DEPARTMENT OF ENVIRONMENTAL QUALITY  
WASTE AND HAZARDOUS MATERIALS DIVISION  
STORAGE AND HANDLING OF GASEOUS AND LIQUEFIED HYDROGEN  
SYSTEMS  
(By authority conferred on the department of environmental quality by section 3c of 1941  
PA 207, MCL 29.3c, and Executive Reorganization Order No. 1998-2, MCL 29.461)  
PART 1. GENERAL PROVISIONS  
R 29.7001 Applicability.  
Rule 1. These rules apply to the operation of all gaseous and Liquefied hydrogen systems.  
A person shall comply with these rules, other applicable state and federal statutes, and rules  
and regulations promulgated under the statutes.  
History: 2008 AACS.  
R 29.7002 Storage and handling of gaseous and Liquefied hydrogen; adoption of  
standard by reference.  
Rule 2. The national fire protection association's (NFPA) Pamphlet 50A, "Standard for  
Gaseous Hydrogen Systems at Consumer Sites," 1999 edition and NFPA Pamphlet 50B,  
"Standard for Liquefied Hydrogen Systems at Consumer Sites," 1999 edition, referred to  
in these rules as the "code," pertaining to the storage and handling, but not transportation,  
of gaseous and Liquefied hydrogen, are adopted by reference as part of these rules. Copies  
of the adopted code are available for inspection at the office of the Department of  
Environmental Quality, Waste and Hazardous Materials Division, Storage Tank Unit, P.O.  
Box 30241, Lansing, Michigan 48909-7741, or for purchase from the National Fire  
Protection Association, Batterymarch Park, Quincy, Massachusetts 02269, telephone  
number 800-344-3555. The cost of the code, at the time of the adoption, is $28.00 each,  
plus a $7.95 handling charge, per copy; or at the office of the Department of Environmental  
Quality, Waste and Hazardous Materials Division, Storage Tank Unit, P.O. Box 30241,  
Lansing, Michigan 48909-7741, for a cost, at the time of the adoption of these rules, of  
$35.95, per copy, plus $20.00 handling, plus shipping.  
History: 2008 AACS.  
PART 2. STORAGE AND HANDLING OF GASEOUS HYDROGEN NFPA 50A  
Chapter 1 General Information  
Page 1  
R 29.7010 Chapter 1 General information.  
Rule 10. Sections 1-1 to 1-1.2 of the storage and handling of gaseous and Liquefied  
hydrogen code are added as follows:  
1-1 Scope. This standard covers the requirements for the design, siting, construction,  
installation, operation, maintenance, and dispensing from a gaseous hydrogen system.  
1-1.1 Nothing in this hydrogen code shall be intended to prevent the use of systems,  
methods, or devices of equivalent or superior quality, strength, fire resistance,  
effectiveness, durability, environmental protection capability, or safety over those  
prescribed by this hydrogen code, if technical documentation is submitted to the  
department to demonstrate equivalency and the system, method, or device is approved for  
the intended purpose.  
1-1.2 This code shall apply to the design and installation of compressed H2 dispensing  
systems.  
Exception: Dispensing to rail and aircraft.  
History: 2008 AACS.  
R 29.7011 Classification.  
Rule 11. Section 1-2 is reproduced from NFPA 50A as follows:  
1-2 Classification. Systems are classified according to the total volume of hydrogen,  
including unconnected reserves, as follows:  
(a) Less than 3500 scf (99 m3), except as covered in 1-3.1  
(b) From 3500 (99 m3) to 15,000 scf (425 m3)  
(c) In excess of 15,000 scf (425 m3)  
History: 2008 AACS.  
R 29.7012 Application.  
Rule 12. Section 1-3.2 is reproduced from NFPA 50A, and sections 1-3,  
1-3.1, 1-3.3, 1-3.4, and 1-3.5 of the storage and handling of gaseous and Liquefied H2 code  
are added as follows:  
1-3 Application.  
1-3.1 The application of this standard at places of public assembly shall meet the  
requirements of section 3-2.2(a) and the approval of the department.  
1-3.2 This standard shall not apply to single systems using containers having a total H2  
content of less than 400 scf (11 m3). Where individual systems, each having a total H2  
content of less than 400 scf (11 m3), are located less than 5 ft (1.5 m) from each other, this  
standard shall apply.  
1-3.3 This standard does not apply to flow-through process containers.  
1-3.4 When required by the department, H2 introduced into any system covered by this  
code shall have a leak detection system acceptable to the department and based on the best  
interest of public health, safety, and welfare and the environment.  
1-3.5 Gaseous H2 in fuel tanks on vehicles and mobile equipment shall not be included in  
determining the maximum allowable quantities.  
Page 2  
History: 2008 AACS.  
R 29.7013 Retroactivity.  
Rule 13. Sections 1-4 and 1-4.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-4 Retroactivity.  
1-4.1 The provisions of this H2 code are necessary to provide a reasonable level of  
protection from loss of life and property from fire and explosion. The provisions shall  
reflect situations and the state of the art prevalent when the H2 code was issued. Unless  
otherwise noted, it is not intended that the provisions of this H2 code be applied to facilities,  
equipment, structures, or installations that were existing or approved for construction or  
installation before the effective date of this H2 code, except in those cases where it is  
determined by the department that the existing situation involves a distinct hazard to public  
health, safety, adjacent property, or the environment.  
History: 2008 AACS.  
R 29.7014 Definitions.  
Rule 14. Section 1-5 of the storage and handling of gaseous and Liquefied H2 code is  
added, and Section 1-5.1 is reproduced from NFPA 50A as follows:  
1-5 Definitions.  
(a) "ANSI" means the american national standards institute.  
(b) "Approved" means acceptable to the department.  
(c) "ASME" means the american society of mechanical engineers.  
(d) "Authority having jurisdiction" means the department.  
(e) "Automatic emergency shutoff valve" means a designated fail-safe automatic closing  
valve designed to shutoff the flow of gases or liquids that is initiated by a control system  
where the control system is activated by either manual or automatic means.  
(f) "Bulk storage" means a single container or containers, where all containers draw down  
at the same time.  
(g) "Cargo transport container" means a mobile unit designed to transport gaseous or  
liquefied H2.  
(h) "Cascade storage system" means storage in containers or cylinders arranged in banks  
where each bank acts as 1 large container. The banks are separated by switching valves to  
provide sequential drawdown of the banks.  
The bank may consist of 1 or more containers or cylinders.  
(i) "Cathodic protection" means a technique to prevent the corrosion of a metal surface  
by making the surface the cathode of an electrochemical cell. This protection renders a  
metallic container or piping component negatively charged with respect to its environment.  
This protection shall be designed by a corrosion expert as defined by these rules.  
(j) "Cathodic protection tester" means a person who can demonstrate an understanding of  
the principles and measurements of all common types of cathodic protection systems  
applicable to metal piping and container systems and who has education and experience in  
soil resistivity, stray current, structure-to-soil potential, and component electrical isolation  
Page 3  
measurements of metal piping and container systems. The person shall be certified as being  
qualified by the national association of corrosion engineers (NACE) international.  
(k) "Composite container" means a container fabricated of 2 or more materials that  
interact to facilitate the container design criteria.  
(l) "Compression discharge pressure" means the varying pressure at the point of discharge  
from the compressor.  
(m) "CGA" means the compressed gas association.  
(n) "Container" means a pressure vessel or cylinder used to store H2.  
(o) "Container appurtenances" means devices connected to container openings for safety,  
control, or operating purposes.  
(p) "Container system" means a container or combination of containers and all attached  
appurtenances, valves, and piping.  
(q) "Container valve" means a valve connected directly to the container outlet.  
(r) "Continuous gas detection system" means a gas detection system in which the  
instrument is maintained in continuous operation.  
(s) "Corrosion expert" means a person who, by reason of thorough knowledge of the  
physical sciences and the principals of engineering and mathematics acquired by a  
professional education and related practical experience, is qualified to engage in the  
practice of corrosion control of container systems. The person shall be certificated as being  
qualified by NACE, as a senior corrosion technologist, a cathodic protection specialist, or  
a corrosion specialist or be a registered engineer who has certification and licensing that  
includes education and experience in corrosion control.  
(t) "Corrosion protection" means protecting a container system to prevent the degradation  
of the metal through oxidation or reactivity with its environment.  
(u) "Cylinder" means a container constructed in accordance with the United States  
Department of Transportation (U.S. DOT) specifications, title 49, code of federal  
regulations (CFR), parts 171-190.  
(v) "Department" means the department of environmental quality.  
(w) "Director" means the director of the department of environmental quality.  
(x) "Dispensing station" means an H2 installation that dispenses H2 from storage  
containers into fuel supply containers or into portable cylinders by means of a compressor,  
reformer, vaporizer, or pressure booster.  
(y) "Emergency shutdown device (ESD)" means a device that closes all fueling operations  
within the fueling facility from either local or remote locations.  
(z) "Excess flow control" means to limit or stop the flow of H2 gas from a source of supply  
when there is a rupture, break, or 'open valve to atmosphere' condition that may present a  
hazard to personnel or the environment.  
(aa) "Fail-safe" means a design feature that provides for the maintenance of safe operating  
conditions in the event of a malfunction of control devices or an interruption of an energy  
source.  
(bb) "Fast fill station" means a storage and dispensing system designed to fill motor  
vehicle fuel tanks with compressed, gasified H2. The vehicle fuel tank is filled by  
connecting to a system designed to provide a fuel fill rate above 12 scfm.  
(cc) "Fixed liquid level device" means a device that indicates when the container is filled  
to its maximum permitted liquid filling volume.  
Page 4  
(dd) "Flow-through process container" means a container that forms an integral part of a  
production process through which there is a steady, variable, recurring, or intermittent flow  
of materials during the operation of the process and the container is utilized to carry out or  
control the heating, cooling, mixing, blending, separating, metering, or chemical reaction  
of materials. The processing is done on a regular basis and it is the primary function of the  
container. A flow-through process container does not include a container that is used for  
the storage of materials before its introduction into the production process or for the storage  
of finished products or by-products from the production process or a container that is only  
used to recirculate materials.  
(ee) "Fuel dispenser system" means all the pumps, meters, piping, hose, and controls used  
for the delivery of fuel.  
(ff) "Fueling connector" means a mating device at the refueling station, including shutoff  
valves that connect the fueling dispenser hose to the vehicle fuel filling system receptacle  
for the transfer of liquid or vapor.  
(gg) "Gallon water capacity (wc)" means the amount of water in gallons at 60 degrees  
Fahrenheit (15 degrees Celsius) required to fill a container.  
(hh) "Gas detection system" means a grouping of 1 or more sensors capable of detecting  
an H2 leak at specified concentrations and activating alarms and safety systems.  
(ii) "Gaseous H2 system" means a system in which the H2 is delivered, stored, and  
discharged in the gaseous form including the piping system. The gaseous H2 system  
terminates at the point where the H2 is dispensed.  
(jj) "Hydrogen (H2)" means the simplest and lightest element in the known universe,  
which exists as a gas except at low cryogenic temperatures.H2 gas is a colorless, odorless  
and highly flammable gas when mixed with oxygen over a wide range of concentrations.  
H2 forms water when combusted, or when otherwise joined with oxygen, as within a fuel  
cell.  
(kk) "Hydrogen code" means the storage and handling of gaseous and liquefied H2 rules  
as promulgated by the department.  
(ll) "Hydrogen gas vehicle (HGV) or vehicle" means a self-propelled device on land, in,  
on, or by which any person or property is or may be transported or drawn upon, except for  
a device exclusively moved by human power, and which has the capability to use H2 gas  
as an engine fuel.  
(mm) "Ignition source" means any item or substance capable of an energy release of type  
and magnitude sufficient to ignite any flammable mixture of gases or vapors that could  
occur at the site.  
(nn) "kPa" means absolute pressure in kilo-Pascals.  
(oo) "kPag" means gauge pressure in kilo-Pascals.  
(pp) "Labeled" means equipment or materials to which has been attached a label, symbol,  
or other identifying mark of an organization that is acceptable to the department and  
concerned with product evaluation, that maintains periodic inspection of production of  
labeled equipment or materials, and by whose labeling the manufacturer indicates  
compliance with accepted or approved standards of construction and or performance.  
(qq) "Listed" means equipment, materials, or services included in a list published by an  
organization that is acceptable to the department and concerned with evaluation of products  
or services, that maintains periodic inspection of production listed equipment or materials  
or periodic evaluation of services, and whose listing states that either the equipment,  
Page 5  
material, or service meets appropriate designated standards or has been tested and found  
suitable for a specified purpose.  
(rr) "Manifolded storage system" means storage in containers arranged in banks where  
each bank acts as 1 large container. The banks are separated by switching valves to provide  
sequential drawdown of the banks. The bank may consist of 1 or more containers.  
(ss) "Manual emergency shutoff valve" means a designated valve designed to shutoff flow  
due to a rupture in pressurized piping system.  
(tt) "Maximum allowable working pressure (MAWP)" means the maximum pressure to  
which any component or portion of the pressure system can be subjected.  
(uu) "Maximum operating pressure (MOP)" means the steady-state gauge pressure at  
which a part or system normally operates.  
(vv) "Metal hydride storage system" means a system for the storage of H2 gas absorbed  
in solid material.  
(ww) "Motor fuel dispensing facility" means that portion of the property where H2 is  
stored and dispensed from fixed equipment into the fuel tanks of motor vehicles, marine  
craft, or into approved containers, including all equipment used in connection therewith.  
(xx) "NACE" means the national association of corrosion engineers, international.  
