DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES  
DIRECTOR'S OFFICE  
CERTIFICATION OF FIRMS FOR FIRE ALARM SYSTEMS AND FIRE  
SUPPRESSION SYSTEMS IN STATE-REGULATED FACILITIES  
(By authority conferred on the state fire safety board by sections 3c, 26, 27, 28, 29, 30, 32,  
and 33 of 1941 PA 207, and Executive Reorganization Order No. 1997-2, MCL 29.3c,  
29.26, 29.27, 29.28, 29.29, 29.30, 29.32, 29.33, and 29.451)  
R 29.2801 Definitions.  
Rule 1. As used in these rules:  
(a) "Act" means 1941 PA 207, MCL 29.1 et seq.  
(b) "Approved" means acceptable to the department of consumer and industry services,  
office of fire safety.  
(c) "As-built drawings" means drawings portraying the actual construction or installation  
of a system within a building or portion thereof, depicting any and all changes from the  
original design of the system. "As-built drawings" may also be referenced as "record  
drawings."  
(d) "Custom designed fire alarm system or fire suppression system" means a system that  
is comprised of standard components which are individually listed by an approved  
laboratory and which are selected and installed in accordance with the listing.  
(e) "Design location" means the place where system layout and application engineering  
is performed for a required system.  
(f) "Documentation" means a written instrument signed by a qualifying person of a  
certified firm which does all of the following:  
(i) Identifies a specific installation or a specific modification of a required fire alarm  
system or a required fire suppression system.  
(ii) Contains statements to the effect that the required fire alarm system or required fire  
suppression system has been installed or modified pursuant to the instructions and  
specifications of the manufacturer.  
(iii) Identifies applicable state laws and contains a statement that the required fire alarm  
system or required fire suppression system has been installed or modified in compliance  
with those laws.  
(iv) Contains a statement that the required fire alarm system or required fire suppression  
system has been tested and placed in proper operating condition under the supervision of a  
qualifying person employed by the certified firm.  
(g) "Plans and specifications" means the detailed installation drawings, calculations, and  
manufacturer submittals of equipment for a fire alarm system or fire suppression system  
being installed in a regulated facility by a certified firm. The installation drawings,  
calculations, and manufacturer submittals of equipment are also known as shop drawings  
or shop sheets.  
Page 1  
(h) "Pre-engineered or packaged system" means a system consisting of components  
designed to be installed according to pretested limitations as listed by an approved  
laboratory.  
(i) "Qualifying person" means a person who possesses technical qualifications and agrees  
to provide services to a firm for the purpose of qualifying the firm for certification under  
these rules.  
(j) "Responsible person" means a person who possesses certain technical qualifications  
and is employed by the certified firm to perform on-site work on the system being  
documented. A qualifying person may also serve as the responsible person.  
(k) "Supervision" means the act of oversight and monitoring of the work done by a  
certified firm for a fire alarm system or a fire suppression system.  
(l) "Systems modification" means any changes to a required fire alarm system or required  
fire suppression system involving more than the direct replacement of the existing  
components with components approved for the use and coverage.  
(m) "Technical qualification" means the knowledge of applicable codes, standards, and  
laws and the practical knowledge of equipment, material, methods, and theory of operation  
as they relate to fire alarm systems or fire suppression systems, the combination of which,  
when applied to a facility under the jurisdiction of the department of consumer and industry  
services, office of fire safety shall result in a properly operating required fire alarm system  
or required fire suppression system which is acceptable to the department of consumer and  
industry services, office of fire safety.  
History: 1983 AACS; 2003 AACS.  
R 29.2802 System testing, servicing, inspection, or maintenance by certified firm  
required.  
Rule 2. (1) Testing, servicing, inspection, or maintenance functions which are intended to  
be performed by persons who have special training, knowledge, and equipment and which  
is so indicated in the manufacturer's instructions or in a nationally recognized code are  
required to be performed by a certified firm. At a minimum of once a year, system tests of  
required fire alarm systems and fire suppression systems shall be conducted in compliance  
with the standards adopted by reference in R 29.2809 by a certified firm.  
