correction was  
published in Michigan Register, 2016 MR 3.  
R 408.30547 Rescinded.  
History: 2004 AACS; 2008 AACS; 2015 AACS.  
R 408.30547a Radon Control Methods.  
Rule 547a. Figure AF101 and table AF101 are amended to read as follows:  
Page 62  
Figure AF101. EPA map of radon zones.  
Zone 1 High Potential (Greater than 4 pCi/La)  
Zone 2 Moderate potential (From 2 to 4 pCi/L)  
Zone 3 Low potential (Less than 2 pCi/L)  
apCi/L standard for picocuries per liter of radon gas. The U.S. environmental protection  
agency (EPA) recommends that all homes that measure 4 pCi/L and greater be mitigated.  
The EPA and the U.S. geological survey have evaluated the radon potential in the U.S.  
and have developed a map of radon zones designed to assist building officials in deciding  
whether radon resistant features are applicable in new construction.  
The map assigns each of the 83 counties in Michigan to 1 of 3 zones based on radon  
potential. Each zone designation reflects the average short-term radon measurement that  
can be expected to be measured in a building without the implementation of radon-control  
Page 63  
methods. The radon zone designation of highest priority is zone 1. Table AF101 lists the  
zone 1 counties illustrated on the map. More detailed information can be obtained from  
state-specific booklets (EPA-402-R-93-021 through 070) available through state radon  
offices or from EPA regional offices.  
Figure AF101  
EPA Map of Radon Zones  
Table AF101  
High Radon-Potential (Zone 1) Countiesa  
Michigan Counties  
Branch  
Calhoun  
Cass  
Hillsdale  
Jackson  
Kalamazoo  
Lenawee  
St. Joseph  
Washtenaw  
a. The EPA recommends that this county listing be supplemented with other available  
state and local data to further understand the radon potential of a zone 1 area.  
History: 2015 AACS.  
R 408.30547b Chimneys.  
R547b. Sections R1003.9.1, R1005.4, Figure R1001.1, are amended and Figures  
R1003.9.1(1) and R1003.9.1(2) are added to read as follows:  
R1003.9.1. Chimney caps. Masonry chimneys shall have a concrete, metal, or stone  
cap sloped a minimum of 10 degrees to shed water, a drip edge or slot and shall be flashed  
in accordance with figure R1003.9.1(1). The joint space between the flue liner and the cap  
shall be filled with compressible filler and caulked with a suitable sealant to allow for  
expansion and contraction of the materials. All vertical joints in a chimney cap shall be  
caulked with a suitable sealant.  
The cap shall be a minimum of 2” (51 mm) thick at the outer edge and overhang the  
outer wall of the chimney by a minimum of 2” (51 mm). The drip slot shall be located not  
less than 1-1/2” (38 mm) from the outer surface of the chimney. A bond break shall be  
installed between the concrete cap and the chimney masonry.  
Metal caps shall lap down the chimney wall a minimum of 4” (102 mm) and be sealed  
with a suitable sealant.  
Joint sealants shall meet ASTM C 920, type S or M, grade NS, class 25 and be  
installed in accordance with the manufacturer’s installation instructions.  
R1005.4. Factory-built chimneys. Chimneys for use with factory-built fireplaces shall  
comply with the requirements of UL 127. The metal chase cover shall be sloped a  
Page 64  
minimum of 10to shed water. Metal chase cover shall lap down the chimney wall a  
minimum of 4” (102 mm) and be sealed with a suitable sealant. Exterior wall claddings  
shall be applied and flashed in accordance with Section R703 and manufacturer’s  
installation instructions.  
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.  
Page 65  
Figure R1001.1  
Fireplace and Chimney Details  
Page 66  
History: 2015 AACS.  
R 408.30547c General.  
Rule 547c. Sections N1101.3.1, N1101.7, N1101.10, N1101.12.3, N1101.16, tables  
N1101.10, and N1101.10.2(2) are amended and figure N1101.10a of the code is added to  
read as follows:  
N1101.3.1 (R101.4.3). Additions, alterations, renovations, or repairs. Additions,  
alterations, renovations, or repairs to an existing building, building system, or portion  
thereof shall conform to the provisions of this code as they relate to new construction  
without requiring the unaltered portion(s) of the existing building or building system to  
comply with this code. Additions, alterations, renovations, or repairs shall not create an  
unsafe or hazardous condition or overload existing building systems. An addition shall be  
deemed to comply with this code if the addition alone complies or if the existing building  
and addition comply with this code as a single building.  
Exception: The following are exempt provided the energy use of the building is not  
increased:  
1. Storm windows installed over existing fenestration.  
2. Glass only replacements in an existing sash and frame.  
Page 67  
3. Existing ceiling, wall, or floor cavities exposed during construction provided that  
these cavities are filled with insulation.  