(yy) "Original equipment manufacturer (OEM)" means an original equipment motor  
vehicle manufacturer that certifies that the motor vehicle complies with applicable federal  
motor vehicle safety codes.  
(zz) "Partially buried container" means a container that has part of, but less than 100%,  
of the container surface covered with earth.  
(aaa) "Point of transfer" means the point where the transfer connection is made.  
(bbb) "Portable container" means a container designed to be moved readily, as  
distinguished from containers designed for stationary installations. Portable containers,  
designed for transportation with H2, filled to their maximum filling limit, include  
"cylinders," "cargo tanks," and "portable tanks," all 3 of which are defined separately.  
Containers designed to be readily moved from 1 usage location to another, but substantially  
empty of product, are "portable storage containers" and are defined separately.  
(ccc) "Portable storage container" means a container similar to those designed and  
constructed for stationary installation, designed so that it can be moved readily over the  
highways, substantially empty of H2, from 1 usage location to another. Such containers  
either have legs or other supports attached, or are mounted on running gear, such as trailer  
or semitrailer chassis, with suitable supports that can be of the fold-down type, allowing  
them to be placed or parked in a stable position on a reasonably firm and level surface. For  
large-volume, limited-duration product usage, such as at construction sites and normally  
for 6 months or less, portable storage containers function in lieu of permanently installed  
stationary containers.  
(ddd) "Portable tank, or skid tank" means a container of more than 1,000 lb (454 kilogram)  
water capacity used to transport H2, handled as a package, that is, filled to its maximum  
permitted filling limit. Such containers are mounted on skids or runners and have all  
container appurtenances protected in such a manner that they can be safely handled as a  
package.  
(eee) "Pressure relief device (PRD)" means a pressure or temperature activated device  
used to prevent pressure from rising above a specified value and thereby prevent the rupture  
Page 6  
of a normally charged pressure vessel or a cylinder due to emergency or abnormal  
conditions.  
(fff) "Pressure vessel" means a container or other component designed in accordance with  
the ASME code.  
(ggg) "psi" means pounds per square inch.  
(hhh) "psia" means pounds per square inch, absolute.  
(iii) "psig" means pounds per square inch gauge.  
(jjj) "Rated pressure" means the pressure to which a component is rated provided that the  
MAWP is observed for temperature extremes.  
(kkk) "Release" means an unexpected discharge of H2.  
(lll) "Remotely located manually activated shutdown control" means a control system that  
is designed to initiate shut down of the flow of gas or liquid that is manually activated from  
a point located some distance from the delivery system.  
(mmm) "Residential fueling facility" means a listed vehicle fueling appliance used for the  
compression and delivery of H2 into vehicles at a residence which includes its associated  
equipment and piping.  
(nnn) "Service pressure" means the nominal gas pressure at a uniform gas temperature  
of 70 degrees Fahrenheit (21 degrees Celsius) when the equipment is properly and  
completely charged with gas; the nominal design pressure for which the equipment has  
been constructed.  
(ooo) "Set pressure" means the start-to-discharge pressure for which a relief valve is set  
and marked.  
(ppp) "Standard cubic foot per minute (scfm)" means the amount of gas flow in standard  
cubic feet per minute compensated for pressure and temperature.  
(qqq) "Substantially empty" means a gas container of H2 when the residual gas pressure  
is less than 10% of the maximum allowable working pressure of the vessel.  
(rrr) "Vehicle-fueling appliance" means a self-contained listed assembly used for the  
compression and delivery of H2 gas into vehicles including associated equipment and  
piping of the appliance.1-5.1 NFPA official definitions.Combustible Liquid. A liquid  
having a closed-cup flash point at or above 100°  
F (37.8°C) and are subdivided as follows:  
(a) Class II liquids include those having a flash point at or above 100°F (37.8°C) and  
below 140°F (60°C).  
(b) Class IIIA liquids include those having a flash point at or above 140°F (60°C) and  
below 200°F (93.4°C).  
(c) Class IIIB liquids include those having a flash point at or above 200°F (93.4°C).  
Flammable Liquid (Class I). Any liquid having a closed-cup flash point below 100°F  
(37.8°C) and having a vapor pressure not exceeding 40 psia (276 kPa) at 100°F (37.8°C).  
Gallon. A standard U.S. gallon. Limited-Combustible Material. A material, as defined in  
NFPA 220, Standard on Types of Building Construction, not complying with the definition  
of noncombustible material that, in the form in which it is used, has a potential heat value  
not exceeding 3500 Btu/lb (8141 kJ/kg) and complies with one of the following paragraphs  
(a) or (b). Materials subject to an increase in combustibility or flame spread rating, beyond  
the limits herein established, through the effects of age, moisture, or other atmospheric  
condition are considered combustible.  
Page 7  
(a) Materials having a structural base of noncombustible material, with a surfacing not  
exceeding a thickness of 1/8 in. (3.2 mm) that has a flame spread rating not greater than  
50.  
(b) Materials, in the form and thickness used, other than as described in (a), having neither  
a flame spread rating greater than 25 nor evidence of continued progressive combustion  
and of such composition that surfaces that would be exposed by cutting through the  
material on any plane would have neither a flame spread rating greater than 25 nor evidence  
of continued progressive combustion. Noncombustible Material. A material, as defined in  
NFPA 220, Standard on Types of Building Construction, that, in the form in which it is  
used and under the conditions anticipated, will not ignite, burn, support combustion, or  
release flammable vapors when subjected to fire or heat. Materials reported as  
noncombustible, when tested in accordance with ASTM E 136, Standard Method of Test  
for Behavior of Materials in a Vertical Tube Furnace at 750°C, are considered  
noncombustible materials. Outdoors. Location outside of any building or structure or  
locations under a roof, weather shelter, or canopy provided this area is not enclosed on  
more than two sides.  
Separate Building. A detached, noncommunicating building used exclusively to house a  
hydrogen system. Shall. Indicates a mandatory requirement. Special Room. A separate  
enclosed area that is part of or attached to another building and is used exclusively for an  
H2 system. Standard. A document, the main text of which contains only mandatory  
provisions using the word "shall" to indicate requirements and which is in a form generally  
suitable for mandatory reference by another standard or code or for adoption into law.  
Nonmandatory provisions shall be located in an appendix, footnote, or fine-print note and  
are not to be considered a part of the requirements of a standard. Standard Cubic Foot (scf).  
One cubic foot of gas at 70°F (21°C) and 14.7 psia (an absolute pressure of 101 kPa).  
History: 2008 AACS.  
R 29.7015 Equivalency.  
Rule 15. Sections 1-6 to 1-6.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-6 Equivalency.  
1-6.1 Nothing in this H2 code shall be intended to prevent the use of systems, methods, or  
devices having equivalent or superior quality, strength, fire resistance, effectiveness,  
durability, environmental protection capability, or safety over those prescribed by the H2  
code, if technical documentation is submitted to the department to demonstrate equivalency  
and the system, method, or device is approved for the intended purpose.  
1-6.2 An owner or operator may make an application for a variance of rules by applying to  
the department with a satisfactory explanation of why compliance is not possible. The  
department may approve the variance request upon finding that the variance is based upon  
the best interest of public health, safety, and welfare and the environment.  
1-6.3 A person aggrieved by a final decision of the department on a request for variance or  
an equivalency determination may appeal to the circuit court within 21 days of receiving  
the decision.  
History: 2008 AACS.  
Page 8  
R 29.7016 Prohibitions.  
Rule 16. Sections 1-7 to 1-7.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-7 Prohibitions.  
1-7.1 Any H2 storage container system or practice that is not in compliance with these rules  
shall be considered to be in violation of these rules.  
1-7.2 Upon notification by the department, a person shall not deliver H2 to a storage  
container system under any circumstances that are prohibited by these rules or if a container  
is not in compliance with these rules. Such notification may include a verbal or written  
communication or an affixed written notification on the H2 system.  
1-7.3 A person shall not tamper with, remove, or disregard written notification affixed to  
the storage container system.  
1-7.4 An owner or operator shall not continue to use a storage container system that is  
causing a release and shall expeditiously empty the system or the component that is causing  
the release until the system is repaired or replaced.  
History: 2008 AACS.  
R 29.7017 Installation application.  
Rule 17. Sections 1-8 to 1-8.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-8 Installation application.  
1-8.1 An application for plan review shall be submitted, on a form provided by the  
department, by the owner or owner's designee on behalf of the owner to the department not  
less than 30 days before the installation of an H2 storage container system.  
1-8.1.1 The installation application shall include all of the following information:  
(a) A plot map showing all of the following within 100 feet (30.5 meters) of any portion  
from the container system:  
(i) The location of the following:  
(A) Buildings.  
(B) Public roadways.  
(C) Railroad mainlines.  
(D) Public sidewalks.  
(E) Overhead power lines.  
(ii) The proposed location of the dispensing station.  
(iii) The location of property lines.  
(iv) The locations of existing aboveground and underground tanks storing flammable and  
combustible liquids, and flammable, compressed or liquefied gases.  
(v) The location of the point of transfer in relationship to all of the following:  
(A) The container.  
(B) Buildings.  
(C) Public ways.  
(D) Outdoor places of public assembly.  
(E) Driveways.  
Page 9  
(F) Main line railroad track center lines.  
(G) The line of adjoining property that may be built upon.  
(H) Aboveground and underground tanks storing flammable and combustible liquids  
and/or flammable, compressed, or liquefied gases.  
(b) The construction material, the dimensions and the capacity of each container.  
(c) The type of container venting and pressure relief.  
(d) The compressor(s) size (psig and scfm).  
(e) Container appurtenances.  
(f) A piping diagram showing sizes, valves, pressure relief and fittings, and control  
devices.  
1-8.2 Upon acknowledged receipt of the plans, the department shall issue a plan review  
report within 30 days. If the plan review report is not issued within 30 days, the installation  
may be constructed according to the submitted plans and shall comply with these rules.  
1-8.3 An applicant shall notify the department upon completion of the installation before  
the installation is placed into service. The department shall inspect the installation after  
receiving notification and shall certify the installation, if the requirements of the rules are  
met. If the inspection is not made within 2 working days, then the applicant may place the  
installation into service, or if intended to be underground, mounded, or partially  
underground, may cover the installation from sight, and shall notify the department, and  
shall submit a notarized affidavit to the department attesting to the fact that the installation  
complies with the installation application submitted and the applicable rules.  
1-8.4 Upon the owner's request, all plans and specifications that are submitted to the  
department for review shall be returned after the department has certified the installation  
or within 30 working days after notification to the department of the completion of the  
installation. Plans and specifications may be marked "Confidential-Do Not Copy" at the  
time they are submitted.  
History: 2008 AACS.  
R 29.7018 Installation application fees and annual certification.  
Rule 18. Sections 1-9 to 1-9.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-9 Installation application fees and annual certification.  
1-9.1 Only an owner of an H2 container system for which an installation  
application is required to be submitted under section 1-8 of the H2 code shall be required  
to pay fees as specified in section 5 of 1941 PA 207, MCL 29.5.  
1-9.2 For the purpose of assessing fees on permanent installations, each 26,000 scf storage  
capacity of H2 or increment thereof, shall be considered a container or any container filling  
location, as used in section 5 of 1941 PA 207, MCL 29.5.  
History: 2008 AACS.  
R 29.7019 Personnel.  
Rule 19. Sections 1-10 to 1-10.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
Page 10  
1-10 Personnel.  
1-10.1 In the interest of safety, all persons involved in handling H2 shall be trained in the  
proper handling and operating procedures. This training shall be acceptable to the  
department.  
Exception: This training is not required for a person dispensing H2 into a vehicle at an  
attended self-service facility.  
History: 2008 AACS.  
Chapter 2 Design of Gaseous Hydrogen Systems  
R 29.7020 Containers.  
Rule 20. Section 2-1.3 is reproduced from NFPA 50A, and sections 2-1, 2-1.1, 2-1.2, and  
2-1.4 to 2-1.8.2 of the storage and handling of gaseous and Liquefied H2 code are added as  
follows:  
2-1 Containers.  
2-1.1 H2 containers shall comply with 1 of the following:  
(a) Designed, constructed, and tested in accordance with appropriate requirements of  
ASME International, "Boiler and Pressure Vessel Code," Section VIII, "Rules for the  
construction of pressure vessels," adopted by reference in section 8-1.  
(b) Designed, constructed, tested, and maintained in accordance with Title 49, CFR.  
(c) Metal hydride storage systems shall be listed for the application and designed in a  
manner that prevents the removal of the metal hydride.  
(d) When allowed by the department, fully over-wrapped carbon composite containers  
designed to a standard acceptable to the department based on the best interest of public  
health, safety, and the environment.  
2-1.2 Permanently installed aboveground containers shall be provided with substantial  
supports, constructed of noncombustible material on firm foundations of noncombustible  
material, and shall comply with the following subsections as applicable:  
(a) Steel supports in excess of 18 inches (45.72 centimeters) in height, shall have a  
minimum 2-hour fire resistance rating, see figure 2-1.2.  
Exception: Supports may be greater than 18 inches (45.72 centimeters) if owner  
demonstrates, to the satisfaction of the department, that the container will not be exposed  
to a 2-hour pool fire.  
(b) If a permanently installed aboveground container is in an area that is subject to buoyant  
forces, provision shall be made to prevent the container, either full or empty, from floating  
during a rise in water level, including up to the established maximum flood stage.  
(c) Horizontally installed containers shall have not more than 2 points of support  
longitudinally or other methods approved by the department based on the best interest of  
public health, safety, and welfare and the environment.  
