DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
STATE FIRE SAFETY BOARD  
NEW AND EXISTING SCHOOL, COLLEGE, AND UNIVERSITY FIRE SAFETY  
(By authority conferred on the bureau of fire services by section 3c of 1941 PA 207, MCL  
29.3c, and Executive Reorganization Order Nos. 1997-2, 1998-2 and 2003-1, MCL 29.451,  
29.461, and 445.2011)  
PART 1. GENERAL PROVISIONS  
R 29.1901 Applicability.  
Rule 1. These rules apply to all new and existing school, college, and university facilities  
used for instructional purposes as defined by these rules.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1902 Life safety code; adoption by reference.  
Rule 2. (1) The provisions of chapters 1 to 10, 11, 12, 13, 14, 15, 38, 39, and 43 of the  
national fire protection association pamphlet no. 101, 2012 edition, entitled "Life Safety  
Code," referred to in these rules as “code”, are adopted by reference as part of these rules.  
(2) Copies of the adopted provisions in subrules (1) and (3) of this rule are available for  
inspection and distribution from the National Fire Protection Association, 1 Batterymarch  
Park, P.O. Box 9101, Quincy, Massachusetts 02269-9101, telephone number 1-800-344-  
3555 or as otherwise specified in subrule (3) of this rule. The cost of the adopted provisions  
of the "Life Safety Code" as of the time of adoption of these rules is $93.00. The cost of  
the adopted provisions in subrule (3) of this rule are specified in subrule (3) of this rule.  
Copies of the adopted provisions are available for inspection at the offices of the  
Department of Licensing and Regulatory Affairs, Bureau of Fire Services, 3101  
Technology Boulevard, Suite H, Lansing, MI 48910, or as specified in this rule. Copies of  
the adopted provisions may be purchased from the bureau of fire services at cost from any  
national source identified in chapter 2 of the code as amended in subrules (1) and (3) of  
this rule plus $30.00 for shipping and handling as of the time of the adoption of these rules.  
(3) Chapter 2 of the code is amended to read as follows:  
2.1 General. The documents or portions thereof listed in this chapter are referenced within  
this code and shall be considered part of the requirements of this document. The cost of  
each standard at the time of the adoption of these rules is indicated after the title.  
National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471  
NFPA 10, Standard for Portable Fire Extinguishers, 2010 edition. $44.50/each  
NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 2010 edition.  
$44.50/each  
Page 1  
NFPA 12, Standard on Carbon Dioxide Extinguishing Systems, 2011 edition. $44.50/each  
NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems, 2009 edition.  
$44.50/each  
NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 edition. $85.50/each  
NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family  
Dwellings and Manufactured Homes, 2010 edition. $44.50/each  
NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies  
up to and Including Four Stories in Height, 2010 edition. $40.50/each  
NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2010 edition.  
$40.50/each  
NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 edition.  
$44.50/each  
NFPA 16, Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray  
Systems, 2011 edition. $40.50/each  
NFPA 17, Standard for Dry Chemical Extinguishing Systems, 2009 edition. $40.50/each  
NFPA 17A, Standard for Wet Chemical Extinguishing Systems, 2009 edition. $35.00/each  
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire  
Protection Systems, 2011 edition. $52.50/each  
NFPA 30, Flammable and Combustible Liquids Code, 2012 edition. References to this  
standard mean R 29.5401 to R29. 5419, promulgated by the Michigan department of  
licensing and regulatory affairs, bureau of fire services.  
NFPA 30B, Code for the Manufacture and Storage of Aerosol Products, 2011 edition.  
$44.50/each  
NFPA 31, Standard for the Installation of Oil-Burning Equipment, 2011 edition.  
$44.50/each  
NFPA 40, Standard for the Storage and Handling of Cellulose Nitrate Film, 2011 edition.  
$35.00/each  
NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.  
$40.50/each  
NFPA 54, National Fuel Gas Code, 2012 edition. $52.50/each  
NFPA 58, Liquefied Petroleum Gas Code, 2011 edition. References to this code mean the  
administrative rules relating to storage and handling of liquefied petroleum gases, R  
29.6001 to R 29.6097, promulgated by the Michigan department of licensing and  
regulatory affairs, bureau of fire services.  
NFPA 70, National Electrical Code, 2011 edition. References to this code mean the  
Michigan electrical code, R 408.30801 to R 408.30880, promulgated by the Michigan  
department of licensing and regulatory affairs, bureau of construction codes.  
NFPA 72, National Fire Alarm Code, 2010 edition. $85.50/each  
NFPA 80, Standard for Fire Doors and Fire Windows, 2010 edition. $44.50/each  
NFPA 82, Standard on Incinerators and Waste and Linen Handling Systems and  
Equipment, 2009 edition. $40.50/each  
NFPA 88A, Standard for Parking Structures, 2011 edition. $35.00/each  
NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems,  
2012 edition. $40.50/each  
NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning  
Systems, 2012 edition. $35.00/each  
Page 2  
NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and  
Noncombustible Particulate Solids, 2010 edition. $35.00/each  
NFPA 92, Standard for Smoke Control Systems, 2012 edition. $40.50/each  
NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking  
Operations, 2011 edition. $40.50/each  
NFPA 99, Standard for Health Care Facilities, 2012 edition. $64.00/each  
NFPA 101A, Guide on Alternative Approaches to Life Safety, 2010 edition. $44.50/each  
NFPA 105, Standard for the Installation of Smoke Door Assemblies, 2010 edition.  
$35.00/each  
NFPA 110, Standard for Emergency and Standby Power Systems, 2010 edition.  
$39.00/each  
NFPA 111, Standard on Stored Electrical Energy Emergency and Standby Power Systems,  
2010 edition. $40.50/each  
NFPA 160, Standard for the Use of Flame Effects Before an Audience, 2011 edition.  
$40.50/each  
NFPA 170, Standard for Fire Safety and Emergency Symbols, 2009 edition. $44.50/each  
NFPA 204, Standard for Smoke and Heat Venting, 2012 edition. $44.50/each  
NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances,  
2010 edition. $44.50/each  
NFPA 220, Standard on Types of Building Construction, 2012 edition. $35.00/each  
NFPA 221, Standard for High Challenge Fire Walls, Fire Walls, and Fire Barrier Walls,  
2010 edition. $40.50/each  
NFPA 241, Standard for Safeguarding Construction, Alteration, and Demolition  
Operations, 2009 edition. $40.50/each  
NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and  
Materials, 2006 edition. $40.50/each  
NFPA 252, Standard Methods of Fire Tests of Door Assemblies, 2008 edition. $35.00/each  
NFPA 253, Standard Method of Test for Critical Radiant Flux of Floor Covering Systems  
Using a Radiant Heat Energy Source, 2011 edition. $35.00/each  
NFPA 257, Standard on Fire Test for Window and Glass Block Assemblies, 2007 edition.  
$35.00/each  
NFPA 259, Standard Test Method for Potential Heat of Building Materials, 2008  
edition.$35.00/each  
NFPA 260, Standard Methods of Tests and Classification System for Cigarette Ignition  
Resistance of Components of Upholstered Furniture, 2009 edition. $35.00/each  
NFPA 261, Standard Method of Test for Determining Resistance of Mock-Up Upholstered  
Furniture Material Assemblies to Ignition by Smoldering Cigarettes, 2009 edition.  
$35.00/each  
NFPA 265, Standard Methods of Fire Tests for Evaluating Room Fire Growth Contribution  
of Textile Coverings on Full Height Panels and Walls, 2011 edition. $40.50/each  
NFPA 271, Standard Method of Test for Heat and Visible Smoke Release Rates for  
Materials and Products Using an Oxygen Consumption Calorimeter, 2009 edition.  
$40.50/each  
NFPA 286, Standard Methods of Fire Tests for Evaluating Contribution of Wall and  
Ceiling Interior Finish to Room Fire Growth, 2011 edition. $40.50/each  
Page 3  
NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance-Rated Floor Systems, 2007 edition. $35.00/each  
NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, 2009 edition.  
$35.00/each  
NFPA 415, Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading  
Walkways, 2008 edition. $35.00/each  
NFPA 418, Standard for Heliports, 2011 edition. $35.00/each  
NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films,  
2010 edition. $35.00/each  
NFPA 703, Standard for Fire Retardant-Treated Wood and Fire-Retardant Coatings for  
Building Materials, 2012 edition. $35.00/each  
NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning  
Equipment, 2012 edition. $44.50/each  
NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 edition. $44.50/each  
NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition. $64.00/each  
NFPA 1124, Code for the Manufacture, Transportation, Storage, and Retail Sales of  
Fireworks and Pyrotechnic Articles, 2006 edition. $44.50/each  
NFPA 1126, Standard for the Use of Pyrotechnics Before a Proximate Audience, 2011  
edition. $35.00/each  
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems, 2012 edition.  