4. Construction where the existing roof, wall, or floor cavity is not exposed.  
5. Reroofing where the roof is part of the thermal envelope, and where neither the roof  
sheathing nor the roof insulation is exposed.  
6. Reroofing where the roof is not part of the thermal envelope.  
7. Replacement of existing doors that separate conditioned space from the exterior  
shall not require the installation of a vestibule or revolving door, provided, however, that an  
existing vestibule that separates a conditioned space from the exterior shall not be removed.  
8. Alterations that replace less than 50% of the luminaries in a space, provided that  
such alterations do not increase the installed interior lighting power.  
9. Alterations that replace only the bulb and ballast within the existing luminaries in a  
space provided that the alteration does not increase the installed interior lighting power.  
N1101.7 (R102.1.1). Above code programs. The state construction code commission  
may evaluate and approve a national, state, or local energy efficiency program to exceed the  
energy efficiency required by this code. Buildings approved in writing by such an energy  
efficiency program, such as ICC 700-2012 “silver” or energy star version 3 (rev. 07), shall  
be considered in compliance with this code. The requirements identified as “mandatory” in  
chapter 4 shall be met.  
N1101.10 (R301.1). Climate zones. Climate zones from figures 301.1, 301.1a or table  
301.1 shall be used in determining the applicable requirements of this code.  
N1101.12.3. Fenestration product rating. U-factors of fenestration products  
(windows, doors, and skylights) shall be determined in accordance with NFRC 100 by an  
accredited, independent laboratory, and labeled and certified by the manufacturer. Products  
lacking such a labeled U-factor shall be assigned a default U-factor from table  
N1101.12.3(1) or N1101.12.3(2).  
Exception: Computer simulations by independent NFRC certified laboratories or  
approval under section 21 of 1972 PA 230, MCL 125.1521 is considered in compliance  
with this section.  
N1101.16 (R401.3). Certificate (mandatory). A permanent certificate shall be posted  
on or in the electrical distribution panel, and shall meet all of the following:  
(a) Be affixed or attached so it does not cover or obstruct the visibility of the circuit  
directory label, service disconnect label, or other required labels.  
(b) Be completed by the builder or registered design professional.  
(c) List the predominant R-values of insulation installed in or on ceiling/roof, walls,  
foundation (slab, basement wall, crawlspace wall and/or floor) and ducts outside  
conditioned spaces and U-factors for fenestration. If there is more than 1 value for each  
component, then the certificate shall list the value covering the largest area.  
(d) List the types and efficiencies of heating, cooling, and service water heating  
equipment.  
(e) If a gas-fired unvented room heater, electric furnace, or baseboard electric heater is  
installed in the residence, then the certificate shall list “gas-fired unvented room heater,” as  
appropriate. An efficiency shall not be listed for gas-fired unvented room heaters, electric  
furnaces, or electric baseboard heaters.  
Page 68  
Table N1101.10  
Climate Zones by County  
Zones  
5A  
6A  
7
Allegan  
Barry  
Bay  
Berrien  
Branch  
Alcona  
Alger  
Alpena  
Antrim  
Baraga  
Chippewa  
Gogebic  
Houghton  
Iron  
Arenac  
Calhoun  
Cass  
Clinton  
Eaton  
Genesee  
Gratiot  
Benzie  
Keweenaw  
Luce  
Mackinac  
Ontonagon  
Schoolcraft  
Charlevoix  
Cheboygan  
Clare  
Crawford  
Delta  
Hillsdale  
Ingham  
Ionia  
Jackson  
Kalamazoo  
Kent  
Dickinson  
Emmet  
Gladwin  
Grand Traverse  
Huron  
Iosco  
Lapeer  
Isabella  
Lenawee  
Livingston  
Macomb  
Midland  
Monroe  
Montcalm  
Muskegon  
Oakland  
Ottawa  
Saginaw  
Shiawassee  
St. Clair  
St. Joseph  
Tuscola  
Van Buren  
Washtenaw  
Wayne  
Kalkaska  
Lake  
Leelanau  
Manistee  
Marquette  
Mason  
Mecosta  
Menominee  
Missaukee  
Montmorency  
Newaygo  
Oceana  
Ogemaw  
Osceola  
Oscoda  
Otsego  
Presque Isle  
Roscommon  
Sanilac  
Wexford  
Key: A – Moist. Absence of moisture designation indicates moisture regime is irrelevant.  
Table N1101.10.2(2)  
Climate Zone Definitions  
Zone  
Number  
5A  
Thermal Criteria  
IP Units  
SI Units  
5400 < HDD65F7200  
3000 < HDD18C4000  
Page 69  
6A  
7
7200 < HDD65F9000  
9000 < HDD65F12600  
4000 < HDD18C5000  
5000 < HDD18C7000  
For SI: ºC = [(ºF)-32]/1.8  
History: 2015 AACS.  