(d) Horizontally installed containers shall not be in direct contact with each other.  
(e) Composite containers shall be protected from UV radiation as required in the  
manufacturer's specifications.  
(f) Aboveground containers shall be protected by painting or other equivalent means  
where necessary to inhibit corrosion.  
Page 11  
Exception: Composite containers shall not be painted without prior permission from the  
container manufacturer.  
(g) Welding or brazing for the repair or alteration of an ASME pressure vessel shall  
comply with the standard adopted in section 8-1.2.1.  
(h) Other welding or brazing shall be permitted only on saddle plates, lugs, or brackets  
which are attached to the pressure vessel by the pressure vessel manufacturer.  
(i) The exchange or interchange of pressure vessel appurtenances intended for the same  
purpose shall not be considered a repair or alteration and appurtenances must comply with  
these rules.  
2-1.3 Each portable container shall be legibly marked with the name hydrogen in  
accordance with ANSI/CGA C-4, Method of Marking Portable Compressed Gas  
Containers to Identify the Material Contained. Each manifold hydrogen supply unit shall  
be legibly marked with the name hydrogen or a legend such as "This unit contains  
hydrogen."  
2-1.4 An owner or operator that has had a container subjected to heat exposure due to fire  
shall remove the container from service, unless the owner or operator provides  
documentation of recertification in accordance with section 2-1.1, to the department  
substantiating container integrity.  
2-1.5 Guard posts or other approved means shall be provided to protect a container system  
subject to vehicular damage. When guard posts are installed, all of the following design  
specifications shall be met:  
(a) Guard posts shall be constructed of steel not less than 4 inches (10.16 centimeters)  
in diameter and shall be filled with concrete.  
(b) Guard posts shall be spaced not more than 4 feet (1.2 meters) on center.  
(c) Guard posts shall be set not less than 4 feet (1.2 meters) deep in a concrete footing that  
is not less than 15 inches (38.1 centimeters) in diameter.  
(d) Guard posts shall be not less than 4 feet (1.2 meters) in height above grade.  
(e) Other means as approved by the department based on the best interests of public health,  
safety, and welfare and the environment.  
Page 12  
2-1.6 Physical protection. Containers, piping, valves, pressure-relief devices, regulating  
equipment, and other appurtenances shall be protected against physical damage and  
tampering.  
2-1.7 Portable containers subject to shifting or upset shall be secured. Nesting may be used  
to secure portable containers.  
2-1.8 Underground containers. Underground containers for the storage of gaseous H2 shall  
be in accordance with this subsection.  
2-1.8.1 Construction. Storage containers for gaseous H2 shall be designed and constructed  
in accordance with Section VIII of ASME International, "Boiler and Pressure Vessel  
Code," adopted by reference in section 8-1, and shall be vacuum-jacketed in accordance  
with section 2-1.10.1.1.  
2-1.8.2 Corrosion Protection. The underground container shall be protected by an  
engineered corrosion protection system designed by a corrosion expert. If cathodic  
protection is used the maintenance schedule shall meet the requirements of section 5-4.  
History: 2008 AACS.  
R 29.7021 Pressure relief devices.  
Rule 21. Section 2-2.3 is reproduced from NFPA 50A, and sections 2-2, 2-2.1, 2-2.2, and  
2-2.4 to 2-2.7.1 of the storage and handling of gaseous and Liquefied H2 code are added as  
follows:  
2-2 Pressure relief devices.  
2-2.1 H2 containers shall be protected from credible overpressure scenarios by a relief  
device installed in accordance with the ASME International, "Boiler Pressure Vessel  
Code," section VIII division 1 sections UG 125 through 137, adopted by reference in  
section 8-1. When all credible overpressure sources are external to the container, the relief  
device(s) need not be installed directly on the container. In such cases, the relief devices  
may be installed in the piping between the container and the source(s) of overpressure and  
a block valve may be installed between the relief device(s) and container, provided the  
source of overpressure is blocked from the container.  
2-2.1.1 Fully over-wrapped carbon composite containers shall be protected by thermally  
activated pressure relief devices acceptable to the department based on the best interests of  
public health, safety, welfare and the environment.  
2-2.2 Pressure relief devices, when installed, shall be arranged to discharge upward and  
unobstructed to the open air in such a manner as to prevent any impingement of escaping  
gas upon the container, adjacent structures, or personnel. The vent and piping system from  
relief device(s) shall be designed and installed in accordance with CGA G-5.5.  
2-2.3 Pressure relief devices or vent piping shall be designed or located so that moisture  
cannot collect and freeze in a manner that would interfere with proper operation of the  
device.  
2-2.4 Pressure relief valves for gaseous H2 service shall not be fitted with manual relief  
(lifting devices).  
2-2.5 Pressure relief valves for gaseous H2 systems, if externally adjustable, shall be  
provided with a means for sealing the adjustment to prevent tampering.  
Page 13  
2-2.5.1 If at any time it is necessary to break such a seal, the valve shall be removed from  
service until it has been reset and sealed in accordance with design, certification, and  
installation code specified in section 2-2.1.  
2-2.6 Pressure relief valves shall be tested at least every 5 years.  
Exception: Non-ASME relief valves used for blocked-in portions of piping as thermal  
relief valves will not be tested.  
2-2.7 Excess flow control shall be provided for pressurized H2 piping systems above 15  
psig when system design allows their application to add a significant measure of safety for  
break, rupture, or open valve (to atmosphere) conditions.  
2-2.7.1 The location of excess flow control shall be as specified as in either of the following  
situations:  
(a) Where piping originates from a source located in a room or area, the excess flow  
control shall be located within the same room or area.  
(b) Where piping originates from a bulk source, the excess flow control shall be as close  
to the bulk source as possible.  
Exception: The above requirements shall not apply to piping for inlet connections designed  
to prevent backflow, piping pressure relief devices, or systems containing 450 scf of H2  
gas or less.  
History: 2008 AACS.  
R 29.7022 Piping, tubing, and fittings.  
Rule 22. Sections 2-3.1 is reproduced from NFPA 50A, and sections 2-3.1.1, 2-3.1.2, and  
2-3.2 to 2-3.13 of the storage and handling of gaseous and Liquefied H2 code are added as  
follows:  
2-3 Piping, tubing, and fittings.  
2-3.1 Piping, tubing, and fittings shall be suitable for H2 service and for the pressures and  
temperatures involved. Cast-iron pipe and fittings shall not be used.  
2-3.1.1 A piping system shall be substantially supported and protected against physical  
damage and excessive stresses arising from settlement, vibration, expansion, or  
contraction. Supports for aboveground piping shall be constructed of noncombustible  
material.  
2-3.1.2 Aboveground piping systems shall be protected from corrosion in compliance with  
recognized standards. Underground piping systems shall be in compliance with section 5-  
4.  
2-3.2 Material specifications and thickness requirements for piping and tubing shall  
conform to ASME B31.3, "Process Piping," adopted by reference in section 8-1.  
2-3.3 Brazing materials shall have a melting point above 1,000 degrees Fahrenheit (538  
degrees Celsius). Flanged connection shall use a gasket that is suitable for H2. When  
making joints in piping and tubing, thread sealants, when used, shall be suitable for H2  
service and shall be applied to male pipe threads prior to assembly.  
2-3.4 Aboveground piping systems shall be marked in accordance with the following:  
(a) Marking shall include the name of the gas and direction of flow arrow.  
(b) Marking for piping systems shall be provided at the following locations:  
(i) At each critical process control valve.  
(ii) At wall, floor, or ceiling penetrations.  
Page 14  
(iii) At each change in direction.  
(iv) At a minimum of every 20 feet (6.1 meters) or fraction thereof throughout the piping  
run.  
2-3.5 Threaded or flanged connections shall not be used in areas other than outdoors.  
2-3.6 Underground piping shall be installed on a bedding of at least 6 inches (15.24  
centimeters) of well-compacted backfill material.  
2-3.7 In areas subject to vehicle traffic, the pipe trench shall be of sufficient depth to permit  
a cover of not less than 18 inches (45.72 centimeters) of well compacted backfill material  
and pavement.  
Exception 1: In paved areas where a minimum of 8 inches (20.32 centimeters) of asphalt  
paving is used, the depth of the backfill between the topmost tier of piping and the paving  
may be reduced to not less than 8 inches (20.32 centimeters).  
Exception 2: In paved areas where a minimum of 6 inches (15.24 centimeters) of reinforced  
concrete paving is used, the depth of backfill between the topmost tier of the piping and  
the paving may be reduced to not less than 4 inches (10.16 centimeters).  
2-3.8 In areas not subject to vehicle traffic, the pipe trench shall be of sufficient depth to  
permit 6 inches (15.24 centimeters) each of bedding and cover of well-compacted backfill  
material. A greater burial depth shall be provided when required by the manufacturer's  
instructions.  
2-3.9 Piping within the same trench shall be separated by more than 3 times the diameter  
of the larger adjacent pipe.  
2-3.10 Piping to equipment shall be provided with an accessible, manual shutoff valve.  
2-3.11 Pipe, tubing, fittings, and other piping components shall be capable of withstanding  
a hydrostatic test of at least 3 times the rated service pressure without structural failure as  
documented by the manufacturer.  
2-3.12 All natural gas piping shall be installed in accordance with R 29.4601 et seq.  
2-3.13 All liquefied petroleum gas piping shall be installed in accordance with R 29.4001  
et seq.  
History: 2008 AACS.  
R 29.7023 Equipment assembly.  
Rule 23. Sections 2-4 to 2-4.6 are reproduced from NFPA 50A, and sections 2-4.7 to 2-  
4.10 of the storage and handling of gaseous and Liquefied H2 code are added as follows:  
2-4 Equipment assembly.  
2-4.1 Valves, gauges, regulators, and other accessories shall be recommended for H2  
service by the manufacturer or the H2 supplier.  
2-4.2 Installation of H2 systems shall be supervised by personnel familiar with proper  
practices with reference to their construction and use.  
2-4.3 Storage containers, piping, valves, regulating equipment, and other accessories shall  
be accessible and shall be protected against physical damage and against tampering by the  
general public.  
2-4.4 Cabinets or housings containing H2 control or operating equipment shall be ventilated  
to minimize accumulation of H2.  
2-4.5 Each mobile H2 supply unit used as part of an H2 system shall be secured to prevent  
movement.  
Page 15  
2-4.6 Mobile H2 supply units shall be electrically bonded to the system before discharging  
H2.  
2-4.7 Emergency shutoff valves shall be approved and shall incorporate all of the following  
means of closing:  
(a) Automatic shutoff through thermal (fire) actuation. Where fusible elements are used,  
they shall have a melting point not exceeding 250 degrees Fahrenheit (121 degrees  
Celsius).  
(b) Manual shutoff from a remote location.  
(c) Manual shutoff at the installed location.  
2-4.8 The fill line, when it is independent of the withdraw line on a storage container, shall  
be equipped with a backflow check valve located as close as practical to the container to  
prevent discharge of H2 from the container in case of the rupture of the line, hose, or  
fittings.  
2-4.9 Where excess-flow check valves are used, the closing flow shall be greater than the  
maximum system design flow rate and less than the flow rating of the piping system that  
results from a complete line failure between the excess-flow check valve and the equipment  
downstream of the excess-flow check valve.  
2-4.10 Gas piping from an outdoor compressor or storage system into a building shall be  
provided with shutoff valves located outside the building. The shutoff valves shall be  
readily accessible and as close as practical to the building. Each valve shall be permanently  
identified.  
History: 2008 AACS.  
R 29.7024 Marking.  
Rule 24. Sections 2-5 to 2-5.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-5 Marking. Gaseous H2 containers and systems shall be marked in accordance with this  
section.  
2-5.1 Identification of contents. Each container shall be marked as follows: "GASEOUS  
HYDROGEN - FLAMMABLE GAS" in letters that are not less than 3 inches (76  
millimeters) in height.  
2-5.2 Container specification. Stationary containers shall be marked with the  
manufacturing specification and maximum allowable working pressure on a permanent  
nameplate in accordance with the standard to which the container was manufactured.  
2-5.3 Portable containers. Portable containers shall be marked in accordance with CGA C-  
7, "Guide to the Preparation of Precautionary Labeling and Marking of Compressed Gas  
Containers," adopted by reference in section 8-1.  
2-5.4 Stationary containers. Stationary containers shall be marked in accordance with  
NFPA 704, "Standard Systems for the Identification of the Hazards of Materials for  
Emergency Response," adopted by reference in section 8-1.  
History: 2008 AACS.  
R 29.7025 Testing.  
Page 16  
Rule 25. Section 2-6 is reproduced from NFPA 50A, and section 2-6.1 of the storage and  
handling of gaseous and Liquefied H2 code is added as follows:  
2-6 Testing. After installation, all piping, tubing, and fittings shall be tested and proved H2  
gas-tight at maximum operating pressure.  
2-6.1 Containers, if out of service in excess of 1 year, shall be inspected and tested as  
outlined in section 2-6. The pressure relief devices shall be checked to determine if they  
are operable and properly set.  
History: 2008 AACS.  
R 29.7026 Approval.  
Rule 26. Sections 2-7 and 2-7.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-7 Approval.  
2-7.1 Systems and all system components shall be listed or approved, including, but not  
limited to all of the following:  
(a) Container.  
(b) Pressure relief device, including a pressure relief valve.  
(c) Pressure gauge.  
(d) Pressure regulator.  
(e) Valve.  
(f) Hose and hose connection.  
(g) Vehicle fueling connection.  