$52.50/each  
2.3 Other Publications.  
American Concrete Institute, P. O. Box 9094, Farmington Hills, MI 48333  
ACI 216.1/TMS 0216.1, Standard Method for Determining Fire Resistance of Concrete  
and Masonry Construction Assemblies, 2008. $54.50/each  
2.3.2 ANSI Publications.  
American National Standards Institute, Inc., 25 West 43rd Street, 4th floor, New York, NY  
10036.  
ICC/ANSI A117.1, American National Standard for Accessible and Usable Buildings and  
BHMA/ANSI A156.19, American National Standard for Power Assist and Low Energy  
Power Operated Doors, 2007. www.ansi.org $36.00/each  
2.3.3 ASCE Publications. American Society of Civil Engineers, 1801 Alexander Bell  
ASCE/SFPE 29, Standard Calculation Methods for Structural Fire Protection, 2008.  
$69.00/each  
Three Park Avenue, New York, NY 10016-5990  
2.3.5 ASSE Publications. American Society of Safety Engineers, 1800 East Oakton Street,  
Des Plaines, IL 60018. www.asse.org  
ANSI/ASSE A1264.1, Safety Requirements for Workplace Floor and Wall Openings,  
Stairs and Railing Systems, 2007. $69.00/each  
Page 4  
Barr Harbor Drive, West Conshohocken, PA 19428-2959  
ASTM C 1629/C 1629M, Standard Classification for Abuse-Resistant Nondecorated  
Interior Gypsum Pan Products and Fiber-Reinforced Cement Panels, 2006. $49.20/each  
ASTM D 1929, Standard Test Method for Determining Ignition Temperatures of Plastic,  
(2001 e1). $49.20/each  
ASTM D 2859, Standard Test Method for Ignition Characteristics of Finished Textile Floor  
Covering Materials, 2006. $43.20/each  
ASTM D 2898, Standard Test Methods for Accelerated Weathering of Fire-Retardant-  
Treated Wood for Fire Testing, 2010. $36.00/each  
ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building  
Materials, 2010. $70.80/each  
ASTM E 108, Standard Test Methods for Fire Tests of Roof Coverings, 2010a.  
$56.40/each  
ASTM E 119, Standard Test Methods for Fire Tests of Building Construction and  
Materials, 2010b. $70.80/each  
ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical Tube Furnace  
at 750°C, 2009b. $56.40/each  
ASTM E 648, Standard Test Method for Critical Radiant Flux of Floor Covering Systems  
Using a Radiant Heat Energy Source, 2010. $56.40/each  
ASTM E 814, Standard Test Method for Fire Tests of Through Penetration Fire Stops,  
2010. $56.40/each  
ASTM E 1352, Standard Test Method for Cigarette Ignition Resistance of Mock-Up  
Upholstered Furniture Assemblies, 2008a. $47.00/each  
ASTM E 1353, Standard Test Methods for Cigarette Ignition Resistance of Components  
of Upholstered Furniture 2008a(e1). $47.00/each  
ASTM E 1354, Standard Test Method for Heat and Visible Smoke Release Rates for  
Materials and Products Using an Oxygen Consumption Calorimeter, 2009. $56.40/each  
ASTM E 1537, Standard Test Method for Fire Testing of Upholstered Furniture, 2007.  
$70.80/each  
ASTM E 1590, Standard Test Method for Fire Testing of Mattresses, 2007. $70.80/each  
ASTM E 1591, Standard Guide for Obtaining Data for Deterministic Fire Models, 2007.  
$47.00/each  
ASTM E 1966, Standard Test Method for Fire-Resistive Joint Systems, 2007. $47.00/each  
ASTM E 2072, Standard Specification for Photoluminescent (Phosphorescent) Safety  
Markings, 2010. $36.00/each  
ASTM E 2074, Standard Test Method for Fire Tests of Door Assemblies, Including  
Positive Pressure Testing of Side-Hinged and Pivoted Swinging Door Assemblies, 2000.  
$56.40/each  
ASTM E 2307, Standard Test Method for Determining Fire Resistance of Perimeter Fire  
Barrier Systems Using Intermediate-Scale, Multi-Story Test Apparatus, 2010.  
$47.00/each  
ASTM E 2404, Standard Practice for Specimen Preparation and Mounting of Textile,  
Paper, or Vinyl Wall or Ceiling Coverings to Assess Surface Burning Characteristics, 2008.  
$43.20/each  
Page 5  
ASTM E 2573, Standard Practice for Specimen Preparation and Mounting of Site-  
Fabricated Stretch Systems to Assess Surface Burning Characteristics, 2007a.  
$43.20/each  
ASTM E 2599, Standard Practice for Specimen Preparation and Mounting of Reflective  
Insulation Materials and Radiant Barrier Materials for Building Applications to Assess  
Surface Burning Characteristics, 2009. $43.20/each  
ASTM E 2652, Standard Test Method for Behavior of Materials in a Tube Furnace with a  
Cone-Shaped Airflow Stabilizer, at 750 Degrees C, 2009a. $56.40/each  
ASTM F 851, Standard Test Method for Self-Rising Seat Mechanisms, 1987 (2005).  
$36.00/each  
ASTM F 1577, Standard Test Methods for Detention Locks for Swinging Doors, 2005.  
$70.80/each  
ASTM G 155, Standard Practice for Operating Xenon Arc Light Apparatus for Exposure  
of Non-Metallic Materials, 2005a. $47.00/each  
2.3.7 FMGR Publication.  
FM Global Research, FM Global, 1301 Atwood Avenue, P.O. Box 7500, Johnston, RI  
02919.  
ANSI/FM 4880, American National Standard for Evaluating Insulated Wall or Wall and  
Roof/Ceiling Assemblies, Plastic Interior Finish Materials, Plastic Exterior Building  
Panels, Wall/Ceiling Coating Systems, Interior or Exterior Finish Systems, 2007. Free  
FM Approval Standard 6921, Containers for Combustible Waste, 2004. Free  
UL 300, Standard for Fire Testing of Fire Extinguishing Systems for Protection of  
Commercial Cooking Equipment, 2005. $502.00/each at www.comm-2000.com  
2.3.8 NEMA Publications. National Electrical Manufacturers Association, 1300 North  
NEMA Sb 30, Fire Service Annunciator and Interface, 2005. $69.00/each  
per UL website. (All revisions included in purchase of standard) Underwriters Laboratories  
Inc., 333 Pfingsten Road, Northbrook, IL 60062  
ANSI/UL 9, Standard for Fire Tests of Window Assemblies, 2009. $631.00/each  
ANSI/UL 10B, Standard for Fire Tests of Door Assemblies, 2008, revised 2009.  
$631.00/each  
ANSI/UL 10C, Standard for Positive Pressure Fire Tests of Door Assemblies, 2009.  
$631.00/each  
ANSI/UL 263, Standard for Fire Tests of Building Construction and Materials, 2007.  
$631.00/each  
UL 294, Standard for Access Control System Unites, 1999, revised 2010. $502.00/each  
UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, 2006.  
$275.00/each  
ANSI/UL 305, Standard for Safety Panic Hardware, 1997. $502.00/each  
ANSI/UL 555, Standard for Fire Dampers, 2006, Revised 2002. $998.00/each  
ANSI/UL 555S, Standard for Smoke Dampers, 2006, Revised 2010. $502.00/each  
ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials,  
2009, revised 2010. $631.00/each  
ANSI/UL 790, Test Methods for Fire Tests of Roof Coverings, 2004, revised 2008.  
$502.00/each  
Page 6  
ANSI/UL 924, Standard for Emergency Lighting and Power Equipment, 2006, Revised  
2009. $998.00/each  
ANSI/UL 1040, Standard for Fire Test of Insulated Wall Construction, 1996, revised 2007.  
$502.00/each  
ANSI/UL 1315, Standard for Safety for Metal Waste Paper Containers, 2007.  
$502.00/each  
ANSI/UL 1479, Standard for Fire Tests of Through-Penetration Firestops, 2003, revised  
2010. $502.00/each  
ANSI/UL 1715, Standard for Fire Test of Interior Finish Material, 1997, revised 2008.  