Page 70  
Editor's Note: An obvious error in R 408.30547c was corrected at the request of the promulgating agency,  
pursuant to Section 56 of 1969 PA 306, as amended by 2000 PA 262, MCL 24.256. The rule containing the  
error was published in Michigan Register, 2015 MR 19. The memorandum requesting the correction was  
published in Michigan Register, 2016 MR 3.  
R 408.30547d Building thermal envelope.  
Rule 547d. Sections N1102.2.6, N1102.2.12, N1102.3.3, N1102.3.6, N1102.4,  
N1102.4.1.1, N1102.4.1.2, N1102.4.2, N1102.4.3, N1102.4.4, tables N1102.1.1, N1102.1.3,  
and N1102.4.1.1 of the code are amended to read as follows:  
N1102.2.6 (R402.2.6). Steel-frame ceilings, walls, and floors. Steel-frame ceilings,  
walls, and floors shall meet the insulation requirements of table N1102.2.6 or shall meet the  
U-factor requirements in table N1102.1.3. The calculation of the U-factor for a steel-frame  
envelope assembly shall use a series-parallel path calculation method.  
N1102.2.12 Thermally isolated sunroom insulation. The minimum ceiling insulation  
R-values shall be R-24 in zones 5 to 7. The minimum wall R-value shall be R-13 in all  
zones. New wall or walls separating a sunroom from conditioned space shall meet the  
building thermal envelope requirements.  
N1102.3.3 (R402.3.3). Glazed fenestration exemption. Up to 15 square feet (1.4m2)  
of glazed fenestration per dwelling unit may be exempt from U-factor requirements in  
section N1102.1.1. This exemption shall not apply to the U-factor alternative approach in  
section N1102.1.1 and the total UA alternative in section N1102.1.4.  
N1102.3.6 (R402.3.6). Replacement fenestration. Where some or all of an existing  
fenestration unit is replaced with a new fenestration product, including sash and glazing, the  
replacement fenestration unit shall meet the applicable requirements for U-factor in table  
N1102.1.3. Where some or all of an existing fenestration unit is replaced with a new  
fenestration product, including sash and glazing, the replacement fenestration unit shall  
meet the applicable requirements for U-factor in table N1102.1.1.  
N1102.4 (R402.4). Air leakage. The building thermal envelope shall be constructed  
to limit air leakage in accordance with the requirements of sections N1102.4.1 through  
N1102.4.4.  
N1102.4.1 (R402.4.1). Building thermal envelope. The building thermal envelope  
shall comply with sections N1102.4.1.1 and N1102.4.1.2.  
N1102.4.1.1 (R402.4.1.1). Installation (mandatory). The components of the building  
thermal envelope as listed in table N1102.4.1.1 shall be installed in accordance with the  
manufacturer’s instructions and the criteria listed in table N1102.4.1.1, as applicable to the  
method of construction. The sealing methods between dissimilar materials shall allow for  
differential expansion and contraction.  
N1102.4.1.2 (R402.4.1.2). Testing (prescriptive). The building or dwelling unit shall  
be tested and verified as having an air leakage rate of not exceeding 4 air changes per hour.  
Testing shall be conducted with a blower door at a pressure of 0.2” w.g. (50 pascals).  
Where required by the code official, testing shall be conducted by a certified independent  
third party. Certification programs shall be approved by the state construction code  
commission. A written report of the results of the test shall be signed by the party  
conducting the test and provided to the code official. Testing shall be performed at any  
time after creation of all penetrations of the building thermal envelope.  
Page 71  
During testing all of the following apply:  
1. Exterior windows and doors, fireplace, and stove doors shall be closed, but not  
sealed, beyond the intended weather stripping or other infiltration control measures.  
2. Dampers including exhaust, intake, makeup air, backdraft, and flue dampers shall  
be closed, but not sealed beyond intended infiltration control measures.  
3. Interior doors, if installed at the time of the test, shall be open.  
4. Exterior doors for continuous ventilation systems and heat recovery ventilators  
shall be closed and sealed.  
5. Heating and cooling systems, if installed at the time of the test, shall be turned off.  
6. Supply and return registers, if installed at the time of the test, shall be fully open.  
N1102.4.2 (R402.4.2). Fireplaces (mandatory). New wood-burning masonry  
fireplaces shall have tight-fitting flue dampers and outdoor combustion air.  
N1102.4.3 (R402.4.3). Fenestration air leakage (mandatory). Windows, skylights,  
and sliding glass doors shall have an air infiltration rate of no more than 0.3 cfm per square  
foot (1.5 L/s/m2), and swinging doors no more than 0.5 cfm per square foot (2.6 L/s/m2),  
when tested according to NFRC 400 or AAMA/WDMA/CSA 101/I.S.2/A440 by an  
accredited, independent laboratory and listed and labeled by the manufacturer.  