(h) Electrical equipment related to the H2 system.  
(i) Dispenser.  
(j) Emergency shutoff valves.  
(k) Metal hydride storage.  
(l) Gas detection equipment and alarms.  
(m) H2 generators.  
(n) Pumps or compressor.  
(o) Stationary engine fuel system.  
History: 2008 AACS.  
R 29.7027 Pressure gauges.  
Rule 27. Section 2-8 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
2-8 Pressure gauges. A pressure gauge, if provided, shall be capable of reading at least 1.2  
times the system MAWP.  
History: 2008 AACS.  
R 29.7028 Pressure regulators.  
Page 17  
Rule 28. Sections 2-9 to 2-9.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-9 Pressure regulators.  
2-9.1 A pressure regulator inlet and each chamber shall be designed for its service pressure  
with a safety factor of at least 3.  
2-9.2 Pressure chambers shall provide for overpressure relief, if required.  
2-9.3 Regulators shall be designed, installed, or protected so that their operation is not  
affected by freezing rain, sleet, snow, ice, mud, insects, or debris. Regulator protection may  
be integral with the regulator.  
History: 2008 AACS.  
R 29.7029 Valves.  
Rule 29. Sections 2-10 to 2-10.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-10 Valves.  
2-10.1 Shutoff valves shall have a rated service pressure not less than the rated service  
pressure of the entire system and shall be capable of withstanding a hydrostatic test of at  
least 3 times the rated service pressure without rupture.  
2-10.1.1 Leakage shall not occur when tested at least 1.1 times the rated service pressure,  
using an inert gas compatible with industry practices.  
2-10.2 Valves of a design that allows the valve stem to be removed without removal of the  
complete valve bonnet or without disassembly of the valve body shall not be used.  
History: 2008 AACS.  
R 29.7030 Hose and hose connections.  
Rule 30. Sections 2-11 to 2-11.6 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-11 Hose and hose connections.  
2-11.1 Hose shall be constructed of or lined with materials that are resistant to corrosion  
and compatible with H2.  
2-11.2 Hose, metallic hose, flexible metal hose, tubing, and their connections shall be  
designed for the most severe pressures and temperatures expected under normal operating  
conditions with a burst pressure of at least 3 times the service pressure.  
2-11.3 Prior to use, hose assemblies shall be tested by the manufacturer or  
its designated representative at a pressure at least 1.1 times the service pressure.  
2-11.4 Hose and metallic hose shall be distinctly marked by the manufacturer  
either by the manufacturer's permanently attached tag or by distinct markings indicating  
the manufacturer's name or trademark, applicable service identifier and design pressure.  
2-11.5 The use of hose in an installation shall be limited to only the following applications:  
(a) Vehicle fueling hose.  
(b) Inlet connection to compression equipment.  
(c) Section of metallic hose not exceeding 36 inches in length in the pipeline to provide  
flexibility where necessary.  
Page 18  
2-11.6 Each section shall be so installed that it is protected against mechanical damage and  
is readily visible for inspection.  
History: 2008 AACS.  
R 29.7031 Vehicle fueling connection.  
Rule 31. Sections 2-12 to 2-12.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-12 Vehicle fueling connection.  
2-12.1 Fueling receptacles and nozzles for gaseous H2 service shall be listed or approved  
in accordance with a standard acceptable to the department and based on the best interest  
of public health, safety, and welfare and the environment.  
2-12.2 The use of adapters shall be prohibited.  
History: 2008 AACS.  
R 29.7032 Temporary installations.  
Rule 32. Sections 2-13 and 2-13.1 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
2-13 Temporary installations.  
2-13.1 ASME or U.S. DOT containers that are used as portable storage containers, (see  
definition of portable container in section 1-5), for temporary, less than 6 months at any  
given location, stationary service shall comply with the following:  
(a) If mounted on legs or supports, then such supports shall be of steel and either shall be  
welded to the container by the manufacturer at the time of fabrication or shall be attached  
to lugs that have been so welded to the container. The legs or supports or the lugs for the  
attachment of these legs or supports shall be secured to the container in accordance with  
the code or rule under which the container was designed and built to withstand loading in  
any direction equal to twice the weight of the empty container and attachments.  
(b) If the container is mounted on a trailer or semi-trailer running gear so that the unit can  
be moved by a conventional over-the-road tractor, then attachment to the vehicle, or  
attachments to the container to make it a vehicle, shall comply with the appropriate U.S.  
DOT requirements for cargo tank service. The unit also shall comply with applicable state  
and U.S. DOT motor carrier regulations and shall be approved by the department.  
History: 2008 AACS.  
Chapter 3 Location of Gaseous Hydrogen Systems  
R 29.7033 General requirements.  
Rule 33. Sections 3-1.1, and 3-1.4 are reproduced from NFPA 50A, and sections 3-1.2,  
3-1.3, and 3-1.5 to 3-1.10 of the storage and handling of gaseous and Liquefied H2 code  
are added as follows:  
Page 19  
3-1 General requirements.  
3-1.1 The system shall be located so that it is accessible to delivery equipment and to  
authorized personnel. Roadways or other means of access for emergency equipment, such  
as fire department apparatus, shall be provided.  
3-1.2 Above ground systems shall be located either at grade or above grade.  
3-1.3 Aboveground systems shall not be located beneath or where exposed to failure of the  
following:  
(a) Electric power lines as follows:  
(i) Not less than 50 feet (15.24 meters) horizontally from the vertical plane below the  
nearest overhead wire of an electric trolley, train, or bus line.  
(ii) Not less than 5 feet (1.52 meters) horizontally from the vertical plane below the nearest  
overhead electrical wire.  
(b) Piping containing all classes of flammable or combustible liquids, see definition in  
Section 1-5.  
(c) Piping containing oxidizing materials.  
3-1.4 Systems within 50 feet (15.24 meters) of aboveground storage of all classes of  
flammable and combustible liquids shall be located on ground higher than such storage,  
except where dikes, diversion curbs, grading, or separating solid walls are used to prevent  
accumulation of these liquids under the system.  
3-1.5 Underground systems shall be located underground, mounded, or partially buried and  
outside of any buildings. Buildings shall not be constructed over any underground,  
mounded, or partially buried container. Sides of adjacent containers shall be separated by  
not less than 3 feet (1 meter) unless approved by the department.  
(a) Excavation for underground, mounded, or partially buried containers shall be made  
with due care to avoid damage to an existing structure or its foundation. Containers shall  
not be installed where loads from adjacent structures may be transmitted to the container.  
A structure or foundation of a structure on the same property shall not be erected or  
constructed within 10 feet (3.1 meters) of any point on the container surface, unless the  
footings extend to the bottom of the container. A container shall not be installed less than  
10 feet (3.1 meters) from the nearest wall of any basement, pit, or property line.  
3-1.6 All underground containers shall be set on firm foundation and surrounded with 6  
inches (15.24 centimeters) minimum of noncorrosive inert material such as clean sand or  
pea gravel.  
3-1.7 Underground or mounded containers shall be covered with not less than 2 feet (0.6  
meter) of earth or with not less than 1 foot (30.48 centimeters) of earth on top of which  
shall be placed a reinforced concrete slab not less than 4 inches (10.16 centimeters) thick.  
If containers are likely to be subjected to traffic, they shall be protected against damage  
from vehicles passing over them by at least 3 feet (1 meter) of earth cover plus 6 inches  
(15.24 centimeters) of reinforced concrete. When reinforced concrete paving  
is used as part of the protection, it shall extend at least 1 foot (30.48 centimeters)  
horizontally beyond the outline of the container in all directions  
3-1.8 Containers installed in an area subject to flooding, high water table, or other buoyant  
forces shall be safeguarded from movement by anchoring or other means acceptable to the  
department based on the best interests of public health, safety, and welfare and the  
environment.  
Page 20  
3-1.9 Aboveground gaseous H2 systems shall be fenced and posted to prevent entrance by  
unauthorized personnel.  
Exception: Gaseous H2 dispensers may be located outside the fence.  
3-1.10 Underground installations shall be deemed to provide engineered protection from  
overhead power lines.  
History: 2008 AACS.  
R 29.7034 Specific requirements.  
Rule 34. Sections 3-2.1, 3-2.4, 3-2.5, and table 3-2.1 are reproduced from NFPA 50A,  
and table 3-2.2, sections 3-2.2, 3-2.3 and 3-2.6 to 3-2.9 of the storage and handling of  
gaseous and Liquefied H2 code are added as follows:  
3-2 Specific requirements.  
3-2.1 The location of a system, as determined by the maximum total contained volume of  
H2, shall be in the order of preference as indicated by Roman numerals in table 3-2.1.  
Table 3-2.1  
Preferred Locations of Gaseous Hydrogen Systems  
Nature of Location  
Size of Hydrogen System  
Less than 3500 scf (99 m3) 3500 scf to 15,000 scf In Excess of 15,000 scf (425 m 3)  
(99 m3 to 425 m3)  
Outdoors  
I
I
I
In a separate building  
II  
II  
II  
In a special room  
III  
III  
Not permitted  
Not permitted  
Inside buildings not in a IV  
special room or exposed  
to other occupancies  
Not permitted  
3-2.2 The minimum distance in feet from an H2 system of indicated capacity located either  
outdoors, in separate buildings, or in special rooms to any specified outdoor exposure shall  
be in accordance with table 3-2.2. The distances in numbers 1, 3 to 10, and 14 inclusive in  
table 3-2.2 shall not apply where protective structures having a minimum fire resistance  
rating of 2 hours are located between the system and the exposure.  
(a) An aboveground H2 storage container system shall be erected per table 3-2.2, but not  
less than 50 feet (22.9 meters), from any of the following:  
A school.  
A church.  
A hospital.  
A theater.  
Page 21  
Assembly occupancy for 50 or more persons.  
Exception: The restrictions in section 3-2.2(a) shall not apply to an aboveground H2 system  
used exclusively for stationary power generation.  
Table 3-2.2  
Minimum Distance from Outdoor Gaseous Hydrogen Systems to Exposures  
Total Gaseous Hydrogen Storage  
Type of Outdoor  
Exposure  
Less than  
3500 scf to 15,000 scf In excess  
of 15,000  
3500 scf (99 m3)  
(99 m3 to 425 m3)  
Feet  
scf (425  
m3)  
(meter)  
Feet  
(meter)  
Feet  
(meter)  
1. Building or structure  
(a) Wall(s) adjacent to system  
constructed of noncombustible or  
limited-combustible materials  
0a (0)  
5a (1.5)  
5a (1.5)  
(1) Sprinklered building or structure  
or unsprinklered building or  
structure having noncombustible  
contents  
(2) Unsprinklered building or  
structure with combustible contents  
Adjacent wall(s) with fire resistance  
rating less than 2 hoursb  
Adjacent wall(s) with fire resistance  
rating of 2 hours or greaterb  
(b) Wall(s) adjacent to system  
constructed of other than  
noncombustible or  
0c (0)  
0 (0)  
10 (3.1)  
5 (1.5)  
25d (7.6)  
5 (1.5)  
10 (3.1)  
25 (7.6)  
50d (15.2)  
limited-combustible materials  
2. Wall openings  
(a) Not above any part of a system 10 (3.1)  
10 (3.1)  
25 (7.6)  
10 (3.1)  
25 (7.6)  
(b) Above any part of a system  
3. All classes of flammable and  
combustible liquids above ground  
(a) 0-1000 gal (3785L)  
(b) In excess of 1000 gal (3785L)  
4. All classes of flammable and  
combustible liquids below ground  
0-100 gal (3785L)e  
25 (7.6)  
10 (3.1)  
25 (7.6)  
25 (7.6)  
25 (7.6)  
50 (15.2)  
50 (15.2)  
10 (3.1)  
25 (7.6)  
10 (3.1)  
25 (7.6)  
10 (3.1)  
25 (7.6)  
(a) Tank  
(b) Vent or fill opening of tank  
Page 22  
5. All classes of flammable and  
combustible liquids below ground –  
in excess of 1000 gal (3785L)e  
(a) Tank  
20 (6.1)  
25 (7.6)  
20 (6.1)  
25 (7.6)  
20 (6.1)  
25 (7.6)  
(b) Vent of fill opening of tank  
6. Flammable gas storage (other  
than H2), either high pressure or low  
pressure  
10 (3.1)  
25 (7.6)  
25 (7.6)  
25 (7.6)  
(a) 0-15,000 scf (255 me) capacity  
(b) In excess of 15,000 scf (255  
me) capacity  
50 (15.2)  
50 (15.2)  
7. Oxygen storage  
Refer to NFPA 51, Standard for the Design and Installation of  
Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied  
Processes  
Refer to NFPA 55, Standard for the Storage, Use, and Handling  
of Compressed Gases and Cryogenic Fluids in Portable and  
Stationary Containers, Cylinders, and Tanks  
(a) 20,000 scf (566 me) or less  
(b) More than 20,000 scf (566 me)  
8. Fast-burning solids such as  
ordinary lumber, excelsior, or paper  
9. Slow-burning solids such as  
heavy timber or coal  
50 (15.2)  
25 (7.6)  
25 (7.6)  
50 (15.2)  
50 (15.2)  
25 (7.6)  
25 (7.6)  
50 (15.2)  
50  
(15.2)  
25  
(7.6)  
25  
(7.6)  
50  
(15.2)  
10. Open flames and welding  
11. Air compressor intakes or inlets  
to ventilating or air-conditioning  
equipment  
12. Places of public assembly less  
than 50 people  
13 Public sidewalks and parked  
vehicles  
14 Line of adjoining property that  
can be built upon  
25 (7.6)  
15 (4.6)  
5 (1.5)  
50 (15.2)  
15 (4.6)  
5 (1.5)  
50  
(15.2)  
15  
(4.6)  
5 (1.5)  
15. Flammable/Combustible liquid  
dispenser  
16. Public Way, driveway  
10 (3.1)  
15 (4.6)  
50 (15.2)  
10 (3.1)  
15 (4.6)  
50 (15.2)  
10  
(3.1)  
15  
(4.6)  
50  
17. Railroad  
(15.2)  
a Portions of wall less than 10 ft (3m) (measured horizontally) from any part of a system shall have a  
fire resistance rating of at least Â½ hour.  
bExclusive of windows and doors (see number 2 of Table 3-2.2).  
cPortions of walls less than 10 ft (3m) (measured horizontally) from any part of a system shall have a  
fire resistance rating of at least 1 hour.  
dBut not less than 1/2 the height of adjacent wall of building or structure.  
eDistances can be reduced to 15 ft (4.5m) for Class IIIB combustible liquids.  