$897.00/each  
ANSI/UL 1784, Standard for Air Leakage tests for Door Assemblies, 2001, revised 2009.  
$502.00/each  
UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes, 2006.  
$998.00 each  
UL 1994, Standard for Luminous Egress Path Marking Systems, 2004, revised 2010.  
$998.00/each  
ANSI/UL 2079, Standard for Tests for Fire Resistance of Building Joint Systems, 2004,  
revised 2008. $502.00/each  
U.S. Government Printing Office, Washington, DC 20402.  
Title 16, Code of Federal Regulations, Part 1500 and Part 1507. Free  
Title 16, Code of Federal Regulations, Part 1632, "Standard for the Flammability of  
Mattresses and Mattress Pads (FF-4-72)." Free  
2.3.11 Other Publication.  
Merriam-Webster's Collegiate Dictionary, 11th edition, Merriam-Webster, Inc.,  
2.4 References for Extracts in Mandatory Sections.  
NFPA 1, Uniform Fire Code, 2012 edition. $85.50/each  
NFPA 72, National Fire Alarm Code, 2010 edition. $85.50/each  
NFPA 80, Standard for Fire Doors and Fire Windows, 2010 edition. $40.50/each  
NFPA 88A, Standard for Parking Structures, 2011 edition. $35.00/each  
NFPA 288, Standard Methods of Fire Tests of Floor Fire Door Assemblies Installed  
Horizontally in Fire Resistance-Rated Floor Systems, 2009 edition. $35.00/each  
NFPA 301, Code for Safety to Life from Fire on Merchant Vessels, 2008 edition.  
$44.5.00/each  
NFPA 415, Standard on Airport Terminal Buildings, Fueling Ramp Drainage, and Loading  
Walkways, 2008 edition. $35.00/each  
NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition. $64.00/each  
NFPA 921, Guide for Fire and Explosion Investigations, 2011 edition. $85.50/each  
ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, 2010.  
(4) Rules promulgated by the department of licensing and regulatory affairs, bureau of  
fire services, are available for inspection from the Michigan government website,  
available from the Michigan department of licensing and regulatory affairs, bureau of fire  
services by calling (517) 241-8847.  
Page 7  
(5) Rules pertaining to the Michigan elevator code, R 408.7001 to R 408.8695; the  
Michigan mechanical code, R 408.30901 to R408.30998; the Michigan building code, R  
408.30401 to R 408.30499a; the Michigan electrical code, R 408.30801 to R 408.30880;  
the Michigan plumbing code, R 408.30701 to R 408.30796; and the Michigan rehabilitation  
code, R 408.30551 to R 408.30577, are available for inspection and distribution at cost at  
the Department of Licensing and Regulatory Affairs, Bureau of Construction Codes, 611  
W. Ottawa, Lansing, MI 48933. Copies of these rules are available at no cost from the  
administrative code”.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1903 Definitions.  
Rule 3. As used in these rules:  
(a) "Act" means 1941 PA 207, MCL 29.1 to 29.34  
(b) "Authority having jurisdiction" means the director of the department of licensing and  
regulatory affairs, an employee of the department of licensing and regulatory affairs  
appointed by the director to implement the act, or an employee of a city, village, or  
township delegated authority to enforce the code under section 2b of the act.  
(c) "Code" means national fire protection association pamphlet no. 101, 2012 edition,  
entitled "Life Safety Code."  
(d) "College" or "university" means a junior college, community college, college, or  
university that is duly authorized to grant degrees by 1 of the following:  
(i) Article VIII of the Michigan Constitution of 1963.  
(ii) The Michigan legislature.  
(iii) Action by the state board of education.  
(e) "Cosmetic remodeling" means surface changes solely to the wall, floor, and ceiling  
that do not decrease the fire rating of the wall, floor, or ceiling, including the replacement  
of windows and doors.  
(f) “Instructional facility” means a building or part of a building that is used for mandatory  
instructional purposes, is occupied by 6 or more students and used 4 or more hours per day  
or more than 12 hours per week, and is owned or leased by, or under the control of a college  
or university as defined in these rules.  
(g) "Maintenance" means repair required to keep a building and its component parts in an  
operative condition at all times, including the replacement of its component parts when,  
for any reason, the component parts are no longer dependable. "Maintenance" does not  
include renovation.  
(h) "Open court" means a court that is open and unobstructed on at least 1 side by a  
minimum of 20 feet in width and 13 feet 6 inches in height. The opening shall lead to a  
public way.  
(i) "Penthouse" means an enclosed, unoccupied structure above the roof of a building,  
other than a tank, tower, spire, dome cupola, or bulkhead. The aggregate area shall not  
exceed 1/3 of the supporting roof. A penthouse shall be considered as part of the story  
below.  
(j) "Room" means a space or area bounded by any obstruction to egress that, at any time,  
encloses more than 80% of the perimeter of the space or area. An opening that is less than  
Page 8  
3 feet clear wide and less than 6 feet 8 inches high shall not be considered in computing  
the unobstructed perimeter. A vestibule that is used for weather protection is not a room  
for the purposes of these rules.  
(k) "School" means a building or part of a building that is owned or leased by, or under  
the control of, a public or private school or school system for the purpose of instruction as  
required by section 1561 of 1976 PA451, MCL 380.1561 that is occupied by 6 or more  
students, and is used 4 or more hours per day or more than 12 hours per week. School does  
not mean a college building or university building.  
(l) “Stop work order” means a notice from the authority having jurisdiction to  
immediately cease work being done because the work being performed is contrary to the  
rules or is being performed in a dangerous or unsafe manner. Any person who continues to  
work after being served with a stop work order, except the work that the person is directed  
to perform to remove a violation or unsafe condition, to provide for security of the building  
or to provide for weather protection of the building, shall be subject to penalties described  
by the act.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1904 Plans and specifications.  
Rule 4. (1) A school, college, university, or designated representative shall submit plans  
and specifications to the bureau of fire services for all projects that involve construction,  
remodeling, renovation, modification, reconstruction, or an addition.  
(2) A school, college, or university need not submit plans and specifications to the bureau  
of fire services for routine maintenance functions or cosmetic remodeling; however, a  
school, college, or university shall ensure that all work is in compliance with these rules.  
(3) Plans and specifications for work that involves the practice of architecture or  
engineering, as defined by the provisions of article 20 of the occupational code, 1980 PA  
299, MCL 339.2001 to 339.2014, shall bear the seal of an architect or professional engineer  
who is licensed pursuant to the occupational code. If a public works project consisting of  
construction, renovation, modification, reconstruction, or an addition is estimated to cost  
less than $15,000.00, it is not necessary to employ a registered architect or engineer, but  
the plans for the building shall be submitted to the bureau of fire services for approval  
pursuant to section 5a of 1937 PA 306, MCL 388.855a.  
(4) Plans and specifications shall contain all of the following information, as applicable:  
(a) A complete floor plan and layout of the building drawn accurately to scale.  
(b) The use of each room.  
(c) The dimensions of each room.  
(d) The size, location, direction of swing, and fire rating of each door and frame assembly.  
(e) The size and location of windows.  
(f) The wall construction, including the fire-resistance rating.  
(g) The type of construction as identified in national fire protection association pamphlet  
no. 220, entitled "Standard on Types of Building Construction," as adopted in these rules.  
(h) The number of stories, including basement and attic areas.  
(i) The interior finish classification.  
(j) The location of fuel-fired equipment.  
(k) The type of furnace and water heater.  
Page 9  
(l) Air-handling systems.  
(m) Fire detection and alarm systems plans and specifications in compliance with the  
provisions of the act.  
(n) Sprinkler or other suppression system plans and specifications in compliance with the  
provisions of the act.  
(o) The type, size, and location of fire extinguishers.  
(p) Other pertinent information that is required to determine compliance with these rules.  
(5) A firm certified in compliance with section 26 of 1941 PA 207, MCL 29.26, shall  
submit fire alarm/detection system and fire suppression system plans to the bureau of fire  
services pursuant to the act.  
(6) Plan approval that is given before the effective date of these rules shall terminate 6  
months after the effective date of these rules if construction has not started. However, upon  
written request, the bureau of fire services may grant an approval extension in a specific  
instance.  
(7) Projects that involve construction, remodeling, or an addition, including fire alarm or  
fire detection systems and fire suppression systems, discovered to be in violation of the  
requirement of this rule shall be subject to the issuance of a stop work order by the authority  
having jurisdiction. Inspections shall not be conducted and approval shall not be granted  
by the authority having jurisdiction until the provisions of this rule are met.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1905 Inspection during construction; inspection of existing facilities; approval  
for occupancy.  