Exception: Site-built windows, skylights, and doors.  
N1102.4.4 (R402.4.4). Recessed lighting (mandatory). Recessed luminaires installed  
in the building thermal envelope shall be sealed to limit air leakage between conditioned  
and unconditioned spaces. All recessed luminaires shall be IC-rated and labeled as having  
an air leakage rate not more than 2.0 cfm (0.944 L/s) when tested in accordance with  
ASTM E 283 at a 1.57 psf (75 Pa) pressure differential. All recessed luminaires shall be  
sealed with a gasket or caulk between the housing and the interior wall or ceiling covering.  
Page 72  
TABLE N1102.1.1 (R402.1.1)  
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENTa  
Clima  
te  
Zone  
Fenestrati  
on  
Skylig  
Ceili  
ng  
R-  
Wood  
Frame Wall  
R-Value  
Mass  
Wall  
Floor  
R-  
Value  
Baseme  
Slabd  
R-  
Crawl  
Spacec  
Wall  
htb  
U-  
Factor  
ntc  
U-Factorb  
R-  
Wall  
R-Value  
Value  
Value  
Valueg  
&
R-Value  
Depth  
5A  
6A  
7
0.32  
0.32  
0.32  
0.55  
0.55  
0.55  
38  
49  
49  
20 or 13 +  
13/17  
15/20  
19/21  
30e  
30e  
38e  
10/13  
15/19  
15/19  
10, 2  
ft  
10, 4  
ft  
10, 4  
ft  
15/19  
15/19  
15/19  
5f  
20 or 13 +  
5f  
20 or 13 +  
5f  
a. R-values are minimums. U-factors are maximums. When insulation is installed in a cavity which is less than the label or design thickness of  
the insulation, the installed R-value of the insulation shall not be less than the R-values specified in the table.  
b. The fenestration U-factor column excludes skylights.  
c. “15/19” means R-15 continuous insulation on the interior or exterior of the home or R-19 cavity insulation at the interior of the basement wall.  
“15/19” may be met with R-13 cavity insulation on the interior of the basement wall plus R-5 continuous insulation on the interior or exterior of the  
home. “10/13” means R-10 continuous insulation on the interior or exterior of the home or R-13 cavity insulation at the interior of the basement wall.  
d. R-5 shall be added to the required slab edge R-values for heated slabs.  
e. Or insulation sufficient to fill the framing cavity, R-19 minimum.  
f. First value is cavity insulation, second is continuous insulation or insulated siding, so “13 + 5” means R-13 cavity insulation plus R-5  
continuous insulation or insulated siding. If structural sheathing covers 40% or less of the exterior, continuous insulation R-value may be reduced by  
no more than R-3 in the locations where structural sheathing is used – to maintain a consistent total sheathing thickness.  
g. The second R-value applies when more than 1/2 the insulation is on the interior of the mass wall.  
TABLE N1102.1.3 (R402.1.3)  
EQUIVALENT U-FACTORSa  
Clim  
ate Zone  
Fenestrati  
on  
Skylig  
ht  
Ceiling  
U-  
Frame  
Wall  
Mass Wall  
Floor  
U-  
Basemen  
t
Crawl  
Space  
U-Factorb  
U-Factor  
U-  
Factor  
U-Factor  
Factor  
Wall  
Wall  
Factor  
U-Factor  
U-  
Factor  
5A  
6A  
7
0.32  
0.32  
0.32  
0.55  
0.55  
0.55  
0.030  
0.026  
0.026  
0.057  
0.057  
0.057  
0.082  
0.060  
0.057  
0.033  
0.033  
0.028  
0.059  
0.050  
0.050  
0.055  
0.055  
0.055  
a. Nonfenestration U-factors shall be obtained from measurement, calculation, or an approved source.  
b. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.065 in zone 5 and marine 4, and  
0.057 in zones 6 and 7.  
Page 74  
TABLE N1102.4.1.1 (R402.4.1.1)  
AIR BARRIER AND INSULATION INSTALLATION  
COMPONENT  
CRITERIAa  
Air barrier and thermal barrier  
A continuous air barrier shall be installed in the building envelope.  
Exterior thermal envelope contains a continuous air barrier.  
Breaks or joints in the air barrier shall be sealed.  
Air-permeable insulation shall not be used as a sealing material.  
The air barrier in any dropped ceiling/soffit shall be aligned with the insulation and  
any gaps in the air barrier sealed.  
Access openings, drop down stair, or knee wall doors to unconditioned attic spaces  
shall be sealed.  
