3.3.11.6 “Unattended self-service motor fuel dispensing facility” means a motor fuel
dispensing facility that does not have an attendant or employee on duty. The customer or
vehicle operator conducts the dispensing operation. This includes coin, currency, membership
card, and credit card dispensing operations. Unattended self-service motor fuel dispensing
facilities shall include those, new or existing, where access is limited by locked dispensers,
security fencing, or other means to effectively prevent unauthorized access or dispensing.
3.3.15.1 “Aboveground storage tank (AST) system” means a tank or combination of tanks,
including the pipes that are connected to the tank, tanks, or ancillary equipment containment
systems, if any, which is, was, or may have been, used to contain an accumulation of liquids
and which has less than 10% of its volume, including the volume of the underground pipes that
are connected to the tank, or tanks, beneath the surface of the ground.
3.3.15.4 “Tank system” means an AST system or an UST system.
3.3.15.5 “Underground storage tank (UST) system” means a tank or combination of tanks
including the underground pipes that are connected to the tank or tanks or underground
ancillary equipment containment system, if any, which is, was, or may have been, used to
contain an accumulation of liquids and which has 10% or more of its volume, including the
volume of the underground pipes that are connected to the tank or tanks, beneath the surface
of the ground.
3.3.19 “Bureau” means bureau of fire services.
3.3.20 “Building” means any structure used or intended for supporting or sheltering any use
or occupancy.
3.3.20.1 “Important building” means a building that is considered not expendable in an
exposure fire.
3.3.20.2 “Storage tank building” means a 3-dimensional space that is enclosed by a roof and
walls that cover more than 1/2 of the possible area of the sides of the space, is of sufficient size
to allow entry by personnel, will likely limit the dissipation of heat or dispersion of vapors,
and restricts access for fire fighting.
History: 2014 AACS.
R 29.5708 Aboveground storage tanks.
Rule 708. Section 4.3.2.6.1 is added to the FL/CL code as follows:
4.3.2.6.1 A minimum separation is not required for a listed secondary containment tank which
is 4,000 gallons (15,120 liters) or less and which has a 64 inch (162.6 centimeters) nominal
diameter or smaller.
History: 2014 AACS.
R 29.5709 General construction requirements.
Rule 709. Section 7.4.2 of the FL/CL code is adopted with the following changes:
7.4.2 General construction requirements. In major repair garages, where CNG, LNG,
hydrogen or LPG fueled vehicles are repaired, all applicable requirements of R 29.4601 to R
29.4652, R 29.7001 to R 29.7127, or R 29.6001 to R 29.6097 shall be met.
History: 2014 AACS.