(2) Subject to approval by the department of consumer and industry services, office of  
fire safety, limited testing, inspection, and adjustments to a required fire alarm or fire  
suppression system shall be permitted to be performed by a trained staff member who is  
employed by the regulated facility, and who has adequate knowledge of the installation,  
construction, and operation of the apparatus, and the hazards involved.  
History: 1983 AACS; 2003 AACS.  
R 29.2802a Out of service notification.  
Rule 2a. A certified firm shall provide notification and recommendation as soon as  
practical to the owner or operator of a required fire alarm or fire suppression system if the  
required system is not completely operational or if the required system will be out of  
service. Notification shall include the expected duration of the out of service condition.  
Page 2  
History: 2003 AACS.  
R 29.2803 Firm certification.  
Rule 3. A firm shall not be certified under these rules unless the firm employs a qualifying  
person to actively supervise the technical aspects of the installation, modification, testing,  
servicing, inspection, maintenance, and documentation of required fire alarm systems and  
required fire suppression systems performed by the firm. Each design location of a firm  
performing the operations specified in this rule shall be certified and shall be considered a  
separate certified firm for the purpose of these rules.  
History: 1983 AACS; 2003 AACS.  
R 29.2804 Qualifying person; qualifications generally.  
Rule 4. The qualifying person specified in R 29.2803 shall possess technical qualifications  
in each category for which the firm is to be certified. A qualifying person may only perform  
the duties of a qualifying person for 1 certified firm. A qualifying person may work in more  
than 1 design location provided that he or she is not the sole qualifying person for that  
discipline at the other design location.  
History: 1983 AACS; 2003 AACS.  
R 29.2805 Qualifying person; education and experience requirements.  
Rule 5. (1) A person who meets 1 or more of the following combinations of education  
and experience may be considered to meet the requirements of R 29.2804:  
(a) Is an architect or engineer licensed under 1980 PA 299, MCL 339.101 et seq. and has  
12 months of approved experience in the category for which certification is requested.  
(b) Has a baccalaureate degree in an approved field of engineering, with 12 months of  
approved experience in the category for which certification is requested.  
(c) Is a graduate of an approved 4-year apprentice training program, with 12 months of  
approved experience in the category for which certification is requested.  
(d) Is a graduate of an approved training course provided by an equipment manufacturer,  
with 12 months of approved experience in the category for which certification is requested.  
(e) Is the holder of a class I or class II electrician's license, with 12 months of approved  
experience installing or servicing firm alarm systems in the category for which certification  
is requested.  
(f) Has 60 months of approved experience, 75% of which was accrued in the 5-year period  
before certification is requested.  
(g) Is certified and maintains certification at level 3 or above by the National Institute of  
Certification in Engineering Technologies (NICET), in the category for which certification  
is requested.  
(2) Other combinations of education and experience will be evaluated on an individual  
basis.  
Page 3  
(3) All experience qualifications shall have been accumulated within the 5-year period  
before certification is requested.  
(4) If a person is denied acceptance as a qualified person, an appeal may be submitted to  
the state fire safety board within 60 days of the issuance of the denial.  
History: 1983 AACS; 2003 AACS.  
R 29.2806 Notarized affidavit required; content.  
Rule 6. A notarized affidavit signed by a qualifying person for the firm and the chief  
operating officer of the firm or a designated representative of the chief operating officer of  
the firm shall be submitted to the department of consumer and industry services, office of  
fire safety, on a form provided by the department of consumer and industry services, office  
of fire safety. The affidavit shall contain all of the following:  
(a) The name and address of the employing firm.  
(b) The names and addresses of all qualifying persons.  
(c) A statement to the effect that the firm and all qualifying persons shall comply with the  
provisions of the act.  