Ceiling/attic  
Walls  
Corners and headers shall be insulated and the junction of the foundation and sill  
plate shall be sealed.  
The junction of the top plate and top of exterior walls shall be sealed.  
Exterior thermal envelope insulation for framed walls shall be installed in  
substantial contact and continuous alignment with the air barrier.  
Knee walls shall be sealed.  
Windows, skylights, and doors  
The space between window/door jambs and framing, and skylights and framing  
shall be sealed.  
Rim joists  
Floors  
Rim joists shall be insulated and include the air barrier.  
Insulation shall be installed to maintain permanent contact with underside of  
subfloor decking.  
(including above-garage and cantilevered  
floors)  
The air barrier shall be installed at any exposed edge of insulation.  
Where provided in lieu of floor insulation, insulation shall be permanently attached  
to the crawlspace walls.  
Crawl space walls  
Exposed earth in unvented crawl spaces shall be covered with a class I vapor  
retarder with overlapping joints taped.  
Shafts, penetrations  
Narrow cavities  
Duct shafts, utility penetrations, and flue shafts opening to exterior or  
unconditioned space shall be sealed.  
Batts in narrow cavities shall be cut to fit, or narrow cavities shall be filled by  
insulation that on installation readily conforms to the available cavity space.  
Air sealing shall be provided between the garage and conditioned spaces.  
Recessed light fixtures installed in the building thermal envelope shall be air tight,  
Garage separation  
Recessed lighting  
Page 75  
IC rated, and sealed to the drywall.  
Plumbing and wiring  
Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior  
walls, or insulation that on installation readily conforms to available space shall extend  
behind piping and wiring.  
Shower/tub on exterior wall  
Electrical/phone box on exterior walls  
HVAC register boots  
Exterior walls adjacent to showers and tubs shall be insulated and the air barrier  
installed separating them from the showers and tubs.  
The air barrier shall be installed behind electrical or communication boxes or air-  
sealed boxes shall be installed.  
HVAC register boots that penetrate the building thermal envelope shall be sealed to  
the subfloor or drywall.  
Fireplace  
An air barrier shall be installed on fireplace walls.  
a. In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.  
History: 2015 AACS.  
R 408.30547e Simulated performance alternative.  
Rule 547e. Table N1105.5.2(1) [R405.5.2(1)] of the code is amended to read as follows:  
TABLE N1105.5.2(1) [R405.5.2(1)]  
SPECIFICATIONS FOR THE STANDARD REFERENCE AND PROPOSED DESIGNS  
BUILDING  
STANDARD REFERENCE DESIGN  
PROPOSED DESIGN  
COMPONENT  
Above-grade  
walls  
Type: mass wall if proposed wall is mass; otherwise wood frame.  
Gross area: same as proposed  
U-factor: from Table N1102.1.3  
Solar absorptance = 0.75  
Remittance = 0.90  
Type: same as proposed  
Gross area: same as proposed  
U-factor: from Table N1102.1.3, with insulation layer on interior side of walls.  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
Basement and  
crawl space walls  
Above-grade  
floors  
Type: wood frame  
As proposed  
As proposed  
As proposed  
As proposed  
Gross area: same as proposed  
U-factor: from Table N1102.1.4  
Type: wood frame  
Ceilings  
Page 76  
Gross area: same as proposed  
U-factor: from Table N1102.1.4  
Type: composition shingle on wood sheathing  
Gross area: same as proposed  
Solar absorptance = 0.75  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
Roofs  
Emittance = 0.90  
Attics  
Foundations  
Type: vented with aperture = 1 ft2 per 300 ft2 ceiling area  
Type: same as proposed foundation wall area above and below grade and soil.  
Characteristics: same as proposed  
As proposed  
As proposed  
As proposed  
As proposed  
As proposed  
Doors  
Area: 40 ft2  
Orientation: North  
U-factor: same as fenestration from Table N1102.1.3.  
Glazing  
Totalb =  
(a) The proposed glazing area: where proposed glazing area is less than  
of the conditioned floor area.  
15%  
(b) 15% of the conditioned floor area; where the proposed glazing area is 15% or  
more of the conditioned floor area.  
Orientation: equally distributed to four cardinal compass orientations (N, E, S &  
W).  
As proposed  
As proposed  
U-factor: from Table N1102.1.4  
SHGC: From Table N1102.1.2 except that for climates with no requirement (NR)  
As proposed  
SHGC = 0.40 shall be used.  
0.92-(0.21 x SHGC as proposed)  
As proposed  
Interior shade fraction: 0.92-(0.21 x SHGC for the standard reference design)  
External shading: none  
Skylights  
Thermally  
None  
None  
As proposed  
As proposed  
isolated sunrooms  
Air exchange rate  
Air leakage rate of 4 air changes per hour at a pressure of 0.2 inches w.g. (50 Pa).  