Rule 5. (1) During construction, renovation, modification, reconstruction, addition, or  
remodeling, the architect, professional engineer, or owner's representative shall notify the  
bureau of fire services when the building is ready for inspection under both of the following  
conditions:  
(a) When the building is framed and mechanical systems are substantially complete, but  
before concealment.  
(b) Upon completion of construction.  
(2) A person shall not occupy a newly constructed facility or a facility that is being  
remodeled or added to, in whole or in part, without the approval of the bureau of fire  
services.  
(3) The bureau may approve for continuous use an existing school, college, or university  
instructional facility or building established prior to the effective date of these rules if it  
conforms to, or is made to conform to, the provisions of these rules to the extent that, in  
the opinion of the authority having jurisdiction, reasonable life safety against the hazards  
of fire, explosion, and panic is provided and maintained.  
(4) While conducting project inspections pursuant to these rules or an investigation in  
reference to a fire hazard or life safety complaint pursuant to the act, in an existing school,  
college, or university instructional facility or building, the bureau of fire services may  
request to review documents related to the continued operation and maintenance of the  
following systems or items pursuant to section 4.5.8 and the applicable sections of chapter  
4, 7, and 9 of the code.  
(a) Fire alarm system.  
Page 10  
(b) Sprinkler system.  
(c) Hood suppression systems.  
(d) Emergency lighting.  
(e) Fire extinguishers.  
(f) Required emergency generators.  
(g) Egress signage.  
(h) Door locking systems.  
(i) Record of fire and emergency drills as required by the act.  
(j) Emergency plans.  
(k) Any other life safety system.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1906 Projects affecting outside configuration of building; site plan and  
specifications; bureau of fire services or local fire authority specifications; fire safety  
measures during construction.  
Rule 6. (1) For projects involving construction, addition, renovation, modification,  
reconstruction, or remodeling that affect the outside configuration of a building, and as part  
of the building plans and specifications otherwise required by these rules, before the  
construction begins, the owner or the owner's authorized representative shall provide the  
bureau of fire services and the local fire authority with a site plan and specifications that  
detail all of the following information, as applicable:  
(a) The available water supply.  
(b) Hydrant locations.  
(c) Vehicle access routes.  
(d) Fire lanes.  
(2) The authority having jurisdiction or the local fire authority may specify any of the  
following:  
(a) The size of the water mains that supply they hydrants.  
(b) The location of the hydrants.  
(c) The location and dimensions of fire department vehicle access routes.  
(d) The posting of fire lanes.  
(3) As soon as possible during construction, the school, college, university, or designated  
representative shall ensure that appropriate fire safety measures are taken, including the  
provision of fire extinguishers and fire suppression systems, and the establishment of  
access routes to the building that can be traveled by fire department vehicles.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1907 Electrical equipment; inspections; certificate.  
Rule 7. (1) The school, college, university, or designated representative shall ensure that  
the electrical wiring and equipment, including an emergency supply if installed, complies  
with the applicable provisions of the Michigan electrical code, R 408.30801 to R  
408.30880. Copies of the rules are available as specified in R 29.1902.  
Page 11  
(2) An electrical inspection authority acceptable to the bureau of fire services shall  
perform the electrical inspection. The electrical inspection authority shall issue a final  
certificate of compliance covering the installation. The school, college, university, or  
designated representative shall provide a copy of the certificate to the bureau of fire  
services.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1907a Fire reporting.  
Rule 7a. (1) Upon discovery of any unwanted fire, regardless of magnitude, the person  
in control of the building shall immediately notify the local fire department.  
(2) Whenever an unwanted fire occurs, or upon discovery of an unwanted fire, even  
though it has been extinguished, the person in control of the building shall immediately  
notify the local fire department of the existence of the fire, circumstances, and the location  
of the fire. This subrule does not prohibit the facility from using all diligence necessary to  
extinguish the fire prior to the arrival of the fire department.  
(3) The school, college, university, or designated representative shall notify the bureau of  
fire services of all details of the fire not later than the end of the next business day following  
the incident.  
History: 2016 AACS.  
R 29.1908 Universal amendments.  
Rule 8. Sections 4.6.10.1, 4.7.4, 4.8.2.2, 6.2.1.2, 7.2.1.12, 8.3.5, 8.3.5.5.1, 8.3.6.1, 8.4.2,  
8.4.5.1, 8.5.7.1, 8.6.10.2.1, 8.7.3.1, 9.1.1, 9.4.2.1, 9.4.2.2, 9.6.3.5.5, 12.3.2.1.2, 12.7.6.1,  
13.3.2.1.2, 13.7.6.1, and 43.1.2.1 of the code adopted by reference in R 29.1902 are  
amended, section 8.6.10.2.1.1 is added, and sections 7.2.1.12.1, 7.2.1.12.2, 7.3.3.2, 9.1.2,  
9.4.3.1, 9.4.3.2, 12.2.2.2.5, 12.2.10.3, 12.2.11.2, 12.7.1.3, 12.7.6.2, 12.7.7.2, 12.7.9.3.1,  
12.7.9.3.2, 12.7.9.3.3, 13.2.2.2.5, 13.2.10.3, 13.2.11.2, 13.7.1.3, 13.7.6.2, 13.7.7.2,  
13.7.9.3.1, 13.7.9.3.2, 13.7.9.3.3, and 43.1.4.5 of the code are deleted, as follows:  
4.6.10.1. Buildings or portions of buildings shall be permitted to be occupied during  
construction, repair, alterations, or additions only where all means of egress and required  
fire protection features in the building and on-site are in place and continuously maintained  
for the portion occupied and if the occupied portion is separated from the part under  
construction by a wall that has a 1-hour-fire-resistance rating. The temporary 1-hour-rated  
wall that is used for separation may be constructed of combustible material. Instead of  
having all means of egress and fire protection features in place, the school, college,  
university, or designated representative may take other measures that would provide  
equivalent safety if approved by the bureau of fire services.  
4.7.4. Drills shall be held at various times under varying conditions to simulate the unusual  
conditions that can occur in an actual emergency.  
4.8.2.2. Upon request from the bureau of fire services, the school, college, university, or  
designated representative shall submit the required emergency plans for review.  
6.2.1.2. Hazard of contents shall be classified by the registered design professional (RDP)  
or owner and upon request shall be submitted to the authority having jurisdiction for review  
Page 12  
and approval on the basis of character of the contents and the processes of operations  
conducted in the building or structure.  
7.2.1.12. Where permanently mounted folding or movable partitions divide a room into  
smaller spaces, a swinging door leaf or open doorway shall be provided as an exit access  
from each space.  
7.2.1.12.1. Deleted.  
7.2.1.12.2. Deleted.  
7.3.3.2. Deleted.  
8.3.5. The provisions of section 8.3.5 shall govern the materials and methods of  
construction used to protect through-penetration and membrane penetrations in fire walls,  
fire barrier walls, and fire resistance-rated horizontal assemblies. The provisions of section  
8.3.5 shall not apply to existing material and methods of construction used to protect  
existing through-penetrations and existing membrane penetrations in fire walls, fire barrier  
walls, or fire resistance-rated horizontal assemblies, unless otherwise required by chapters  
11 to 43.  
8.3.5.5.1. Where piping penetrates a fire resistance-rated wall or floor assembly,  
combustible piping shall not connect to noncombustible piping within 35 inches (915  
millimeters) of the firestop system or device with the demonstration that the transition will  
not reduce the fire resistance rating, except in the case of existing installations.  
8.3.6.1. The provisions of section 8.3.6 shall govern the materials and methods of  
construction used to protect joints in between and at the perimeter of fire barriers or, where  
fire barriers meet other fire barriers, the floor or roof deck above, or the outside walls. The  
provisions of section 8.3.6 shall not apply to existing materials and methods of construction  
used to protect existing joints in fire barriers, unless otherwise required by chapters 11 to  
43.  
8.4.2. The following shall apply to smoke partitions:  
(1) They shall extend from the floor to the underside of the floor or roof deck above,  
through any concealed spaces, such as those above suspended ceilings, and through  
interstitial structural and mechanical spaces.  
(2) They shall be permitted to extend from the floor to the underside of a monolithic or  
suspended ceiling where the following conditions are met:  
(a) The ceiling system forms a continuous membrane.  