History: 1983 AACS; 2003 AACS.  
R 29.2807 Notice of termination of employment of qualifying person required; filing  
of new notarized affidavit required.  
Rule 7. (1) A certified firm shall provide written notification to the department of  
consumer and industry services, office of fire safety, within 15 business days, upon the  
termination of employment of any qualifying person of the firm.  
(2) If the employment of a firm's sole qualifying person is terminated, then a new  
notarized affidavit nominating a new qualifying person shall be filed with the department  
of consumer and industry services, office of fire safety, within 60 days, pursuant to R  
29.2806 or the firm's certification is invalid.  
History: 1983 AACS; 2003 AACS.  
R 29.2807a Responsible person; education and experience requirements.  
Rule 7a. A person who meets all of the following conditions may be considered to meet  
the requirements of R 29.2810 as a responsible person:  
(a) Is employed by the certified firm.  
(b) Has technical knowledge of the fire alarm or fire suppression system to be installed,  
modified, tested, serviced, inspected, or maintained.  
(c) Has been involved with the on-site work of the fire alarm or fire suppression system.  
(d) Has conducted required acceptance testing of the fire alarm or fire suppression system.  
(e) Meets any of the following combinations of education and experience:  
(i) Is certified at level 2 or above by NICET, national institute of certification in  
engineering technologies, in the appropriate category for the fire alarm or fire suppression  
system being documented.  
Page 4  
(ii) Is a graduate of an approved 4-year apprentice training program for the fire alarm or  
fire suppression system being documented.  
(iii) Is a licensed journey electrician or a licensed fire alarm technician if the system  
being documented is a fire alarm system.  
History: 2003 AACS.  
R 29.2808 Application for certification; categories of certification.  
Rule 8. (1) A firm wishing to be certified under section 26 of the act shall submit an  
application to the department of consumer and industry services, office of fire safety, on  
forms provided by the department of consumer and industry services, office of fire safety.  
(2) A firm wishing to be certified may only be certified in the category or categories and  
for the type of work for which the firm demonstrates qualification. Categories of  
certification are as follows:  
(a) Fire alarm systems.  
(b) Fire alarm voice communication systems.  
(c) Custom-designed carbon dioxide systems.  
(d) Pre-engineered carbon dioxide systems.  
(e) Custom-designed wet or dry chemical systems.  
(f) Pre-engineered wet or dry chemical systems.  
(g) Custom-designed clean agent suppression systems.  
(h) Pre-engineered clean agent suppression systems.  
(i) Custom-designed foam systems.  
(j) Pre-engineered foam systems.  
(k) Custom-designed, water-based sprinkler systems, including underground water  
supply.  
(l) Custom designed water spray or water mist systems.  
(m) Water reservoir (aboveground).  
(n) Water reservoir (underground).  
(o) Custom designed pressure tank water supply.  
(p) Engineered pump pressure supply.  
(q) Engineered explosion suppression systems.  
(r) Categories for new technologies.  
(3) If the categories of certification in subrule (2) of this rule do not adequately describe  
a required system or portion of a system for which certification is required, then the firm  
shall provide sufficient information so that a category can be determined.  
(4) An application shall be completed and accompanied by the statutory fee,  
$50.00 of which is not refundable, if it is determined that the qualifying person does not  
meet the requirements of R 29.2804. Each question shall be answered in its entirety. The  
application shall request, at a minimum, all of the following information:  
(a) The official name and mailing address of the firm.  
(b) The location of the firm if other than the mailing address.  
(c) The name or names of the chief operating officer or officers of the firm.  
(d) The name or names of the qualifying person or persons, listed by  
Page 5  
category of certification as set forth in subrule (2) of this rule, to whom the firm desires to  
delegate authority to document the installation or modification of required fire alarm  
systems or required fire suppression systems pursuant to the firm's certification.  