The mechanical ventilation rate shall be in addition to the air leakage rate and the  
same as in the proposed design, but no greater than 0.01 x CFA + 7.5 x (Nbr + 1)  
where:  
The measured air exchange ratec.  
The mechanical ventilation rated shall  
be in addition to the air leakage rate  
and shall be as proposed.  
CFA = conditioned floor area  
Page 77  
Nbr = number of bedrooms  
Energy recovery shall not be assumed for mechanical ventilation.  
IGain = 17,900 + 23.8 x CFA + 4104 x Nbr (Btu/day per dwelling unit)  
Internal gains  
Internal mass  
Same as standard reference  
design.  
An internal mass for furniture and contents of 8 pounds per square foot of floor  
area.  
Same as standard reference  
design, plus any additional mass  
specifically designed as a thermal  
storage elementc but not integral to  
the building envelope or structure.  
Structural mass  
For masonry floor slabs, 80% of floor area covered by R-2 carpet and pad, and  
20% of floor directly exposed to room air.  
As proposed  
As proposed  
As proposed  
For Masonry basement walls, as proposed, but with insulation required by Table  
R402.1.4 located on the interior side of the walls.  
For other walls, for ceilings, floors, and interior walls, wood frame construction.  
Heating  
As proposed for other than electric heating without a heat pump. Where the  
proposed design utilizes electric heating without a heat pump the standard reference  
design shall be an air source heat pump meeting the requirements of the Michigan  
energy code-commercial provisions.  
systemsf,g  
As proposed  
As proposed  
As proposed  
Capacity: sized in accordance with Section N1103.7.  
As proposed  
Capacity: sized in accordance with Section N1103.7.  
Cooling  
systemsf,h  
Service water  
heatingf,g,h,i  
As proposed  
Use: same as proposed design  
Thermal  
distribution systems  
Untested distribution systems: DSE = 0.88  
Untested distribution systems:  
DSE from Table N1105.5.2(2)  
Tested ducts: Leakage rate to outside conditioned space as specified Section  
N1103.3.2  
Tested ducts: Tested leakage rate  
to outside conditioned space  
Tested duct location: Unconditioned attic  
Duct location: As proposed  
Duct insulation: As proposed  
Tested duct insulation: in accordance with Section N1103.3.1  
Type: Manual, cooling temperature setpoint = 75F;  
Thermostat  
Page 78  
Heating temperature setpoint = 72F  
Same as standard reference  
For SI: 1 square foot = 0.93 m2, 1 British thermal unit = 1055 J, 1 pound per square foot = 4.88 kg/m2, 1 gallon (U.S.) = 3.785 L,  
C = (F-3)/1.8, 1 degree = 0.79 rad, 1 inch water gauge = 1250 Pa.  
a. Glazing shall be defined as sunlight-transmitting fenestration, including the area of sash, curbing, or other framing elements, that enclose  
conditioned space. Glazing includes the area of sunlight-transmitting fenestration assemblies in walls bounding conditioned basements. For doors  
where the sunlight-transmitting opening is less than 50% of the door area, the glazing area is the sunlight transmitting opening area. For all other doors,  
the glazing area is the rough frame opening area for the door including the door and the frame.  
b. For residences with conditioned basements, R-2 and R-4 residences and townhouses, the following formula shall be used to determine glazing  
area:  
AF = As x FA x F  
where:  
AF = Total glazing area.  
As = Standard reference design total glazing area.  
FA = (Above-grade thermal boundary gross wall area)/(above-grade boundary wall area + 0.5 x below-grade boundary wall area).  
F = (Above-grade thermal boundary wall area)/(above-grade thermal boundary wall area + common wall area) or 0.56, whichever is greater.  
and where:  
Thermal boundary wall is any wall that separates conditioned space from unconditioned space from unconditioned space or ambient conditions.  
Above-grade thermal boundary wall is any thermal boundary wall component not in contact with soil.  
Below-grade boundary wall is any thermal boundary wall in soil contact.  
Common wall area is the area of walls shared with an adjoining dwelling unit.  