(b) A smoke-tight joint is provided between the top of the smoke partition and the bottom  
of the suspended ceiling.  
(c) Where the space above the ceiling is used as a plenum, air transfer openings in smoke  
partitions into the plenum shall be provided with approved smoke dampers designed and  
tested pursuant to the requirements of ANSI/UL 555S, standard for smoke dampers, to  
limit the transfer of smoke.  
(3) Smoke partitions enclosing hazardous areas shall be permitted to terminate at the  
underside of a monolithic or suspended ceiling where the following conditions are met:  
(a) The ceiling system forms a continuous membrane.  
(b) A smoke-tight joint is provided between the top of the smoke partition and the bottom  
of the suspended ceiling.  
(c) Where the space above the ceiling is used as a plenum, air transfer openings in smoke  
partitions into the plenum shall be provided with approved smoke dampers designed and  
Page 13  
tested pursuant to the requirements of ANSI/UL 555S, standard for smoke dampers, to  
limit the transfer of smoke.  
8.4.5.1. The provisions of section 8.4.5 shall govern the materials and methods of  
construction used to protect joints in between and at the perimeter of smoke partitions or,  
where smoke partitions meet other smoke partitions, the floor or roof deck above or, the  
outside walls. The provisions of section 8.4.5 shall not apply to existing materials and  
methods of construction used to protect existing joints in smoke partitions, unless otherwise  
required by chapters 11 to 43.  
8.5.7.1. The provisions of section 8.5.7 shall govern the materials and methods of  
construction used to protect joints in between and at the perimeter of smoke barriers, or  
where barriers meet other smoke barriers, the floor or roof deck above, or the outside walls.  
8.6.10.2.1. Unless otherwise provided in section 8.6.10.2.1.1, the aggregate area of a  
mezzanine located within a room, other than those located in a special-purpose industrial  
occupancies, shall not exceed one-third the open area of the room in which the mezzanines  
are located. Enclosed spaces shall not be included in a determination of the size of the room  
in which the mezzanine is located.  
8.6.10.2.1.1. The aggregate area of mezzanines in buildings and structures of type I of type  
II construction shall not exceed one-half of the floor area of the room in buildings and  
structures equipped throughout with an approved automatic sprinkler system pursuant to  
section 9.7 and an approved emergency voice or emergency alarm communication system  
pursuant to NFPA 72.  
8.7.3.1. The school, college, university, or designated representative shall store and handle  
flammable and combustible liquids in compliance with the storage and handling of  
flammable and combustible liquids, R 29.5101 to R 29.5516.  
9.1.1. The school, college, university, or designated representative shall ensure the  
equipment which utilizes gas and related gas piping is installed in compliance with the  
provisions of NFPA 54, national fuel gas code, NFPA 58, liquefied petroleum gas code, or  
rules promulgated under the act, as applicable.  
9.1.2. Deleted.  
9.4.2.1. The school, college, university, or designated representative shall ensure that new  
elevators, escalators, dumbwaiters, and moving walks are installed pursuant to the  
Michigan elevator rules, R 408.7001 to R 408.8695.  
9.4.2.2. The school, college, university, or designated representative shall ensure that  
existing elevators, escalators, dumbwaiters, and moving walks are in compliance with the  
Michigan elevator rules, R 408.7001 to R 408.8695.  
9.4.3.1. Deleted.  
9.4.3.2. Deleted.  
9.6.3.5.5. Visible signals shall not be required in any of the following areas:  
(1) Exit stair enclosures.  
(2) Offices less than 200 square feet.  
(3) Closets and coat rooms.  
(4) Electrical closets.  
(5) Mechanical pipe chases.  
(6) Crawl spaces.  
(7) Small bathrooms in classrooms.  
(8) Janitor closets.  
Page 14  
(9) Storage rooms less than 200 square feet.  
(10) Unoccupied spaces.  
12.2.2.2.5. Deleted.  
12.2.10.3. Deleted.  
12.2.11.2. Deleted.  
12.3.2.1.2. Rooms or spaces for the storage, processing, or use of materials specified in  
section 12.3.2.1.2(1) to (3) shall be protected pursuant to the following:  
(1) Separation from the remainder of the building by fire barriers having a minimum 1-  
hour fire resistance rating or protection of such rooms by automatic extinguishing systems  
as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless otherwise permitted by either of the following:  
(i) The requirement of section 12.3.2.1.2(1)(a) shall not apply to rooms enclosing  
furnaces, heating and air-handling equipment, or compressor equipment with a total  
aggregate input rating less than 200,000 BTU (211MJ), provided that such rooms are not  
used for storage.  
(ii) The requirement of section 12.3.2.1.2(1)(a) shall not apply to attic locations of the  
rooms addressed in section 12.3.2.1.2(1)(a)(i), provided that such rooms comply with the  
draftstopping requirements of section 8.6.10.  
(b) Rooms or spaces larger than 100 square feet (4.6 square meters) and used for the  
storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(2) Separation from the remainder of the building by fire barriers having a minimum 1-  
hour fire resistance rating and protection of such rooms by automatic extinguishing systems  
as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including woodworking and painting areas.  
(c) Rooms or spaces used for the processing or use of combustible supplies deemed  
hazardous by the authority having jurisdiction.  
(d) Rooms or spaces used for processing or use of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(3) Where automatic extinguishing is used to meet the requirements of section  
12.3.2.1.2(1) or (2), the protection shall be permitted pursuant to section 9.7.1.2.  
12.7.1.3. Deleted.  
12.7.6.1. In assembly use areas having occupant loads greater than 1,000, there shall be  
crowd managers or crowd manager supervisors at a ratio of 1 crowd manager/supervisor  
for every 250 occupants unless otherwise permitted by any of the following:  
(1) This requirement shall not apply to assembly use areas being utilized for instructional  
classroom space.  
(2) This requirement shall not apply to assembly occupancies used exclusively for  
religious worship with occupant load not more than 2,000.  
(3) The ratio of trained crowd managers to occupants shall be permitted to be reduced  
where, in the opinion of the authority having jurisdiction, the existence of an approved,  
supervised automatic sprinkler system and the nature of the event warrant.  
12.7.6.2. Deleted.  
12.7.7.2. Deleted.  
Page 15  
12.7.9.3.1. Deleted.  
12.7.9.3.2. Deleted.  
12.7.9.3.3. Deleted.  
13.2.2.2.5. Deleted.  
13.2.10.3. Deleted.  
13.2.11.2. Deleted.  
13.3.2.1.2. Rooms or spaces for the storage, processing, or use of materials specified in  
section 13.3.2.1.2(1) to (3) shall be protected pursuant to the following:  
(1) Separation from the remainder of the building by fire barriers having a minimum 1-  
hour fire resistance rating or protection of such rooms by automatic extinguishing systems  
as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless otherwise permitted by either of the following:  
(i) The requirement of section 13.3.2.1.2(1)(a) shall not apply to rooms enclosing  
furnaces, heating and air handling equipment, or compressor equipment with a total  
aggregate input rating less than 200,000 Btu (211 MJ), provided that such rooms are not  
used for storage.  
(ii) The requirement of section 13.3.2.1.2(1)(a) shall not apply to attic locations of the  
rooms addressed in section 13.3.2.1.2(1)(a)(i), provided that such rooms comply with the  
draftstopping requirements of section 8.6.10.  
(b) Rooms or spaces larger than 100 square feet (4.6 square meters) and used for the  
storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(2) Separation from the remainder of the building by fire barriers having a minimum 1-  
hour fire resistance rating and protection of such rooms by automatic extinguishing systems  
as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including woodworking and painting areas.  
(c) Rooms or spaces used for processing or use of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(3) Where automatic extinguishing is used to meet the requirements of section  
13.3.2.1.2(1) or (2), the protection shall be permitted pursuant to section 9.7.1.2.  
13.7.1.3. Deleted.  
13.7.6.1. In assembly occupancies having occupant loads greater than 1,000, there shall be  
crowd managers or crowd manager supervisors at a ratio of 1 crowd manager/supervisor  
for every 250 occupants unless otherwise permitted by either of the following:  
(1) This requirement shall not apply to assembly use areas being utilized for instructional  
classroom space.  
(2) This requirement shall not apply to assembly occupancies used exclusively for  
religious worship with occupant load not more than 2,000.  
(3) The ratio of trained crowd managers to occupants shall be permitted to be reduced  
where, in the opinion of the authority having jurisdiction, the existence of an approved,  
supervised automatic sprinkler system and the nature of the event warrant.  