(e) A notarized technical qualifications resume signed by the qualifying person for the  
qualifying person or persons who will provide the technical qualifications for the firm. The  
resume shall be accompanied by written evidence from employers and schools attesting to  
the technical qualifications stated in the resume. If the qualifying person holds certification  
at level 3 or above from NICET, national institute of certification in engineering  
technologies, then a technical resume is not required.  
(f) A statement from the chief operating officer of the firm stating that the firm is capable  
of providing service to required fire alarm systems or required fire suppression systems  
within 24 hours on a 24-hour, 7-day-a-week basis.  
(g) A statement from the chief operating officer of the firm stating that replacement parts  
are available for required fire alarm systems or required fire suppression systems.  
(5) A firm shall be approved and certified by the department of consumer and industry  
services, office of fire safety, before performing work specified in the act. If a firm is denied  
certification, then the firm may request an appeal to the state fire safety board within 60  
days of the certification denial.  
(6) If a firm is denied certification and wishes to appeal that denial, then the firm shall  
provide all of the following information to the state fire safety board with a letter requesting  
an appeal:  
(a) The history and background of the firm.  
(b) A copy of the firm's employee training policy and a description of the training  
programs.  
(c) A specific list of completed fire alarm systems or fire suppression systems installed or  
serviced by the firm. The list shall be submitted as evidence of qualification in the category  
or categories for which certification is requested. The fire alarm system or fire suppression  
system shall be available for inspection by the department of consumer and industry  
services, office of fire safety.  
(d) Samples of typical operating and maintenance instructions provided by the firm to the  
owner or operator of a fire alarm system or fire suppression system.  
(e) Samples of fire alarm system or fire suppression system inspection forms and  
procedures used by the firm and samples of shop drawings prepared by the firm for  
installed or modified systems.  
(f) A list of the testing, maintenance, service, or inspection services available listed by  
category of certification as set forth in subrule (2) of this rule for which certification is  
requested.  
(g) The firm's geographic area of coverage.  
(h) Not less than 3 references recommending that the firm be certified by the department  
of consumer and industry services, office of fire safety. The references shall be from  
sources that have knowledge of the technical capability in the type of fire alarm system or  
fire suppression system for which certification is requested and can speak for the firm's  
qualifications.  
(7) The board may request additional information before rendering a decision.  
History: 1983 AACS; 2003 AACS.  
Page 6  
R 29.2809 Plans and specifications.  
Rule 9. (1) Before installation or modification of a required fire alarm system or required  
fire suppression system, detailed plans and specifications of the proposed required fire  
alarm system or required fire suppression  
system or modification of the system shall be submitted to the department of consumer and  
industry services, office of fire safety, by a certified firm or licensed architect or engineer  
for approval. Violation of this rule may result in an immediate stop work order, which will  
remain in effect until plans are submitted to the office of fire safety and receive approval  
from the office of fire safety before work may resume on the project.  
(2) The plans required by subrule (1) of this rule shall be sufficiently detailed and drawn  
with symbols of a standard form at a minimum of 1/8 inch equals 1 foot scale so that  
compliance with applicable fire safety rules can be determined.  
(3) The specifications required by subrule (1) of this rule shall be sufficiently detailed so  
that correct application of equipment and materials and compliance with applicable fire  
safety rules can be determined.  
(4) Notwithstanding subrules (2) and (3) of this rule, the plans and specifications  
submitted for review and approval shall contain all of the following detailed and specific  
information:  
(a) The complete identification of the owner or occupant of the facility.  
(b) The intended use of the facility.  
(c) The location of the facility.  
(d) The title of the facility.  
(e) The electrical inspection authority having jurisdiction if the proposed installation  
includes any electrical equipment or wiring.  
(f) The point of the compass.  
(g) The identification of the specific materials and methods of proposed installation or  
modification to be used.  
(h) The specific laws, codes, and standards which apply to the required fire alarm system  
or required fire suppression system.  