L and CFA are in the same units.  
c. Where required by the code official, testing shall be conducted by a certified independent third party. Hourly calculations as specified in the  
ASHRAE handbook of fundamentals, or the equivalent shall be used to determine the energy loads resulting from infiltration.  
d. The combined air exchange rate for infiltration and mechanical ventilation shall be determined in accordance with equation 43 of 2001  
ASHRAE handbook of fundamentals, page 26.24 and the “whole-house ventilation” provisions of 2001 ASHRAE handbook of fundamentals, page  
26.19 for intermittent mechanical ventilation.  
e. Thermal storage element shall mean a component not part of the floors, walls, or ceilings that is part of a passive solar system, and that provides  
thermal storage such as enclosed water columns, rock beds, or phase-change containers. A thermal storage element must be in the same room as  
fenestration that faces within 15 degrees (0.26 rad) of true south, or must be connected to such a room with pipes or ducts that allow the element to be  
actively charged.  
f. For a proposed design with multiple heating, cooling, or water heating systems using different fuel types, the applicable standard reference  
design system capacities and fuel types shall be weighted in accordance with their respective loads as calculated by accepted engineering practice for  
each equipment and fuel type present.  
g. For a proposed design without a proposed heating system, a heating system with the prevailing federal minimum efficiency shall be assumed for  
both the standard reference and proposed design.  
Page 79  
h. For a proposed design home without a proposed cooling system, an electric air conditioner with the prevailing federal minimum efficiency shall  
be assumed for both the standard reference design and the proposed design.  
i. For a proposed design with a non-storage-type water heater, a 40-gallon storage-type water heater with the prevailing federal minimum energy  
factor for the same fuel as the predominant heating fuel type shall be assumed. For the case of a proposed design without a proposed water heater, a 40-  
gallon storage-type water heater with the prevailing federal minimum efficiency for the same fuel as the predominant heating fuel type shall be assumed  
for both the proposed design and standard reference design.  
History: 2015 AACS.  
Page 80  
R 408.30547f Systems.  
Rule 547e. Sections N1103.2.1, N1103.2.2, and N1103.4.2 of the code are amended to read  
as follows:  
N1103.2.1. Insulation (prescriptive). All portions of the air distribution system shall be  
installed in accordance with Section M1601 and be insulated to an installed R-6 when system  
components are located within the building but outside the conditioned space, and R-8 when  
located outside to the building thermal envelope. When located within a building envelope  
assembly, at least R-8 shall be applied between the duct and that portion of the assembly farthest  
from conditioned space.  
Exception: Portions of the air distribution system within appliances or equipment.  
N1103.2.2. Sealing (mandatory). Ducts, air handlers, and filter boxes shall be sealed. Joints  
and seams shall comply with either the international mechanical code or international residential  
code, as applicable.  
Exceptions:  
1. Air-impermeable spray foam products may be applied without additional joint seals.  
2. Where a duct connection is made that is partially inaccessible, 3 screws or rivets shall be  
equally spaced on the exposed portion of the joint so as to prevent a hinge effect.  
3. Continuously welded and locking-type longitudinal joints and seams in ducts operating at  
static pressures less than 2 inches (51 mm) of water column (500 Pa) pressure classification shall  
not require additional closure systems.  
Duct tightness shall be verified by either of the following:  
1. Postconstruction test: Total leakage to the outside of a conditioned space or total leakage  
shall be less than or equal to 4 cfm (113.3 L/min) per 100 square feet (9.29 m2) of conditioned  
floor area when tested at a pressure differential of 0.1 inches (2.54 mm) w. g. (25 Pa) across the  
entire system, including the manufacturer’s air handler enclosure. All register boots shall be  
taped or otherwise sealed during the test.  
2. Rough-in test: Total leakage shall be less than or equal to 4 cfm (113.3 L/min) per 100  
square feet (9.29 m2) of conditioned floor area when tested at a pressure differential of 0.1 inches  
(2.54 mm) w.g. (25 Pa) across the system, including the manufacturer’s air handler enclosure. All  
registers shall be taped or otherwise sealed during the test. If the air handler is not installed at the  
time of the test, total leakage shall be less than or equal to 3 cfm (85 L/min) per 100 square feet  
(9.29 m2) of conditioned floor area.  
Exception: The total leakage test is not required for ducts and air handlers located entirely  
within the building thermal envelope.  
N1103.4.2. Hot water pipe insulation (prescriptive). Insulation for hot water pipe with a  
minimum thermal resistance (R-value) of R-3 shall be applied to the following:  
1. Piping larger than 3/4 inch nominal diameter.  
2. Piping serving more than 1 dwelling unit.  
3. Piping located outside the conditioned space.  
4. Piping from the water heater to a distribution manifold.  
5. Piping located under a floor slab.  
6. Buried piping.  
7. Supply and return piping in recirculation systems other than demand recirculation  
systems.  
History: 2015 AACS.  
Page 81  
R 408.30547g Energy rating index compliance alternative.  
Rule 547f. Sections N1106.1, N1106.2, N1106.3, N1106.3.1, N1106.4, N1106.5, N1106.6,  
N1106.6.1, N1106.6.2, N1106.6.3, N1106.7, N1106.7.1, N1106.7.2, N1106.7.3, and table  
N1106.4 of the code are added to read as follows:  
N1106.1 (R406.1). Scope. This section establishes criteria for compliance using an energy  
rating index (ERI) analysis.  