13.7.6.2. Deleted.  
13.7.7.2. Deleted.  
13.7.9.3.1. Deleted.  
Page 16  
13.7.9.3.2. Deleted.  
13.7.9.3.3. Deleted.  
43.1.2.1. The portion or portions of a building undergoing repair, renovation, modification,  
or reconstruction shall comply with both of the following:  
(1) Requirements of the applicable existing occupancy chapters.  
(2) Requirements of the applicable section of this chapter.  
43.1.4.5. Deleted.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1909 Rescinded.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1910 Rescission.  
Rule 10. R 29.301 to R 29.321 of the Michigan Administrative Code are rescinded.  
History: 1998-2000 AACS.  
PART 2. SCHOOLS  
R 29.1921 Life safety code; adoption by reference of standards for new schools.  
Rule 21. The provisions of chapters 1 to 12, 14, and 43 of the code that apply to new educational  
occupancies are adopted by reference in R 29.1902 except as amended by these rules.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1922 Amendments.  
Rule 22. Sections 14.1.2.2, 14.1.6, 14.2.6.2, 14.2.6.3, 14.2.11.1.1, 14.2.11.2, 14.3.2.1,  
14.3.4.1.2, 14.3.4.2.1, and 14.7.2.1 of the code are amended, sections 14.1.2.1.1,  
14.1.2.2.1, 14.2.11.1.3, 14.3.2.5.1, 14.3.4.4, 14.3.4.5, 14.7.4.2.1, and 14.7.4.4 are added to  
the code, and sections 14.2.2.2.3.1, 14.3.4.2.3, 14.3.4.2.3.1, 14.3.4.2.3.2, 14.7.2.2, 14.7.2.3,  
and 14.7.3.3 are deleted to read as follows:  
14.1.2.1.1. Educational occupancies shall include child care operations established and  
operated by an intermediate school board, the board of a local school district, the board or  
governing body of a state-approved nonpublic school, or by a person or entity with whom  
a school contracts for services, if the child care center is located in a school that is approved  
by the state fire marshal.  
14.1.2.2. Unless otherwise permitted by section 14.1.2.1.1 educational occupancies shall  
not include any of the following:  
(a) A part or full-day preschool.  
(b) A day care center.  
Page 17  
(c) A kindergarten-only building.  
(d) A building that houses a combination of preschool and kindergarten.  
(e) A building that houses a combination of day care and kindergarten.  
14.1.2.2.1. A program specifically tailored for special needs children, special needs adults,  
or both, who range from 17 to 26 years of age, that is located in a community in a facility  
such as a shopping mall or business building, where the students will gain specific job  
experience and learn life studies, shall not be defined as a school.  
14.1.6. For minimum construction requirements refer to the Michigan building code, R  
408.30401 to R 408.30499.  
14.2.2.2.3.1. Deleted.  
14.2.6.2. Travel distances to an exit shall not exceed 200 feet (61 meters) from any point  
in a building, unless otherwise permitted by section 14.2.6.3.  
14.2.6.3. Travel distance shall not exceed 250 feet (76.2 meters) in educational occupancies  
protected throughout by an approved automatic sprinkler system pursuant to Section 9.7.  
14.2.11.1.1. The school or designated representative shall ensure every room or space  
which is more than 250 square feet (23.2 square meters) and which is used for classroom  
or other educational purposes or is normally subject to student occupancy shall have not  
less than 1 outside window for emergency rescue or ventilation that complies with the  
following unless otherwise permitted by section 14.2.11.1.2:  
(1) The windows shall be openable from the inside without the use of tools, only held  
closed by a single operation lock, and shall provide a clear opening of not less than 20  
inches (50.8 centimeters) in width, 24 inches (61 centimeters) in height, and 5.7 square feet  
(0.5 square meters) in area. A screen on the window shall be readily removable without  
any special knowledge or tools.  
(2) The bottom of the opening shall be not more than 44 inches (112 centimeters) above  
the floor, and any latching device shall be capable of being operated from not more than  
54 inches (1370 mm) above the finished floor.  
(3) The clear opening shall allow a rectangular solid, with a width and height that provides  
not less than the required 5.7 square feet (0.5 square meters) opening and a depth of not  
less than 20 inches (510 millimeters), to pass fully through the opening.  
(4) The windows shall be accessible by the fire department and shall open into an area  
that has access to a public way. Windows opening onto an open court, as defined in the  
code, are acceptable.  
(5) The windows shall be identified by a permanent durable and legible sign having letters  
that are not less than 5/8 of an inch high and 1/8 of an inch wide. The sign shall read “rescue  
window.”  
14.2.11.1.3. Windowless student occupied rooms in additions to existing buildings or  
renovated buildings shall be permitted where it is impractical to comply with section  
14.2.11.1.1 where all of the following:  
(1) A minimum of 50% of the required exits pass into a separate atmosphere created by a  
minimum 2-hour fire rated barrier with labeled 90-minute fire rated door assemblies in all  
openings. Glazing, other than permitted in the door by NFPA 80, shall be permitted only  
if the glazing has been tested for a 2-hour rating as well. The fire barrier shall completely  
separate the building from exterior wall to exterior wall.  
(2) Each separate area shall have approved exiting pursuant to the code.  
Page 18  
(3) A maximum of 25% of the total area of the student occupied rooms in the building  
shall be permitted to be windowless.  
14.2.11.2. Lockups. Locking devices for designated “quiet rooms” shall meet all of the  
following criteria:  
(1) The locking mechanism shall be a spring operated latch, which shall be manually  
depressed to keep it in the latched position. Upon manual release, the latch shall  
automatically return to the unlatched position.  
(2) A viewing window shall be required for observation of the student.  
(3) There shall be constant supervision by a teacher or responsible adult at all times a  
student is in the room.  
14.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in  
section 14.3.2.1(1) to (4) shall be protected pursuant to the following:  
(1) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistive rating or protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless the rooms enclose only air-handling equipment.  
(b) Rooms or spaces greater than 100 square feet used for storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(d) Janitor closets [see also 14.3.2.1(4)].  
(2) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistance rating and protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including wood working and painting areas.  
(c) Rooms or spaces used for the processing or use of combustible supplies deemed  
hazardous by recognized standards.  
(d) Industrial arts and crafts rooms.  
(3) Where automatic extinguishing is used to meet the requirements of section 14.3.2(1)  
or (2), the protection shall be permitted pursuant to section9.7.1.2.  
(4) Where janitor closets addressed in section 14.3.2.1(1)(d) are protected pursuant to the  
sprinkler option of section 14.3.2.1(1), the janitor closet doors shall be permitted to have  
ventilating louvers.  
14.3.2.5.1. The school or designated representative shall ensure that any room that is used  
for instruction and has 3 or more gas outlets be provided with a master gas valve which  
shall be conveniently located outside the door of the room and be clearly marked so that  
the valve may be closed without having to enter the room. This section shall not apply to  
life skills rooms in which gas outlets supply stoves for cooking.  
14.3.4.1.2. The requirement of section 14.3.4.1.1 shall not apply to a building meeting all  
of the following criteria:  
(1) Has an area not exceeding 1,000 square feet.  
(2) Contains a single classroom.  
(3) Is located not less than 10 feet from another building.  
14.3.4.2.1. Initiation of the required fire alarm system shall be by manual means pursuant  
to section 9.6.2.1(1). Manual fire alarm pull stations shall be provided pursuant to sections  
Page 19  
9.6.2.2 to 9.6.2.5 of the code and at all exterior doors in the natural path of escape whether  
or not the path of escape is designated a required exit by these rules.  
14.3.4.2.3. Deleted.  
14.3.4.2.3.1. Deleted.  
14.3.4.2.3.2. Deleted.  
14.3.4.4. The school fire alarm system shall be provided with zone annunciation pursuant  
to the requirements of section 9.6.7 of the code.  
14.3.4.5. In buildings provided with automatic extinguishing protective systems, all  
extinguishing system control valves shall be electronically supervised through the fire  
alarm system to cause an audible and visual supervisory signal at a location in the building  
where the signal will alert responsible personnel.  
14.7.2.1. Emergency egress drills shall be conducted pursuant to the act.  
14.7.2.2. Deleted.  
14.7.2.3. Deleted.  
14.7.3.3. Deleted.  
14.7.4.2.1. Items permitted to be located in required egress corridors, provided the required  
clear width of the corridor is not obstructed, are limited to include fixed benches or  
hardwood or non-combustible material, trophy cases which are not used for excessive  
amounts of combustible materials, drinking fountains, telephones, vending machines, and  
other fixtures or items as approved by the authority having jurisdiction.  