3-2.2.1 Loose or piled combustible material and weeds and long dry grass shall not be  
within 10 feet (3.1 meters) of any system.  
Roof top storage.  
Page 23  
Construction of the building/roof that carries the load of the storage tank must carry a  
minimum 1-hour fire rating.  
System must be securely mounted to roof.  
System must be located to allow for inspection of the system acceptable to the department  
based on the best interest of public health, safety, and welfare and the environment.  
3-2.3 Unloading connections on delivery equipment shall not be positioned closer to any  
of the exposures cited in table 3-2.2 than the distances given for the storage system.  
(a) H2 transfer between cargo transport vehicle and stationary container systems (single  
or multiple containers utilizing a common or manifolded transfer line), shall comply with  
all of the following:  
(i) Owners and operators shall ensure that fixed piping is used between the container and  
master shutoff and check valves. The piping and manifolds shall be secured to the container  
frame. Flexible hoses are only permitted between the check valve and the cargo vehicle  
unloading connection.  
(ii) Emergency shutoff valves required in this section shall be tested annually for proper  
operation. The results of the tests shall be documented.  
(iii) All installations shall have at least 1 clearly identified and easily accessible manually  
operated remote emergency shutoff device. Within 1 year after the effective date of these  
rules, existing installations shall have at least 1 clearly identified and easily accessible  
manually operated remote emergency shutoff device. The emergency shutoff device shall  
be located not less than 20 feet (6.1 meters) nor more than 100 feet (30.5 meters) in the  
path of egress from the emergency shutoff valve and not less than 20 feet (6.1 meters) from  
the container system.  
(iv) During transfer of H2 to and from cargo vehicles, the hand or emergency brake of the  
vehicle shall be set, and chock blocks shall be used to prevent rolling of the vehicle.  
(v) Transfer systems shall be capable of depressurizing to facilitate disconnection. Bleed  
connections shall lead to a safe point of discharge.  
(vi) Cargo vehicle shall be equipped with air-brake interlock in front of the unloading  
connection to protect against drive-away.  
(b) The delivery vehicle shall be located so that all parts of the vehicle are on the premises  
when delivery is made. Check valves shall be located as close to the container as practical.  
(i) Sources of ignition shall not be permitted in the unloading area while transfer is in  
progress.  
3-2.4 H2 systems of less than 3500 scf (99 m3), where located inside buildings and exposed  
to other occupancies, shall be situated in the building so that the system will be as follows:  
(a) In an adequately ventilated area as in 4-2.2.  
(b) 20 feet (6.1 meters) from all classes of flammable and combustible liquids, oxidizing  
gases, and readily combustible materials, such as excelsior and paper.  
(c) 25 feet (7.6 meters) from open flames, ordinary electrical equipment, or other sources  
of ignition .  
(d) 50 feet (15.24 meters) from intakes of ventilation or air-conditioning equipment and  
air compressors.  
(e) 50 feet (15.24 meters) from other flammable gas storage.  
(f) Protected against damage or injury due to falling objects or working activity in the  
area. More than one system of 3500 scf (99 cubic meters) or less shall be permitted to be  
installed in the same room, provided the systems are separated by at least 50 feet (15.24  
Page 24  
meters) or where a masonry structure having a minimum fire resistance rating of 2 hours  
is located between the systems. Each such system shall meet all of the requirements of this  
section.  
Exception: The separation distance between multiple systems of 3500 scf (99 cubic meters)  
or less shall be permitted to be reduced to 25 feet (7.6 meters) in buildings where the  
occupancy between storage areas is free of combustible materials and protected with a  
sprinkler system designed for Ordinary Hazard, Group 1 occupancies or Light Hazard  
occupancies in accordance with NFPA 13, Standard for the Installation of Sprinkler  
Systems.  
3-2.6 An owner and operator shall ensure that a container system, which is underground,  
mounded, or partially underground, is protected from corrosion by 1 of the following:  
(a) The approved container system is cathodically protected by all the following  
requirements:  
(i) The approved container system is coated with a suitable dielectric material approved  
by the department.  
(ii) Factory-installed or field installed cathodic protection systems are designed by a  
corrosion expert or in accordance with the NACE recommended practice RP0285 entitled  
"Corrosion Control of Underground Storage Tank Systems by Cathodic Protection," or  
impressed current systems are designed to allow a determination of current operating status  
as required in section 5.4-1 of the H2 code.  
(iii) Cathodic protection systems are operated and maintained in accordance with the  
provisions of section 5.4-1 of the H2 code.  
(b) The container is made of nonmetallic construction or corrosion-resistant, such as  
fiberglass or a composite.  
(c) Or other means acceptable to the department and based on the best interest of public  
health, safety, and welfare and the environment.  
3-2.7 Out-of-service aboveground containers.  
Containers that are no longer in service for a period of 12 months shall be closed. To close  
the aboveground container, the owner or operator shall empty the container, purge it with  
an inert gas and safeguard it against tampering. Piping that is removed from service shall  
be purged with nitrogen and capped or removed.  
3-2.7.2 Each container that is to be reused at the original location or a new location shall  
be purged with an inert gas and be in compliance with all the requirements for the  
installation of a new container, and shall be recertified by the manufacturer or authorized  
representative, and tested in accordance with the container's design specifications or be  
pressure tested with an inert gas or H2 at 1.1 times the MAWP for not less than 10 minutes.  
Piping that is to be reused shall comply with all the requirements for the installation of new  
piping and shall be tested in compliance with section  
3-2.9 of this code prior to being brought back into service.  
3-2.8 Out-of-service underground, mounded, and partially buried containers.  
3-2.8.1 Containers that are no longer used to store H2 and are not intended to be brought  
back into service shall be permanently closed. To permanently close the container, the  
container shall be emptied and purged with an inert gas to render the container free of H2,  
and then the container shall be removed from the ground. When a structure above or near  
the container prevents removal, the container shall be emptied and purged with an inert gas  
to render the container free of H2, then the container shall be filled with an inert solid  
Page 25  
material. Piping that is permanently removed from service shall be purged with an inert  
gas and capped or removed.  
3-2.8.2 Containers may be rendered temporarily out-of-service only when it is intended  
they be brought back into service at a later date. To temporarily close a container, all of the  
following requirements shall be met:  
(a) The container shall be emptied and purged with an inert gas.  
(b) Corrosion protection for the container and all underground piping shall be maintained  
in compliance with section 5-4.1 of this code.  
(c) The vent line shall remain functional.  
(d) The container shall be secured against tampering.  
(e) Piping that is temporarily removed from service shall be purged with an inert gas and  
capped.  
3-2.8.2.1 Each container that is temporarily out of service for greater than 12 months shall  
be pressure tested with an inert gas at 1.1 times the MAWP for not less than 10 minutes  
prior to being brought into service. Temporarily out of service piping shall be tested in  
compliance with section 3-2.9 of this code prior to being brought back into service.  
3-2.9 Testing. After installation, prior to being placed into service, all container  
connections and all fielderected piping, tubing, hose, and hose assemblies shall be tested  
and proved H2 gas-tight for the rated pressure, volume, and temperature of the gas  
transported by an approved method as outlined in ASME B31.3, "Process Piping," adopted  
by reference in section 8-1, or the following:  
(a) Perform a pressure test at 1.1 times MAWP, a minimum of 10 minutes.  
(b) During pressure test, check for pressure decay. If leakage is detected, use leak  
detection fluid to find local leaks. Energize the piping with H2 at the MOP, and check for  
local leaks with a "sonic tester," "sniffer," or method acceptable to the department based  
on the best interests of public health, safety, welfare and the environment. If the test "fails"  
the requirements in subsections (a), (b), or (c) of this section, the system must be purged  
with an inert gas, repaired, and subsections (a), (b), and (c) of this section shall be repeated  
until the test "passes."  
History: 2008 AACS.  
R 29.7035 Vaults for aboveground containers.  
Rule 35. Sections 3-3 to 3-3.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-3 Vaults for aboveground containers. Vaults may be installed aboveground, underground  
or partially buried.  
3-3.1 General. Aboveground containers may be installed in vaults that meet the  
requirements of section 3-3. Except as modified by the provisions of section 3-3, vaults  
shall meet all other applicable provisions of these rules.  
3-3.2 Vault design and construction. Vaults shall be designed and constructed to meet the  
following requirements:  
(a) The walls and floor of the vault shall be constructed of reinforced concrete at least 6  
inches (15.24 centimeters) thick.  
(b) The top of an aboveground vault shall be constructed of noncombustible material and  
shall be designed to be weaker than the walls of the vault to ensure that, in the event of any  
Page 26  
explosion, the thrust occurring inside the vault is directed upward before destructive  
internal pressure develops within the vault. The top of an at-grade or below-grade vault  
shall be designed to relieve or contain the force of any explosion occurring inside the vault.  
The walls of a vault, which are partially below-grade, shall extend not less than 4 feet (1.2  
meters) above grade.  
(c) The top and floor of a below-grade vault and the container foundation shall be  
designed to withstand all anticipated loading from vehicular traffic, where applicable.  
(d) The walls and floor of a below-grade vault shall be designed to withstand anticipated  
soil and hydrostatic loading. The vault shall be liquid tight.  
(e) Adjacent vault may share a common wall.  
(f) The vault enclosure shall not have openings except those necessary for access to,  
inspection of, and filling, emptying, and venting of the container.  
(g) When required, the vault shall be designed to be wind and earthquake resistant, in  
accordance with good engineering practice.  
(h) The vault shall be provided with an open and continuous vent to provide ventilation  
to dilute, disperse, and remove any vapors. This continuous vent line shall terminate 12  
feet (3.7 meters) abovegrade.  
(i) Each vault shall be provided with a means for personal entry, which shall only be at  
the top of the vault to allow for the visual inspection of the container and piping surfaces.  
At each entry point, a warning sign that indicates the need for procedures for safe entry  
into a confined space shall be posted. Each entry point shall be secured against  
unauthorized entry and vandalism.  
(j) The vault shall be provided with an approved means to admit a fire suppression agent.  
(k) The loading and unloading transfer connection for abovegrade vaults shall terminate  
outside the vault.  
(l) Provisions shall be made for the normal operation of valves without entering the vault.  
(m) A vault shall be located not less than 15 feet (4.6 meters) from buildings and property  
lines.  
(n) Container selection and arrangement. Containers shall be listed for aboveground use.  
Each container or manifolded system, shall be in its own vault and shall be completely  
enclosed by the vault, and securely fastened to the floor of the vault. Sufficient clearance  
between the container and the vault shall be provided to allow for visual inspection and  
maintenance of all the vault surfaces as well as the tank and its appurtenances.  
(o) The vault shall be provided with a continuous H2 gas leak detection device with an  
audible alarm set at 25% of the LEL and will render the system inoperable. The H2 leak  
detection device shall function during system maintenance operations.  
History: 2008 AACS.  
R 29.7036 Location of dispensing operations and equipment.  
Rule 36. Sections 3-4 to 3-4.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-4 Location of dispensing operations and equipment.  
3-4.1 Dispensing equipment located outdoors shall be in accordance with the following:  
Page 27  
(a) Dispensing equipment shall be allowed under weather protection in accordance with  
the requirements of section 4-5 and constructed in a manner that prevents the accumulation  
of H2 gas.  
3-4.2 Gaseous H2 compression and storage equipment located on top of motor fuel-  
dispensing facility canopies shall be in accordance with the following:  
(a) Canopies shall be constructed in accordance with the requirements for weather  
protection found in section 2209.3.2.6 of the International Fire Code.  
(b) Fuel-dispensing areas under canopies shall be equipped throughout with an approved  
automatic sprinkler system. Operation of the fire sprinkler system shall activate the  
emergency functions of the following:  
(i) Operation of the fire sprinkler system shall activate an automatic emergency discharge  
system, which will discharge the H2 gas from the equipment on the canopy top through the  
vent pipe system.  
(ii) Operation of the fire sprinkler system shall activate the emergency shutdown control  
in section 7-6.  
(iii) Approved signage having a minimum of 3-inch (7.62 centimeters) block letters shall  
be affixed on all sides on the exterior of the canopy structure stating either CANOPY TOP  
HYDROGEN STORAGE or using NFPA 704, "Standard System for the Identification of  
Fire Hazards of Materials," 1996 edition, adopted by reference in section 8-1.1.  
(iv) System must be in compliance with section 3-2.2.2.  
3-4.3 Dispensing equipment located outdoors shall be aboveground, shall not be beneath  
electric power lines or where exposed by their failure, and shall be a minimum of 10 feet  
(3.1 meters) from the nearest important building or property line or 20 feet (6.1 meters)  
from any activity that involves a fixed source of ignition.  