(5) In addition to the information required in subrule (4) of this rule, plans and  
specifications shall include the information required in the associated sections of national  
fire protection association codes and standards, which are and adopted by reference as part  
of these rules, as follows:  
(a) NFPA 11, 1998 edition, entitled "Low-expansion Foam." Cost: $28.00  
(b) NFPA 11A, 1999 edition, entitled "Medium- and High-Expansion Foam Systems."  
cost: $25.25.  
(c) NFPA 12, 2000 edition, entitled "Carbon Dioxide Extinguishing Systems." cost:  
$25.25.  
(d) NFPA 12a, 1997 edition, entitled "Halon 1301 Fire Extinguishing Systems." cost:  
$28.00.  
(e) NFPA 13, 1999 edition, entitled "Installation of Sprinkler Systems." cost: $40.25.  
(f) NFPA 13d, 1999 edition, entitled "Installation of Sprinkler Systems in One- and two-  
family dwellings and manufactured homes." cost: $25.25.  
(g) NFPA 13r, 1999 edition, entitled "Installation of Sprinkler Systems in Residential  
Occupancies Up To and Including Four Stories in Height." cost: $25.25.  
Page 7  
(h) NFPA 14, 2000 edition, entitled "Installation of Standpipe, Private Hydrant and Hose  
Systems." cost: $25.25.  
(i) NFPA 15, 2001 edition, entitled "Water Spray Fixed Systems for Fire Protection."  
cost: $28.00.  
(j) NFPA 16, 1999 edition, entitled "Installation of Foam-Water Sprinkler and Foam-  
Water Spray Systems." cost: $25.25.  
(k) NFPA 17, 1998 edition, entitled "Dry Chemical Extinguishing Systems." cost:  
$25.25.  
(l) NFPA 17a, 1998 edition, entitled "Wet Chemical Extinguishing Systems." cost:  
$21.00.  
(m) NFPA 20, 1999 edition, entitled "Installation of Stationary Pumps for Fire  
Protection." cost: $28.00.  
(n) NFPA 22, 1998 edition, entitled "Water Tanks for Private Fire Protection." cost:  
$28.00.  
(o) NFPA 24, 1995 edition, entitled "Installation of Private Fire Service Mains and Their  
Appurtenances." cost: $25.25.  
(p) NFPA 25, 1998 edition, entitled "Inspection, Testing, and Maintenance of Water-  
Based Fire Protection Systems." cost: $33.25.  
(q) NFPA 72, 1999 edition, entitled "National Fire Alarm Code." cost: $40.25.  
(r) NFPA 96, 2001 edition, entitled "Ventilation Control and Fire Protection of  
Commercial Cooking Operations." cost: $25.25.  
(s) NFPA 170, 1999 edition, entitled "Fire Safety Symbols." cost: $25.25.  
(t) NFPA 2001, 2000 edition, entitled "Clean Agent Fire Extinguishing Systems." COST:  
$33.25.  
(6) Copies of the adopted codes and standards are available for inspection and distribution  
at cost at the Office of the State Fire Safety Board, Office of Fire Safety, Department of  
Consumer and Industry Services, 7150 Harris Drive, Lansing, Michigan 48909. Copies of  
the adopted standards may be purchased from the National Fire Protection Association, 1  
Batterymarch Park, P.O. Box 9101, Quincy, Massachusetts 02269, telephone number 1-  
800-344-3555, internet address WWW.NFPA.ORG.  
History: 1983 AACS; 2003 AACS.  
R 29.2810 Documentation.  
Rule 10. (1) Before the installation or modification of a required fire alarm system or  
required fire suppression system can be documented, all of the following shall be  
performed under the supervision of a qualifying person of a firm certified by the  
department of consumer and industry services, office of fire safety, in the category of the  
system involved:  
(a) A visual inspection of the entire required fire alarm system or required fire suppression  
system, including concealed areas. This may require periodic inspections as the installation  
or modification of the required fire alarm system or required fire suppression system  
progresses.  