14.7.4.4. Desks and other instructional equipment shall be prohibited in required egress  
corridors.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1923 Life safety code; adoption by reference of standards for existing schools.  
Rule 23. The provisions of chapters 1 to 11, 13, 15, and 43 of the code that apply to  
existing educational occupancies are adopted by reference in R 29.1902, except as  
amended by these rules.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1924 Amendments.  
Rule 24. Sections 15.1.2.2, 15.1.6, 15.2.6.2, 15.2.6.3, 15.2.11.1.1, 15.2.11.1.2, 15.2.11.2,  
15.3.2.1, 15.3.4.1.2, 15.3.4.2.1, 15.3.6, 15.3.7.2, and 15.7.2.1 are amended, sections  
15.1.2.1.1, 15.1.2.2.1, 15.2.11.1.3, 15.3.4.3.1.7, 15.7.4.2.1, and 15.7.4.4 are added and  
sections 15.2.2.2.3.1, 15.3.4.2.3, 15.3.4.2.3.1, 15.3.4.2.3.2, 15.7.2.2, 15.7.2.3, and 15.7.3.3  
are deleted, to read as follows:  
15.1.2.1.1. Educational occupancies shall include child care operations established and  
operated by an intermediate school board, the board of a local school district, the board or  
governing body of a state-approved nonpublic school, or by a person or entity with whom  
a school contracts for services, if the child care center in located in a school that is approved  
by the state fire marshal.  
Page 20  
15.1.2.2. Unless otherwise permitted by section 15.1.4.1.1; educational occupancies shall  
not include any of the following:  
(a) A part or full-day preschool.  
(b) A day care center.  
(c) A kindergarten-only building.  
(d) A building that houses a combination of preschool and kindergarten.  
(e) A building that houses a combination of day care and kindergarten.  
15.1.2.2.1. A program specifically tailored for special needs children, special needs adults,  
or both, who range from 17 to 26 years of age, that is located in a community in a facility  
such as a shopping mall or business building, where the students will gain specific job  
experience and learn life studies, shall not be defined as a school.  
15.1.6. For minimum construction requirements, refer to the Michigan rehabilitation code,  
R 408.30551 to R 408.30577.  
15.2.2.2.3.1. Deleted.  
15.2.6.2. Travel distances to an exit shall not exceed 200 feet (61 meters) from any point  
in the building unless otherwise permitted by section 15.2.6.3 or 15.2.6.4 (see also section  
7.6).  
15.2.6.3. Travel distance shall not exceed 250 feet (76.2 meters) in educational occupancies  
protected throughout with an approved automatic sprinkler system pursuant to section 9.7.  
15.2.11.1.1. The school or designated representative shall ensure every room or space that  
is more than 250 square feet (23.2 square meters) and is used for classroom or other  
educational purposes or is normally subject to student occupancy shall have not less than  
1 outside window for emergency rescue or ventilation that complies with the following  
unless otherwise permitted by section 15.2.11.1.2:  
(1) The windows shall be openable from the inside without the use of tools, only held  
closed by a single operation lock, and provides a clear opening of not less than 20 inches  
(50.8 centimeters) in width, 24 inches (61 centimeters) in height, and 5.7 square feet (0.5  
square meters) in area. A screen on the window shall be readily removable without any  
special knowledge or tools.  
(2) The bottom of the opening shall be not more than 44 inches (112 centimeters) above  
the floor and any latching device shall be capable of being operated from not more than 54  
inches (137 centimeters) above the finished floor.  
(3) The clear opening shall allow a rectangular solid with a width and height that provides  
not less than the required 5.7 square foot opening and a depth of 20 inches to pass fully  
through the opening.  
(4) The windows shall be accessible by the fire department and shall open into an area  
that has access to a public way. Windows opening onto an open court, as defined in the  
code, are acceptable.  
(5) The windows shall be identified by a permanent, durable, and legible sign having  
letters not less than 5/8 of an inch high and 1/8 of an inch wide.  
15.2.11.1.2. The requirements of section 15.2.11.1.1 shall not apply to any of the following:  
(1) Buildings protected throughout by an approved automatic sprinkler system in  
compliance with section 9.7.  
(2) Where the room or space has a door leading directly to the outside of the building.  
(3) Rooms located 4 or more stories above the finished ground level.  
Page 21  
(4) Where awning type or hopper-type windows that are hinged or subdivided to provide  
a clear opening of not less than 4 square feet (0.38 square meters) or any dimension of not  
less than 22 inches (560 millimeters) meet the following criteria:  
(a) The windows shall be permitted to continue in use.  
(b) Screen walls or devices located in front of required windows shall not interfere with  
rescue requirements.  
(5) Where a room or space complies with the following:  
(a) Doors shall exist that allow travel between adjacent classrooms.  
(b) Doors used to travel from classroom to classroom shall provide either of the following:  
(i) Direct access to exits in both directions.  
(ii) Direct access to an exit in 1 direction and to a separate smoke compartment that  
provides access to another exit in the other direction.  
(c) The corridor shall be separated from the classrooms by a wall that restricts the passage  
of smoke, and all doors between the classrooms and corridor shall be self-closing or  
automatic-closing pursuant to section 7.2.1.8.  
(d) The length of travel to exits along such paths shall not exceed 150 feet (46 meters).  
(e) Each communicating door shall be marked in accordance with section 7.10.  
(f) No locking device shall be permitted on the communicating doors.  
(6) If a window retrofit project is undertaken, then compliance with the window clear  
opening dimensions is not required. Unless the existing sill construction is being modified,  
the existing sill height can be maintained. All other requirements of section 15.2.11.1.1  
shall apply.  
(7) A school building constructed before August 1, 1989, that is in compliance with both  
of the following provisions:  
(a) The windowless section of the story is not more than 25% of the total area of the story,  
excluding corridors.  
(b) All windowless rooms, spaces, and public assembly places have 50% of their required  
exits visible directly to the exterior of the building and within 20 feet from the door of the  
occupied room.  
15.2.11.1.3. Windowless student occupied rooms in additions to existing buildings or  
renovated buildings shall be permitted where it is impractical to comply with section  
15.2.11.1.1 where all of the following:  
(1) A minimum of 50% of the required exits pass into a separate atmosphere created by a  
minimum 2-hour fire rated barrier with labeled 90-minute fire rated door assemblies in all  
openings. Glazing, other than permitted in the door by NFPA 80, shall be permitted only  
if the glazing has been tested for a 2-hour rating as well. Such construction shall completely  
separate the building from exterior wall to exterior wall.  
(2) Each separate area shall have approved exiting pursuant to the code.  
(3) A maximum of 25% of the total area of the student occupied rooms in the building  
shall be permitted to be windowless.  
15.2.11.2. Lockups. Locking devices for designated “quiet rooms” shall meet all of the  
following criteria:  
(1) The locking mechanism shall be a spring operated latch, which is manually depressed  
to keep it in the latched position. Upon manual release, the latch shall automatically return  
to the unlatched position.  
(2) A viewing window shall be required for observation of the student.  
Page 22  
(3) There shall be constant supervision by a teacher or responsible adult at all times a  
student is in the room.  
15.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in  
section 15.3.2.1(1) to (4) shall be protected pursuant to the following:  
(1) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistive rating or protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless such rooms enclose only air-handling equipment.  
(b) Rooms or spaces greater than 100 square feet used for storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(d) Janitor closets [see also 15.3.2.1(4)].  
(2) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistance rating and protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including wood working and painting areas.  
(c) Rooms or spaces used for the processing or use of combustible supplies deemed  
hazardous by recognized standards.  
(d) Industrial arts and crafts rooms.  
(3) Where automatic extinguishing is used to meet the requirements of section 15.3.2(1)  
or (2), the protection shall be permitted pursuant to section 9.7.1.2.  
(4) Where janitor closets addressed in section 15.3.2.1(1)(d) are protected pursuant to the  
sprinkler option of section 15.3.2.1(1), the janitor closet doors shall be permitted to have  
ventilating louvers.  
15.3.4.1.2. The requirements of section 15.3.4.1.1 shall not apply to buildings meeting all  
of the following criteria:  
(1) Buildings having an area not exceeding 1,000 square feet.  
(2) Buildings containing a single classroom.  
(3) Building located not less than 10 feet from another building.  