3-4.4 Dispensing equipment shall be located so that all parts of the vehicle being served  
are on the premises of the motor fuel dispensing facility.  
3-4.5 Dispensing equipment shall be protected against collision damage by means  
acceptable to the department. Dispensing equipment shall be securely bolted in place.  
Dispensing equipment shall be installed in accordance with manufacturer's instructions.  
History: 2008 AACS.  
R 29.7037 Installation of emergency shutdown equipment.  
Rule 37. Sections 3-5 to 3-5.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-5 Installation of emergency shutdown equipment.  
3-5.1 Breakaway protection shall be provided in a manner such that, if a pull away event  
occurs, H2 gas will cease to flow at any separation.  
3-5.2 A breakaway device shall be installed at every dispensing point. Such a device shall  
be arranged to separate by a force not greater than 150 pounds (75 kilograms), when applied  
in any direction that the vehicle would move. Breakaway devices shall be compatible with  
a standard acceptable to the department.  
History: 2008 AACS.  
Page 28  
Chapter 4 Design considerations at specific locations  
R 29.7038 Outdoor locations.  
Rule 38. Sections 4-1, 4-1.1, and 4-1.2 were reproduced from NFPA 50A as follows:  
4-1 Outdoor Locations.  
4-1.1 Where protective walls or roofs are provided, they shall be constructed of  
noncombustible or limited-combustible materials.  
4-1.2 Electrical equipment within 15 feet (4.6 m) shall be in accordance with Article 501  
of NFPA 70, National Electrical Code®, for Class I, Division 2 locations.  
History: 2008 AACS.  
R 29.7039 Separate buildings.  
Rule 39. Sections 4-2.1, 4-2.4 to 4-2.6 are reproduced from NFPA 50A, and sections 4-  
2.2, and 4-2.3 of the storage and handling of gaseous and Liquefied H2 code are added as  
follows:  
4-2 Separate buildings.  
4-2.1 Separate buildings shall be constructed of noncombustible or limited-combustible  
materials. Windows and doors shall be located so as to be readily accessible in case of  
emergency.  
Exception: Window glazing shall be permitted to be plastic.  
4-2.2 Ventilation to the outdoors shall be provided. Inlet openings shall be located within  
18 inches (30 centimeters) of the floor in exterior walls only. Outlet openings shall be  
located at the high point of the room in exterior walls or roof. Inlet and outlet openings  
shall each have a minimum total area of 1 square foot/1,000 cubic feet (1 square meters/305  
cubic meters) of room volume. Discharge from outlet openings shall be directed or  
conducted to the atmosphere.  
4-2.3 Deflagration venting shall be provided in exterior walls or roof only.  
4-2.3.1 Vents shall be any 1 or any combination of the following:  
(a) Walls of light material.  
(b) Lightly fastened hatch covers.  
(c) Lightly fastened, outward opening doors in exterior walls.  
(d) Lightly fastened walls or roof.  
(e) Other methods in accordance with NFPA 69.  
4-2.3.2 Where applicable, snow loads shall be considered.  
4-2.4 There shall be no sources of ignition from open flames, electrical equipment, or  
heating equipment.  
4-2.5 Electrical equipment shall be in accordance with Article 501 of NFPA 70, National  
Electrical Code, for Class I, Division 2 locations.  
4-2.6 Heating, if provided, shall be by steam, hot water, or other indirect means except that  
electrical heating may be used if in compliance with 4-2.5.  
History: 2008 AACS.  
Page 29  
R 29.7040 Special rooms.  
Rule 40. Sections 4-3.2 to 4-3.6 are reproduced from NFPA 50A, and sections 4-3.1, 4-  
3.7 to 4-3.9, and table 4-3.9 of the storage and handling of gaseous and Liquefied H2 code  
are added as follows:  
4-3 Special rooms.  
4-3.1 Floor, walls, and ceiling shall be constructed of noncombustible or limited-  
combustible materials. Interior walls or partitions shall have a fire resistance rating of at  
least 2 hours, shall be continuous from floor to ceiling, and shall be securely anchored. At  
least 1 wall shall be an exterior wall. Windows and doors shall be located so as to be readily  
accessible in case of emergency.  
Exception: Window glazing may be of plastic.  
4-3.1.1 If access to the room from outside the primary structure is not possible, access from  
within the primary structure shall be made through 1 vapor-sealing 2-hour self-closing fire  
door.  
4-3.2 Ventilation shall be as provided in section 4-2.2.  
4-3.3 Explosion venting shall be as provided in section 4-2.3.  
4-3.4 There shall be no sources of ignition from open flames, electrical equipment, or  
heating equipment.  
4-3.5 Electrical equipment shall be in accordance with Article 501 of NFPA 70, National  
Electrical Code, for Class I, Division 2 locations.  
4-3.6 Heating, if provided, shall be by steam, hot water, or indirect means except that  
electrical heating shall be permitted to be used if in compliance with 4-3.5.  
4-3.7 Room ventilation.  
4-3.7.1 The ventilation shall be at least 1 cubic feet/minute/square feet (0.3 cubic  
meters/minute/square meters) of room area, but not less than 1 cubic foot/minute/12 cubic  
feet (0.3 cubic meters/minute/3.7 cubic meters) of room volume and shall be designed such  
that an accumulation of H2 at a concentration equal to or greater than 25% of the lower  
flammability limit shall not occur in any part of the room.  
4-3.7.2 Where installed, a gas detection system shall be equipped to sound an alarm and  
visually indicate when a maximum of 25% of the lower flammable limit is reached. At  
40% of the lower flammable limit the gas detection system shall shut down the hydrogen  
system and provide notification to the system operator.  
4-3.7.3 Any failure of the ventilation system shall immediately shut down the fueling  
system and provide notification to the system operator. Reactivation of the fueling system  
shall be by manual restart and shall be conducted by trained personnel.  
4-3.7.4 The gas detection system shall function during ventilation system maintenance  
operations.  
4-3.7.5 A ventilation system for a room within or attached to another building shall be  
designed to ensure that all areas serviced by the ventilation system meet performance  
requirements in accordance with section 4-3.7 during the normal operating conditions and  
during alarm conditions.  
4-3.8 Warning signs.  
4-3.8.1 Access doors shall have warning signs with the words "WARNING - NO  
SMOKING – NON ODORIZED FLAMMABLE GAS - NO OPEN FLAMES. The  
wording shall be in plainly legible, bright red letters not less than 1 inch (2.54 centimeters)  
high on a white background.  
Page 30  
4-3.9 Indoor attended fast-fill fueling.  
4-3.9.1 Attended indoor fast-fill fueling system shall be in accordance with subsections (a)  
to (k) of this section.  
(a) Gas storage equipment shall be located outdoors unless approved by the department.  
Gas processing and compression equipment shall be listed or approved for indoor use or  
located outdoors.  
(b) An emergency manual shutdown device shall be located in the dispensing area not  
less than 20 feet (6.1 meters) and not more than 100 feet (30.5 meters) in the path of egress  
from the dispensing area. Actuation of the emergency manual shutdown device shall  
perform in accordance with subsection (h) of this section.  
(c) The dispenser shall be equipped with a gas detection system which shall actuate in  
accordance with subsection (h) of this section when a maximum of 25% of LFL is detected  
(1% H2 in air).  
(d) The dispenser shall be equipped with a leak detection system capable of identifying a  
leak from the dispensing system outside the dispenser housing by conducting a pre-fill  
pressure test. The leak detection must be capable of detecting a minimum leak rate of 1.9  
gallons/minute and shall actuate in accordance with subsection (h) of this section when a  
leak is detected.  
(e) Whether the fill is communicated or non-communicated, the dispensing system must  
be listed, labeled, or approved to insure that the fills are protective of the safety of the  
temperature, pressure and flow rate of the on-board fuel system during fueling.  
(f) The dispensing area shall be equipped with a fire detection system and shall actuate in  
accordance with subsection (h) of this section if a fire is detected.  
(g) A ventilation system shall be installed for the dispensing area. The ventilation system  
shall be capable of delivering ventilation air as provided in section 4.3.7. The ventilation  
system shall operate prior to dispenser operation, during fueling, and for at least 1 minute  
after fueling has been completed. The ventilation flow rate shall be monitored. Failure or  
reduction of the ventilation flow rate below the required flow rate shall shut down the  
dispensing system.  
Exception: A dispensing area ventilation system is not required when the fuel delivery per  
refueling event is less than those listed in table 4-3.9.  
Table 4-3.9  
Maximum fuel delivery per refueling event that  
does not require room ventilation (kg)  
Room Size (m3)  
1000  
2000  
3000  
4000  
0.8  
1.7  
2.5  
3.3  
4.2  
5000  
(h) The actuation of any 1 of the systems listed in subsections (b) to (g) of this section  
shall be in accordance with table 4-3.9, and shall shut down the dispenser, stop the flow of  
gas into the room, and start or continue to run the ventilation system, if required.  
1. Reactivation of the dispenser and gas flow into the room shall be by manual restart and  
shall be conducted by trained personnel.  
Page 31  
(i) Interior walls, doors, and window openings within 15 feet (4.6 meters) of the dispenser  
shall be constructed of materials having a fire rating of at least 2 hours. Wall penetrations  
shall require use of listed fire rated equipment.  
(j) The owner/operator shall not allow hot work/open flames within 15 feet (4.6 meters)  
of the refueling location unless the dispenser is shut down, depressurized, and purged.  
(k) If H2 is to be removed from the vehicle storage system, H2 shall be discharged into a  
closed transfer system or vented outdoors in accordance with CGA G-5.5, "Hydrogen Vent  
Systems", adopted by reference in section 8-1.  
History: 2008 AACS.  
R 29.7041 Indoor H2 storage system location.  
Rule 41. Sections 4-4 to 4-4.6, and table 4-4.1of the storage and handling of gaseous and  
Liquefied H2 code are added as follows:  
4-4 Indoor H2 storage system location.  
4-4.1 H2 systems of less than 3,500 scf (99 cubic meters) and greater than the maximum  
allowable quantity found in table 4.4.1, where located inside buildings outside of special  
rooms, shall be located in the building so that the system will be as follows:  
(a) In a ventilated area in accordance with the provisions of section 4-3.7.  
(b) Separated from incompatible materials.  
(c) 15 feet (4.6 meters) from ordinary electrical equipment, and 25 feet (7.6 meters) from  
open flames or welding or other sources of ignition.  
(d) 50 feet (15.2 meters) from other low-pressure flammable gas storage (less than 500  
psig).  
(e) Protected against damage in accordance with the provisions of section 2.1.5.  
Table 4-4.1 Quantity Thresholds for Gases Requiring Special Provisions  
Unsprinklered areas  
Sprinklered areas  
No gas cabinet, gas Gas cabinet, gas room,  
room, or exhausted or exhausted enclosure  
enclosure  
No gas cabinet, gas  
Gas cabinet, gas  
room, or exhausted  
enclosure  
Material  
room, or exhausted  
enclosure  
Cryogenic liquid  
(flammable or oxidizing)  
45 gal  
90 gal  
90 gal  
180 gal  
14 kg3 (30 lb)  
27 kg3 (60 lb)  
27 kg3 (60 lb)  
55 kg3 (120 lb)  
Flammable gas liquefied  
nonliquefied  
28 m3 (1,000 ft3)  
28 m3 (2,000 ft3)  
28 m3 (2,000 ft3)  
56 m3 (4,000 ft3)  
4-4.2 More than 1 system of 3,500 scf (99 cubic meters) or less shall be permitted to be  
installed in the same room or area outside of special rooms, provided the systems are  
separated by at least 50 feet (15.2 meters), or by a full height fire-resistive partition having  
a minimum fire resistance rating of 2 hours is located between the systems.  
4-4.3 Each system described in section 4-4.2 shall meet all of the requirements of section  
4-4.1.  
4-4.4 The separation distance between multiple systems of 3,500 scf (99 cubic meters) or  
less shall be permitted to be reduced to 25 feet (7.6 meters) in buildings where the space  
Page 32  
between storage areas is free of combustible materials and protected with a sprinkler  
system.  
4-4.5 When sprinkler protection is provided, the area in which H2 is stored or used shall be  
protected with a sprinkler system designed to be not less than that required by NFPA 13,  
"Standard for the Installation of Sprinkler Systems," adopted by reference in section 8-1,  
for ordinary hazard group 2 with a minimum design area of 3,000 square feet (914.4 square  
meters).  
4-4.6 When sprinkler protection is provided, the area in which the H2 is stored or used shall  
be protected with a sprinkler system designed to be not less than that required by NFPA  
13, "Standard for the Installation of Sprinkler Systems," adopted by reference in section 8-  
1, for extra hazard group 1 with a minimum design area of 2,500 square feet (762 square  
meters).  
History: 2008 AACS.  
R 29.7042 Canopies.  
Rule 42. Sections 4-5 to 4-5.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-5 Canopies.  
4-5.1 A container installation that has a canopy or roof shall have prior approval by the  
department based on the best interests of public health, safety, and welfare and the  
environment. This canopy or roof shall not limit the dissipation of heat or dispersion of  
flammable vapors and cannot restrict firefighting access and control.  
4-5.2 A roof or canopy must meet all of the following conditions:  
(a) The lowest elevation of the roof or canopy shall not be less than 4 feet (1.8 meters)  
from the top of the container.  
(b) All container vent(s) are extended through the roof or canopy.  