N1106.2 (R406.2). Mandatory requirements. Compliance with this section requires that the  
mandatory provisions identified in sections N1101.2 and N1103.4.2 be met. The building thermal  
envelope shall be greater than or equal to levels of efficiency and solar heat gain coefficient in  
table 402.1.2 or 402.1.4 of the 2009 international energy conservation code.  
Exception: Supply and return ducts not completely inside the building thermal envelope  
shall be insulated to a minimum of R-6.  
N1106.3 (R406.3). Energy rating index. The energy rating index (ERI) shall be a numerical  
integer value that is based on a linear scale constructed such that the ERI reference design has an  
index value of 100 and a residential building that uses no net purchased energy has an index value  
of 0. Each integer value on the scale shall represent a 1% change in the total energy use of the  
rated design relative to the total energy use of the ERI reference design. The ERI shall consider  
all energy used in the residential building.  
N1106.3.1 (R406.3.1). ERI reference design. The ERI reference design shall be configured  
such that it meets the minimum requirements of the 2006 international energy conservation code  
prescriptive requirements.  
The proposed residential building shall be shown to have an annual total normalized  
modified load less than or equal to the annual total loads of the ERI reference design.  
N1106.4 (R406.4). ERI-based compliance. Compliance based on an ERI analysis requires  
that the rated design be shown to have an ERI less than or equal to the appropriate value listed in  
table N1106.4 when compared to the ERI reference design.  
N1106.5 (R406.5). Verification by approved agency. Verification of compliance with  
section N1106 shall be completed by an approved third party.  
N1106.6 (R406.6). Documentation. Documentation of the software used to determine the  
ERI and the parameters for the residential building shall be in accordance with sections  
N1106.6.1 through N1106.6.3.  
N1106.6.1 (R406.6.1). Compliance software tools. Documentation verifying that the  
methods and accuracy of the compliance software tools conform to the provisions of this section  
shall be provided to the code official.  
N1106.6.2 (R406.6.2). Compliance report. Compliance software tools shall generate a  
report that documents that the ERI of the rated design complies with sections N1106.3 and  
N1106.4. The compliance documentation shall include all of the following information:  
1. Address or other identification of the residential building.  
2. An inspection checklist documenting the building component characteristics of the rated  
design. The inspection checklist shall show results for both the ERI reference design and the  
rated design, and shall document all inputs entered by the user necessary to reproduce the results.  
3. Name of individual completing the compliance report.  
4. Name and version of the compliance software tool.  
Exception: Multiple orientations. Where an otherwise identical building model is offered in  
multiple orientations, compliance for any orientation shall be permitted by documenting that the  
Page 82  
building meets the performance requirements in each of the 4 (north, east, south and west)  
cardinal orientations.  
N1106.6.3 (R406.6.3). Additional documentation. The code official may require the  
following documents:  
1. Documentation of the building component characteristics of the ERI reference design.  
2. A certification signed by the builder providing the building component characteristics of  
the rated design.  
3. Documentation of the actual values used in the software calculations for the rated design.  
N1106.7 (R406.7). Calculation software tools. Calculation software, where used, shall be in  
accordance with sections N1106.7.1 through N1106.7.3.  
N1106.7.1 (R406.7.1). Minimum capabilities. Calculation procedures used to comply with  
this section shall be software tools capable of calculating the ERI as described in section N1106.3,  
and shall include the following capabilities:  
1. Computer generation of the ERI reference design using only the input for the rated  
design.  
The calculation procedure shall not allow the user to directly modify the building component  
characteristics of the ERI reference design.  
2. Calculation of whole-building, as single zone, sizing for the heating and cooling  
equipment in the ERI reference design residence in accordance with section N1103.7.  
3. Calculations that account for the effects of indoor and outdoor temperatures and part-load  
ratios on the performance of heating, ventilating, and air-conditioning equipment based on  
climate and equipment sizing.  
4. Printed code official inspection checklist listing each of the rated design component  
characteristics determined by the analysis to provide compliance, along with their respective  
performance ratings.  
N1106.7.2 (R406.7.2). Specific approval. Performance analysis tools meeting the  
applicable sections of section N1106 shall be approved. Tools are permitted to be approved based  
on meeting a specified threshold for a jurisdiction. The code official shall approve tools for a  
specified application or limited scope.  
N1106.7 (R406.7.3). Input values. When calculations require input values not specified by  
sections N1102, N1103, N1104, and N1105, those input values shall be taken from an approved  
source.  
Table N1106.4 (R406.4)  
Maximum Energy Rating Index  
Climate Zone  
Energy Rating Index  
1
2
3
4
5
6
7
8
52  
52  
51  
54  
55  
54  
53  
53  
History: 2015 AACS.  
Page 83  
;