(b) All tests required by fire safety rules promulgated pursuant to the act and required by  
the manufacturer of the required fire alarm system or required fire suppression system.  
Page 8  
(c) Testing and adjustment to specifications, as recommended by the manufacturer or  
recognized industry standard, of all functional parts of the required fire alarm system or  
required fire suppression system.  
(d) Correction and rechecking of all items that do not comply with applicable fire safety  
rules.  
(e) Verification that the required fire alarm system or required fire suppression system is  
completely operational and ready to perform required functions.  
(2) Each new required fire alarm system or required fire suppression system or each  
modification of a required fire alarm system or required fire suppression system shall be  
documented to the department of consumer and industry services, office of fire safety, on  
forms provided by the department of consumer and industry services, office of fire safety,  
by a firm certified under the act. The completed documentation form shall be accompanied  
by the required statutory fee.  
(3) The qualifying person shall sign the documentation form stating the supervisory  
responsibilities of a qualifying person have been met. The responsible person shall sign the  
documentation form stating that the requirements of subrule (1) of this rule have been  
satisfied.  
(4) Any fee submitted by a firm which is not certified under the act or which has had its  
certificate suspended or revoked is not subject to refund.  
History: 1983 AACS; 2003 AACS.  
R 29.2811 Electrical inspection.  
Rule 11. The installation or modification of any electrical equipment or wiring shall be  
performed by firms and personnel licensed in compliance with, 1956 PA 217, MCL  
338.881 et seq., and under permit and inspection in compliance with 1972 PA 230, MCL  
125.1501 et seq. Final approval of the project by the department of consumer and industry  
services, office of fire safety, will not be granted until electrical approval has been verified.  
A certificate of approval of the installation or modification of any electrical equipment or  
wiring from the electrical inspection authority having jurisdiction shall be provided by the  
certified firm to the department of consumer and industry services, office of fire safety.  
History: 1983 AACS; 2003 AACS.  
R 29.2811a Inspection.  
Rule 11a. Before final approval of a project, a responsible person shall be present to  
perform all required tests during system inspection by the department of consumer and  
industry services, office of fire safety.  
History: 2003 AACS.  
R 29.2812 Record keeping.  
Rule 12. (1) A firm certified by the department of consumer and industry services, office  
of fire safety, shall maintain a record of the installation, modification, and documentation  
Page 9  
of each required fire alarm system or required fire suppression system the firm installs,  
modifies, or documents. The records shall include, but not be limited to, all of the following  
information:  
(a) The name and location of the facility.  
(b) The name and location of the owner or operator of the facility.  
(c) The type of required fire alarm system or required fire suppression system installed in  
the facility.  
(d) The name of the firm installing the required fire alarm system or required fire  
suppression system if other than the firm documenting the required fire alarm system or  
required fire suppression system.  
(e) The specific codes, rules, or laws requiring the fire alarm system or fire suppression  
system.  
(f) Copies of all plans and specifications, shop drawings, "as built" drawings,  
manufacturer's data on all equipment and devices, manufacturer's installation, and  
maintenance instructions regarding the required fire alarm system or required fire  
suppression system.  
(g) Copies of all tests, certificates, and approvals of the required fire alarm systems or  
required fire suppression systems.  
(2) A copy of the records specified in subrule (1) of this rule shall be kept in the building  
or other location approved by the department of consumer and industry services, office of  
fire safety, in which the required fire alarm system or required fire suppression system is  
installed.  
(3) A firm certified by the department of consumer and industry services, office of fire  
safety, shall maintain a record of all testing, service, inspection, and maintenance  
performed on a required fire alarm system or required fire suppression system. These  
records shall include, but not be  
limited to, all of the following information:  
(a) The name and location of the facility.  
(b) The date of work on the required fire alarm system or required fire suppression system.  
(c) The name of the certified firm and technician performing the work at that time.  