(c) The roof or canopy is constructed in such a way that it will not allow vapors to  
accumulate under the canopy or roof.  
(d) Be constructed of noncombustible materials  
History: 2008 AACS.  
R 29.7043 Fast-fill station.  
Rule 43. Sections 4-6 to 4-6.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-6 Fast-fill station.  
4-6.1 Each line between a gas storage facility and a dispenser at a fast-fill station shall have  
a valve that closes when 1 of the following occurs:  
(a) The power supply to the dispenser is cut off.  
(b) Any emergency shutdown device at the refueling station is activated.  
4-6.2 A manual shutoff valve shall be provided at a fast-fill station upstream of the  
breakaway device specified in section 3-5, where it is readily accessible to the person  
dispensing H2, unless either of the following occurs:  
Page 33  
(a) The self-closing valve referred to in section 4-6.1 is located immediately upstream of  
the dispenser.  
(b) The dispenser is equipped with a self-closing valve that closes each time the dispenser  
is deactivated or when an emergency device is activated.  
History: 2008 AACS.  
R 29.7044 Vehicle fueling appliances in nonresidential occupancies.  
Rule 44. Sections 4-7 to 4-7.7 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-7 Vehicle fueling appliances (VFA) in nonresidential occupancies.  
4-7.1 VFAs shall not exceed a gas flow of 36 scf/minute.  
4-7.2 VFAs shall be listed.  
4-7.3 VFAs may be used to fill stationary containers at vehicular fueling locations.  
4-7.4 A VFAs installed with storage containers shall comply with the provisions of  
chapters 2, 3, and 4.  
4-7.5 The installation of VFAs at a residence shall comply with the requirements of section  
4-9.  
4-7.6 Where more than 1 VFA are located in a common area, spacing between the VFAs  
shall not be less than 3 feet (1 meter), unless permitted in the manufacturer's  
recommendations.  
4-7.7 Unless specifically permitted in the manufacture's recommendations, multiple VFAs  
shall not be manifolded together on the discharge side.  
History: 2008 AACS.  
R 29.7045 Installation of electrical equipment.  
Rule 45. Sections 4-8 to 4-8.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-8 Installation of electrical equipment.  
4-8.1 Electrical equipment and wiring shall be specified and installed in accordance with  
NFPA 70, "National Electrical Code," adopted by reference in section 8-1.  
4-8.2 Static protection shall be required when gaseous H2 cargo transport vehicles are  
loaded or unloaded. This can be achieved when cargo transport vehicles or marine  
equipment are loaded or unloaded by grounding cable, conductive hose, flexible metallic  
tubing, or pipe connections where both halves of metallic couplings are in contact.  
History: 2008 AACS.  
R 29.7046 Residential fueling facility.  
Rule 46. Sections 4-9 to 4-9.11 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-9 Residential fueling facility (RFF).  
Page 34  
4-9.1 Application. This section applies to the design, construction, installation, and  
operation of an RFF.  
4-9.2 Storage of H2 in quantities not exceeding 3,500 scf (99 cubic meters) at 12,500 psig  
shall be permitted in systems listed by a national recognized testing laboratory.  
4-9.2.1 The RFF may store H2 indoors or outdoors. Indoor storage of H2 shall not exceed  
3,500 scf (99 cubic meters) at 7,700 psig provided that indoor storage is ventilated per  
section 4-3.7, or storage shall be in a separate sealed enclosure ventilated directly to  
outdoors.  
4-9.3 System component qualifications. System components not part of a listed fueling  
appliance shall comply with the appropriate provisions of chapter 2.  
4-9.3.1 Fueling appliances shall be listed.  
4-9.4 General safety requirements. All equipment related to RFF installation shall be  
protected to minimize the possibilities of physical damage and vandalism. The use of an  
enclosure for the compressor package, similar to that of a central air conditioner, shall be  
permitted to satisfy this requirement.  
4-9.4.1 All equipment related to RFF installation shall be designed for the pressure,  
temperature, and service expected.  
4-9.4.2 Vehicles shall not be considered a source of ignition.  
Exception: Vehicles containing fuel-fired equipment, such as recreational vehicles, shall  
be considered a source of ignition unless this equipment is shutoff completely before  
entering an area in which ignition sources shall not be permitted.  
4-9.4.3 Unless specifically permitted in the manufacturer's recommendations, multiple  
RFFs shall not be manifolded together on the discharge side.  
4-9.4.4 Where more than 1 RFF is located in a common area, spacing between the RFFs  
shall not be less than 3 feet (1 meter) unless permitted by the manufacturer's  
recommendations.  
4-9.5 Installation.  
4-9.5.1 General. All RFF equipment shall include manufacturer's recommendations and  
such recommendations shall include, but may not be limited to, the requirements for the  
proper installation, operation, and maintenance of the RFF. The RFF shall be installed,  
operated, and maintained in accordance with the manufacturer's recommendations.  
4-9.5.1.1 The RFF shall have a nameplate marked with minimum and maximum gas inlet  
pressure and flow rate, gas outlet maximum pressure, and electrical requirements.  
4-9.5.2 Indoors. Where it is necessary to install the compression unit and refueling  
connections indoors, the compression unit shall be mounted or otherwise located such that  
the compression unit is vented outdoors.  
4-9.5.2.1 Where the RFF or the vehicle being fueled is located indoors, a gas detector set  
to operate at 1/5 25% the lower limit of flammability of H2 shall be installed in the room.  
4-9.5.2.2 The detector shall be located within 6 inches (15.2 centimeters) of the ceiling or  
the highest point in the room.  
4-9.5.2.3 The detector shall stop the flow of H2 and operate an audible or a visual alarm.  
4-9.6 Installation of pressure relief valves shall have pressure relief device vents or vent  
lines to convey escaping gas to the outdoors and then upward to a safe area to prevent  
impinging on buildings, other equipment, or areas open to the public, such as sidewalks.  
Page 35  
4-9.7 Piping and hose. A fueling hose shall be limited to a maximum length of 25 feet (7.62  
meters) and shall be protected from mechanical damage from abrasion and from being  
driven over by a vehicle.  
4-9.7.1 Transfer systems shall be capable of depressurizing the nozzle to facilitate  
disconnection. Bleed connections shall lead to a safe point of discharge.  
4-9.8 Testing. All piping and tubing shall be tested after assembly according to section 2-  
6.  
4-9.9 Installation of emergency shutdown equipment. An RFF shall be equipped with  
emergency manual shut down of the fuel supply prior to the RFF device. The emergency  
manual shutdown actuator shall be at least 5 feet (1.52 meters) from the RFF and in view  
of the RFF.  
4-9.9.1 Breakaway protection shall be provided in a manner so that, in the event of a pull  
away, H2 ceases to flow.  
4-9.9.1.1 The breakaway devices shall comply with ANSI/CSA HGV 4.4, "breakaway  
devices for dispensing systems," adopted by reference in section 8-1.  
4-9.9.1.2 A breakaway device shall be installed at every dispensing point.  
4-9.9.1.3 The breakaway device in 4-9.8.2.3 shall be arranged to separate using a force not  
greater than 150 pounds (75 kilograms) when applied in a horizontal direction.  
4-9.10 Operation. An RFF shall be operated in accordance with the manufacturer's  
instructions.  
4-9.10.1 A fuel supply container shall not be charged in excess of its maximum allowable  
service pressure at normal temperature.  
4-9.10.2 U.S. DOT containers shall be charged in accordance with U.S. DOT regulations.  
4-9.10.3 Where H2 is being transferred to a motor vehicle, the engine shall be turned off.  
4-9.11 Maintenance and inspection. All RFF equipment shall be inspected and maintained  
in accordance with the manufacturer's instructions.  
History: 2008 AACS.  
Chapter 5 Operation and Maintenance  
R 29.7047 Operation.  
Rule 47. Section 5-1 is reproduced from NFPA 50A, and sections 5-1.1 to 5-1.3 of the  
storage and handling of gaseous and Liquefied H2 code are added as follows:  
5-1 Operation. For installations that require any operation of equipment by the user,  
instructions shall be maintained at operating locations.  
5-1.1 A vehicle container shall not be charged in excess of the service pressure  
compensated for the differences in temperature from nominal.  
5-1.2 H2 vehicle containers shall not be subjected to pressure in excess of 125% of the  
marked service pressure even if, on cooling, the pressure settles to the marked service  
pressure.  
5-1.3 Where an overpressure incident that results in operation of the overpressure  
protection system of the dispenser occurs, the dispenser pressure control system shall be  
examined and certified by a qualified operator prior to being returned to service.  
Page 36  
History: 2008 AACS.  
R 29.7048 Maintenance.  
Rule 48. Section 5-2 is reproduced from NFPA 50A, and sections 5-2.1 to 5-2.11 of the  
storage and handling of gaseous and Liquefied H2 code are added as follows:  
5-2 Maintenance. Each hydrogen system installed on consumer premises shall be inspected  
annually and maintained by a qualified representative of the equipment owner.  
5-2.1 Hoses, nozzles and breakaways shall be examined visually to ensure that they are  
safe for use and shall be maintained in accordance with manufacturer's instructions on at  
least a quarterly basis or earlier if required by the manufacturer.  
5-2.2 Hose shall be tested for leaks per manufacturer's requirements and any leakage shall  
be a reason for rejection and replacement.  
5-2.3 Testing shall be carried out with helium or with helium/ H2 blend as the test gas or if  
this is not possible, with H2 using suitable precautions.  
5-2.4 The facility operator shall maintain a maintenance log in good condition and  
accessible to department inspection. Records shall be maintained for a minimum of 2 years.  
5-2.5 Controllers on fuel stations shall be designed to verify the integrity of the fuel hose,  
breakaway, nozzle, and receptacle by pressurizing these components to at least the vehicle  
backpressure and checking pressure drop prior to the start of fueling.  
5-2.6 Containers and their appurtenances, piping systems, compression equipment,  
controls, and detection devices shall be maintained in operating condition and according to  
manufacturer's instructions.  
5-2.7 Pressure relief valves shall be maintained in operating condition.  
5-2.8 Maintenance personnel shall be trained in leak detection procedures.  
5-2.9 Area within 10 feet (3.1 meters) of dispenser shall be free from debris, weeds and  
other material that present a fire hazard.  
5-2.10 Safety, gas detection, and fire protection equipment shall be tested or inspected at  
intervals not to exceed 6 months.  
5-2.11 Maintenance activities on fire control equipment shall be scheduled so that a  
minimum of equipment is taken out of service at any 1 time and fire prevention safety is  
not compromised.  
History: 2008 AACS.  
R 29.7049 Clearance to combustibles.  
Rule 49. Section 5-3 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
5-3 Clearance to combustibles. The area within 10 feet (3.1 meters) of any H2 container  
shall be kept free of dry vegetation and combustible material.  
History: 2008 AACS.  
R 29.7050 Cathodic protection maintenance.  
Page 37  
Rule 50. Sections 5-4 and 5-4.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-4 Cathodic protection maintenance.  
5-4.1(a) Owners and operators shall ensure that all metallic container systems that are  
underground, mounded, or partially underground are protected and maintained to minimize  
corrosion as cited in the NACE standard RP0169 entitled "Recommended Practice, Control  
of External Corrosion of Underground or Submerged Metallic Piping Systems" and NACE  
recommended practice RP0285 entitled "Corrosion Control of Underground Storage Tank  
Systems by Cathodic Protection."  
(b) All corrosion protection systems shall be operated and maintained to continuously  
provide corrosion protection to the metal components of the portion of the ASME approved  
container system that routinely contains H2 gas and that is in contact with the ground.  
(c) All container systems equipped with cathodic protection systems shall be inspected  
for proper operation by a NACE certified cathodic protection tester as defined in section  
1-5. The H2 system shall be tested within 6 months of installation and at least once each  
calendar year at intervals not to exceed 15 months.  
(d) Container systems equipped with impressed current cathodic protection systems shall  
be inspected by the owner every 60 days to ensure that the equipment is operating within  
design specifications. The design limits shall be readily available.  
(e) If container systems are equipped with cathodic protection, then the owner or operator  
shall maintain records to demonstrate that the cathodic protection is in compliance with the  
performance standards of this section. The records shall provide both of the following:  
(1) The results of the last 3 inspections required in subsection (d) of this section.  
The results of testing from the last 2 inspections required in subsection (c) of this section.  
(f) Within 6 months following the repair of any cathodically protected container system,  
where the repairs may affect the operation of the cathodic protection system, the system  
shall be tested in accordance with subsections (c) and (d) of this section to ensure that it is  
operating properly.  
(g) Repairs or replacement of a cathodic protection system shall be conducted by a NACE  
certified corrosion expert as defined in section 1-5. General system maintenance of the  
cathodic protection system including, but not limited to, replacement of fuses, and splicing  
of cable would not be required to be designed by a corrosion expert and shall be approved  
by the department to not increase the hazard to public health, safety, and welfare and the  
environment.  
History: 2008 AACS.  
R 29.7051 Stray or impressed currents and bonding.  
Rule 51. Sections 5-5 to 5-5.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-5 Stray or impressed currents and bonding.  
5-5.1 Where stray or impressed currents are used or can be present on dispensing systems,  
such as cathodic protection, protective measures to prevent ignition shall be taken.  
5-5.2 Static protection between the fuel dispenser and the vehicle shall not be required  
where H2 is transferred by conductive hose, flexible metallic tubing, or pipe connections  
where both halves of the metallic couplings are in continuous contact.  