15.3.4.2.1. Initiation of the required fire alarm system shall be by manual means in  
accordance with section 9.6.2.1(1). Manual fire alarm pull stations shall be provided  
pursuant to sections 9.6.2.2 to 9.6.2.5 of the code and at all exterior doors in the natural  
path of escape whether or not the path of escape is designated a required exit by these rules.  
15.3.4.2.3. Deleted.  
15.3.4.2.3.1. Deleted.  
15.3.4.2.3.2. Deleted.  
15.3.4.3.1.7. A presignal system pursuant to section 9.6.3.3 shall be permitted.  
15.3.6. Corridors shall be separated from other parts of the story by walls having a  
minimum 1-hour-fire-resistance rating pursuant to section 8.3 unless otherwise permitted  
by the following:  
(1) Corridor protection shall not be required where all spaces normally subject to student  
occupancy have at least 1 door opening directly to the outside or to an exterior exit access  
balcony or corridor pursuant to section 7.5.3.  
(2) The following shall apply to buildings protected throughout by an approved automatic  
sprinkler system with valve supervision pursuant to section 9.7:  
Page 23  
(a) Corridor walls shall not be required to be rated, provided that the walls form smoke  
partitions pursuant to section 8.4.  
(b) The provisions of section 8.4.3.5 shall not apply to normally occupied classrooms.  
(3) Where the corridor ceiling is an assembly having a 1-hour-fire-resistance rating where  
tested as a wall, the corridor wall shall terminate at the corridor ceiling.  
(4) Lavatories shall not be required to be separated from corridors, provided they are  
separated from all other spaces by walls having a 1-hour-fire-resistance rating pursuant to  
section 8.3.  
(5) Lavatories shall not be required to be separated from corridors, provided that the  
building is protected throughout by an approved, supervised automatic sprinkler system  
pursuant to section 9.7.  
(6) In school buildings constructed before August 1, 1989, every interior corridor,  
including corridors in flexible plan buildings, shall be constructed to be reasonably smoke-  
tight.  
(7) In a school building constructed before August 1, 1989, and which is protected  
throughout by an approved automatic sprinkler system installed pursuant to section 9.7 of  
the code, corridor walls are not required.  
15.3.7.2. The requirements of section 15.3.7.1 shall not apply to any of the following:  
(1) Where all classrooms have exterior exit access pursuant to section 7.5.3.  
(2) Buildings protected throughout by an approved automatic sprinkler system pursuant  
to section 9.7.  
15.7.2.1. Emergency egress drills shall be conducted pursuant to the act.  
15.7.2.2. Deleted.  
15.7.2.3. Deleted.  
15.7.3.3. Deleted.  
15.7.4.2.1. Items permitted to be located in exit corridors, provided the required clear width  
of the corridor is not obstructed, shall be limited to include fixed benches or hardwood or  
non-combustible material, trophy cases which are not used for excessive amounts of  
combustible materials, drinking fountains, telephones, vending machines, and other  
fixtures or items as approved by the authority having jurisdiction.  
15.7.4.4. Desks and other instructional equipment shall be prohibited in required egress  
corridors.  
History: 1998-2000 AACS; 2016 AACS.  
PART 3. COLLEGES AND UNIVERSITIES  
R 29.1931 Life safety code; adoption by reference for new colleges and universities.  
Rule 31. The provisions of chapters 1 to 12, 38, and 43 of the code that apply to new  
business occupancies, are adopted by reference in R 29.1902, except as amended by these  
rules.  
History: 1998-2000 AACS; 2016 AACS.  
Page 24  
R 29.1932 Amendments.  
Rule 32. Sections 38.1.6, 38.3.2.1, 38.3.4.2, and 38.7.2 are amended, sections 38.1.1.1.1,  
38.1.3.1.1.1, and 38.3.2.4 are added, as follows:  
38.1.1.1.1. A change of use from a business occupancy to a college or university  
instructional facility shall be reviewed and inspected pursuant to section 43.7.2 for a change  
of occupancy.  
38.1.3.1.1.1. If other business occupancies or uses occur in the same building that houses  
a college or university instructional facility, the provisions of section 6.1.14 for multiple  
occupancies shall apply. A college or university instructional facility that is separated from  
the remainder of a business occupancy by 2-hour fire resistance rated assemblies pursuant  
to section 6-1.14.4 shall be considered separate occupancies. Where the building is  
protected throughout by an approved automatic sprinkler system pursuant to section  
9.7.1.1(1) and supervised pursuant to section 9.7.2, the fire resistance rated separations  
shall be permitted to be reduced to a 1-hour fire resistance-rated assemblies pursuant to  
section 6.1.14.4.3.  
38.1.6. For minimum construction requirements, refer to the Michigan building code, R  
408.30401 to R 408.30499.  
38.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in  
section 38.3.2.1(1) to (3) shall be protected pursuant to the following:  
(1) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistive rating or protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless such rooms enclose only air-handling equipment.  
(b) Rooms or spaces greater than 100 square feet used for storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(2) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistance rating and protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including wood working and painting areas.  
(c) Rooms or spaces used for the processing or use of combustible supplies deemed  
hazardous by recognized standards.  
(d) Industrial arts and crafts rooms.  
(3) Where automatic extinguishing is used to meet the requirements of section 38.3.2(1)  
or (2), the protection shall be permitted pursuant to section 9.7.1.2.  
38.3.2.4. Laboratories that use chemicals shall comply with NFPA 45. The college,  
university, or designated representative shall ensure that laboratory units used for  
instructional purposes shall be separated from non-laboratory areas by 1-hour fire rated  
construction regardless of the presence of fire protection. Any room which has 3 or more  
gas outlets shall be provided with a master gas valve which is conveniently located outside  
the door of the room and is clearly marked so that the valve may be closed without having  
to enter the room.  
38.3.4.2. Initiation of the required fire alarm system shall be by all of the following means  
where provided:  
(1) Manual means pursuant to section 9.6.2.1(1).  
Page 25  
(2) Means of an approved automatic fire detection system that complies with section  
9.6.2.1(2) and provides protection throughout the building.  
(3) Means of an approved automatic sprinkler system that complies with section 9.6.2.1(3)  
and provides protection throughout the building.  
38.7.2. Fire drills shall be held pursuant to the act.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1933 Life safety code; adoption by reference of standards for new existing  
colleges and universities.  
Rule 33. The provisions of chapters 1 to 11, 13, 39 and 43 of the code that apply to  
existing business occupancies, are adopted by reference in R 29.1902, except as amended  
by these rules.  
History: 1998-2000 AACS; 2016 AACS.  
R 29.1934 Amendments.  
Rule 34. Sections 39.1.6, 39.3.2.1, 39.3.4.2, and 39.7.2 are amended as follows:  
39.1.6. For minimum construction requirements, refer to the Michigan rehabilitation code,  
R 408.30551 to R 408.30577.  
39.3.2.1. Rooms or spaces for the storage, processing, or use of materials specified in  
section 39.3.2.1(1) to (3) shall be protected pursuant to the following:  
(1) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistive rating or protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Boiler and furnace rooms, unless such rooms enclose only air-handling equipment.  
(b) Rooms or spaces greater than 100 square feet used for storage of combustible supplies.  
(c) Rooms or spaces used for the storage of hazardous materials or flammable or  
combustible liquids in quantities deemed hazardous by recognized standards.  
(2) The rooms or spaces shall be separated from the remainder of the building by fire  
barriers having a minimum 1-hour fire resistance rating and protected by automatic  
extinguishing systems as specified in section 8.7 in the following areas:  
(a) Laundries.  
(b) Maintenance shops, including wood working and painting areas.  
(c) Rooms or spaces used for the processing or use of combustible supplies deemed  
hazardous by recognized standards.  
(d) Industrial arts and crafts rooms.  
(3) Where automatic extinguishing is used to meet the requirements of section 39.3.2(1)  
or (2), the protection shall be permitted pursuant to section 9.7.1.2.  
39.3.4.2. Initiation of the required fire alarm system shall be by all of the following means  
where provided:  
(1) Manual means pursuant to section 9.6.2.1(1).  
(2) Means of an approved automatic fire detection system that complies with section  
9.6.2.1(2) and provides protection throughout the building.  
Page 26  
(3) Means of an approved automatic sprinkler system that complies with section 9.6.2.1(3)  
and provides protection throughout the building.  
39.7.2. Fire drills shall be held pursuant to the act.  
History: 1998-2000 AACS; 2016 AACS.  