(d) The reason for work on the required fire alarm system or required fire suppression  
system.  
(e) The test, service, inspection, or maintenance actually performed on the required fire  
alarm system or required fire suppression system.  
(f) The results of the test, service, inspection, or maintenance on the required fire alarm  
system or required fire suppression system.  
(g) Identification and location in the required fire alarm system or required fire  
suppression system of the parts replaced or repaired.  
(h) The operational status of the required fire alarm system or required fire suppression  
system after testing, service, inspection, or maintenance has been performed.  
(i) The notification and recommendation as soon as practical to the owner or operator of  
the required fire alarm system or required fire suppression system if the required fire alarm  
system or required fire suppression system is not completely operational or will be out of  
service and the expected duration of the out-of-service condition.  
(j) The owner's or operator's acknowledgement of the required fire alarm system's  
condition or the required fire suppression system's condition.  
Page 10  
(4) A copy of the records specified in subrule (3) of this rule shall be maintained and  
displayed at the location of the main system control or other location approved by the  
department of consumer and industry services, office of fire safety.  
(5) The owner or operator of a required fire alarm system or required fire  
suppression system shall maintain records of all tests, service, inspections,  
and maintenance performed under R 29.2802. The records shall comply with the  
requirements of subrules (3) and (4) of this rule.  
(6) All records required to be maintained by these rules shall be available for inspection  
by the department of consumer and industry services, office of fire safety, during normal  
business hours. A person shall not alter, deface, or remove the records required to be  
maintained by these rules.  
History: 1983 AACS; 2003 AACS.  
R 29.2813 Availability of drawings during inspection.  
Rule 13. A drawing which depicts the completed installation or modification of a required  
fire alarm system or required fire suppression system as built shall be available to the  
department of consumer and industry services, office of fire safety, for use during an  
inspection of a required fire alarm system or required fire suppression system. The  
drawings and the drawings for all subsequent modifications shall be maintained with the  
records required by these rules. The drawings shall depict, at a minimum, all of the  
following:  
(a) The location and description of all control devices and equipment of the required fire  
alarm system or required fire suppression system.  
(b) The layout, routing, and sizing of all piping and wiring of the required fire alarm  
system or required fire suppression system.  
(c) The location of all junction boxes and terminations of the required fire alarm system  
or required fire suppression system.  
History: 1983 AACS; 2003 AACS.  
R 29.2814 Notice of noncompliance.  
Rule 14. A firm, owner, qualifying person, or operator of a required fire alarm system or  
required fire suppression system who is found to have installed, modified, serviced,  
inspected, or documented a required fire alarm system or required fire suppression system  
in a manner which is not in compliance with sections 26 to 33 of the act shall be notified,  
in writing, by the department of consumer and industry services, office of fire safety, of  
the specific conditions of noncompliance. The firm, owner, qualifying person, or operator  
who is notified of noncompliance shall, within 10 days after the issuance of the notification  
of noncompliance, signify, in writing, the intention to correct the condition of  
noncompliance, stating a date by which the condition of noncompliance will be corrected.  
The date shall be subject to department of consumer and industry services, office of fire  
safety, approval. The failure on the part of a firm, an owner, a qualifying person, or an  
operator who has been notified of a condition of noncompliance to signify in writing the  
intention to comply within the time limits prescribed in this rule or the failure to correct  
Page 11  
the condition of noncompliance by the date approved by the department of consumer and  
industry services, office of fire safety, shall be considered a refusal to comply. A refusal to  
comply will result in the immediate suspension of the firm's certification and immediate  
suspension of the status of the qualifying person. The suspension will remain in effect until  
the certified firm or the qualifying person requests an appeal hearing with the state fire  
safety board. The state fire safety board may affirm, reverse, or modify the suspension or  
may revoke the certification of a firm in accordance with section 32 of the act.  
History: 1983 AACS; 2003 AACS.  
Page 12  
;