Page 38  
5-5.3 The transfer surface shall be concrete or shall have a resistivity not exceeding API-  
RP 2003, "protection against ignitions arising out of static, lightning, and stray currents,"  
adopted by reference in section 8-1, performance criteria of 1 megohm as measured using  
a method acceptable to the department, such as EN 1081 1998 "Resilient Floor Coverings  
- Determination of the Electrical Resistance.", adopted by reference in section 8-1.  
History: 2008 AACS.  
R 29.7052 Emergency plan.  
Rule 52. Sections 5-6 to 5-6.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-6 Emergency plan.  
5-6.1 An emergency plan shall be prepared and updated wherever gaseous or liquefied H2  
are produced, handled, stored, or used.  
5-6.2 The plan shall be available to the department for inspection upon reasonable notice  
and shall include the following information:  
(a) The type of emergency equipment available and its location.  
(b) A brief description of any testing or maintenance programs for the available  
emergency equipment.  
(c) An indication that hazard identification labeling is provided for each storage area.  
(d) Location of posted emergency procedures.  
(e) A material safety data sheet (MSDS or equivalent) that is available for the gaseous or  
liquefied H2 stored or used on the site.  
(f) A list of personnel or site operating authority who are designated and trained to be  
liaison personnel for the fire department and who are responsible for, but shall not be  
limited to, the following:  
(1) Aiding the emergency responders in pre-emergency planning.  
(2) Identifying the location of the gaseous and liquefied H2 stored or used.  
(3) Accessing material safety data sheets.  
(4) Knowledge of the site emergency procedures.  
(g) A list of types and quantities of gaseous and liquefied H2 found within the facility.  
History: 2008 AACS.  
R 29.7053 Release of H2.  
Rule 53. Sections 5-7 to 5-7.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-7 Release of H2.  
5-7.1 Records of unexpected discharges. Accurate records of the unexpected discharge of  
gaseous or liquefied H2 shall be kept by the facility and made readily available upon  
request. The records shall be kept for a minimum of 2 years.  
5-7.2 Container or PRD failure. When an unexpected discharge due to container or PRD  
failure is discovered the department and the local fire department shall be immediately  
notified, and the container shall be repaired or be removed from service.  
Page 39  
History: 2008 AACS.  
R 29.7054 Security.  
Rule 54. Sections 5-8 and 5-8.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-8 Security.  
5-8.1 Compressed gas cylinders, containers, and systems shall be secured against  
accidental dislodgement and against access by unauthorized personnel.  
History: 2008 AACS.  
R 29.7055 Leaks, damage, or corrosion.  
Rule 55. Sections 5-9 and 5-9.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-9 Leaks, damage, or corrosion.  
5-9.1 Leaking, damaged, or corroded gaseous H2 systems shall be removed from service,  
replaced, or repaired.  
History: 2008 AACS.  
Chapter 6 Fire Protection  
R 29.7056 Fire protection; caution.  
Rule 56. Section 6-1 is reproduced from NFPA 50A as follows:  
6-1 Caution. Personnel shall be cautioned that hydrogen flames are practically invisible.  
History: 2008 AACS.  
R 29.7057 Signage.  
Rule 57. Sections 6-2 to 6-2.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
6-2 Hazard identification signs shall be conspicuously placed at all locations where H2 gas  
is produced, stored, used, or handled.  
6-2.1 Ratings shall be assigned in accordance with NFPA 704, standard system for the  
identification of the hazards of materials for emergency response.  
6-2.2 The hazard classification of the metal hydride storage system shall be based on the  
H2 stored without regard to the metal hydride content.  
History: 2008 AACS.  
R 29.7058 Identification signs.  
Page 40  
Rule 58. Sections 6-3 to 6-3.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
6-3 Signs prohibiting smoking or open flames within 25 feet (7.6 meters) shall be provided  
where H2 gas is produced, stored, or used.  
6-3.1 A sign with the following legends printed in red capital letters on a white background  
shall be conspicuously posted:  
"NONODORIZED FLAMMABLE GAS - NO SMOKING - NO OPEN FLAMES" All  
lettering on signage shall be 3 inches (7.62 centimeters) or more.  
Exception: This does not apply to motor vehicle dispensing per sections 7.2.16 and 4-3.8.1.  
6-3.2 Identification signs. Visible hazard identification signs shall be provided in  
accordance with NFPA 704, "Standard System for the Identification of the Hazards of  
Materials for Emergency Response," adopted by reference in section 8-1, at entrances to  
buildings or areas in which liquefied H2 is stored, handled, or used.  
History: 2008 AACS.  
R 29.7059 Fire protection.  
Rule 59. Section 6-4 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
6-4 A portable fire extinguisher having a rating of not less than 40-B:C, or 2 20-B:C, shall  
be located within 75 feet (22.9 meters) from the pumps, dispensers, and container fill  
openings. Fire extinguishers shall be inspected and maintained according to NFPA 10,  
"standard for portable fire extinguishers," adopted by reference in section 8-1.1.  
History: 2008 AACS.  
R 29.7060 Sprinkler protection.  
Rule 60. Section 6-5 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
6-5 When sprinkler protection is provided, the area in which H2 is stored or used shall be  
protected with an automatic sprinkler system designed to be not less than that required by  
NFPA 13, "standard for the installation of sprinkler systems," adopted by reference in  
section 8-1.  
History: 2008 AACS.  
Chapter 7 Gaseous hydrogen compression, gas processing, storage, and dispensing  
systems  
R 29.7061 System component qualifications.  
Rule 61. Section 7-1 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
Page 41  
7-1 System component qualifications. System components shall comply with the  
appropriate provisions of chapters 2 and 3 of this part.  
History: 2008 AACS.  
R 29.7062 General system requirements.  
Rule 62. Sections 7-2 to 7-2.18 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-2 General system requirements.  
7-2.1 All fuel dispensing facilities shall meet the provisions of this chapter.  
7-2.2 Compression, processing, generation, storage, and dispensing equipment shall be  
protected to prevent damage from vehicles and minimize the possibilities of physical  
damage and vandalism and meet the requirements of section 2-1.5 and section 3-4.4.  
7-2.2.1 Access to storage, compression, and gas processing equipment by members of the  
public shall be restricted by a suitable secure area.  
7-2.3 Control devices shall be installed so that internal or external icing does not cause  
vehicle or fueling station malfunction.  
7-2.4 Vehicles shall not be considered a source of ignition with respect to the provisions  
of this chapter.  
Exception: Vehicles containing fuel-fired equipment, such as recreational vehicles and  
catering trucks, shall be considered a source of ignition unless this equipment is shut off  
completely before entering an area in which ignition sources are not permitted.  
7-2.5 The fueling connection shall prevent the escape of gas where the connector is not  
properly engaged or becomes separated.  
7-2.6 Fueling nozzles for H2 service shall be in accordance with section 2-12.1.  
7-2.7 Compression and gas processing equipment shall be designed for use with H2 and for  
maximum pressures and temperatures to which it can be subjected under normal operating  
conditions.  
7-2.8 Compression and gas processing equipment shall have pressure relief devices that  
limit each stage pressure to the maximum allowable working pressure for the compression  
cylinder and piping associated with that stage of compression and meets the requirements  
of chapter 2.  
7-2.9 H2 compression equipment shall be equipped with appropriate automatic shutdown  
controls.  
7-2.10 Control circuits that shut down shall remain down until manually activated or reset  
by qualified personnel.  
7-2.11 Engine-driven compressor installations shall conform where applicable to R  
29.5101 et seq.  
7-2.12 Gas processing equipment, including compression and generation equipment, in  
processes where liquid is present, shall incorporate means to minimize liquid carryover to  
the storage system.  
7-2.13 A hazard analysis shall be conducted on every H2 fueling system installation by a  
qualified engineer with proven expertise in H2 fueling systems and installations.  
Exception: This does not apply to section 4-9.  
7-2.13.1 The hazard analysis shall include the following: fire protection measures, fire  
protection and suppression systems, detection systems, and ventilation.  
Page 42  
7-2.13.2 At a minimum, the hazard analysis shall include consideration of potential failures  
in hoses, nozzles, dispensing equipment, as well as failures for maintenance and service.  
7-2.13.3 Method used for hazard analysis shall be 1 or combination of several of the  
following recognized procedures: hazard and operability studies (HAZOPs), failure mode  
effects and criticality analysis (FMECA), preliminary hazards analysis (PHA), fault tree  
analysis (FTA) and event tree analysis (ETA). Other analysis methods, when used, shall  
ensure same level of system safety as provided by any of the recognized procedures and be  
acceptable to the department based on the best interest of the public health, safety, and  
welfare and the environment.  
7-2.13.4 Standard designs that have been analyzed by recognized procedures need not be  
studied each and every time such installation occurs. Site-specific elements that are unique  
to the installation shall be reviewed in concert with the analysis performed on the standard  
system to ensure that the standard design has not been altered in a way that would  
negatively affect the hazard analysis.  
7-2.13.5 These hazard analyses shall be available for review at final inspection, prior to the  
installation being placed into service, shall be maintained on site, and be available to the  
department upon request.  
7-2.14 Dispensing systems shall be equipped to stop fuel flow automatically when a fuel  
supply container reaches the temperature-corrected fill pressure.  
7-2.15 Dispensing systems shall be equipped with an overpressure protection device set at  
140 percent of the service pressure of the fueling nozzle it supplies.  
7-2.16 Warning signs shall be conspicuously posted in the dispensing area and shall  
incorporate the following or equivalent wording: "Stop Motor, No Smoking, Non-Odorized  
Flammable Gas. No Filling Of Portable Containers In Or On A Motor Vehicle."  
7-2.17 Each H2 -dispensing device shall be located not less than 10 feet (3.1 meters) from  
property lines, openings to buildings, and buildings of combustible wall construction. A  
dispensing device shall not be less than 20 feet (6.1 meters) from any activity that involves  
a fixed source of ignition. In addition, a dispenser shall not be placed beneath a power line.  
7-2.18 Each container filling location that is open to the public shall have an attendant or  
supervisor on duty who meets the requirements of section 1-10.1 of the rules.  
History: 2008 AACS.  
R 29.7063 Operating requirements for full-service H2 motor fuel dispensing facilities.  
Rule 63. Sections 7-3 to 7-3.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-3 Operating requirements for full-service H2 motor fuel dispensing facilities.  
7-3.1 Each motor fuel dispensing facility shall have an attendant or supervisor on duty  
whenever the facility is open for business. The attendant or supervisor shall dispense H2  
into fuel tanks of motor vehicles or into portable containers.  
7-3.2 The provisions of section 2-1 of this part shall not prohibit the temporary use of a  
portable storage container in conjunction with the dispensing of H2 into a container or  
motor vehicle or motorized equipment which is on the premises and which is not accessible  
to the public. A portable storage container installation shall only be made with the approval  
of the department and comply with all the requirements of section 2-13.  
Page 43  
History: 2008 AACS.  
R 29.7064 Operating requirements for attended self-service motor fuel dispensing  
facilities.  
Rule 64. Sections 7-4 to 7-4.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-4 Operating requirements for attended self-service motor fuel dispensing facilities.  
7-4.1 Self-service motor fuel dispensing facility means that portion of a property where H2  
used as motor fuel is stored and dispensed from fixed, approved dispensing equipment into  
the fuel containers of motor vehicles by persons other than the facility attendant and shall  
also include, where provided, facilities for sale of other retail products.  
7-4.2 There shall be at least 1 attendant on duty while the self-service facility is open for  
business. The attendant's primary function shall be to supervise, observe, and control the  
dispensing of H2 while the H2 is actually being dispensed.  
7-4.3 The responsibility of the attendant shall be as follows:  
(a) Prevent the dispensing of H2 into portable containers in or on a motor vehicle.  
(b) Control sources of ignition.  
(c) Immediately activate emergency controls and notify the fire department of any fire.  
The attendant or supervisor on duty shall be mentally and physically capable of performing  
the functions and assuming the responsibility prescribed in section 7-4.3.  
7-4.4 Operating instructions shall be conspicuously posted in the dispensing area.  
7-4.5 The dispensing area shall at all times be in clear view of the attendant, and the placing  
or allowing of any obstacle to come between the dispensing area and the attendant control  
area is prohibited. This may be achieved by cameras, mirrors, or both. The attendant shall  
at all times be able to communicate with persons in the dispensing area.  
History: 2008 AACS.  
R 29.7065 Operating requirements for unattended self-service motor fuel dispensing  
facilities.  
Rule 65. Sections 7-5 to 7-5.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-5 Operating requirements for unattended self-service motor fuel dispensing facilities.  
7-5.1 Unattended self-service shall be permitted subject to the approval of the department  
based on the best interests of public health, safety, and welfare and the environment. Users  
shall use a key, card, or other method which is unique to each user, and which is provided  
by the facility operator, and shall be properly trained in dispensing operations. The owner  
shall verify such training to the department upon request.  
7-5.2 At least 1 emergency shutoff device specified in section 7-6 shall be provided, and  
shall be reset only by the owner or an owner's authorized agent.  
7-5.3 Operating instructions shall be conspicuously posted in the dispensing area. The  
instructions shall include the location of emergency controls.  
7-5.4 In addition to the warning signs specified in section 6-3, emergency instructions shall  
be conspicuously posted in the dispenser area. The instructions shall incorporate the  
following or equivalent wording:"Emergency instructions In case of fire:  
Page 44  
(1) Use emergency stop button.  
(2) Report accident by calling the local fire number. Report location."  
7-5.5 A telephone or other approved, clearly identified means to notify the fire department  
shall be provided on the site in a location approved by the department.  
History: 2008 AACS.  
R 29.7066 Emergency shutoff devices.  
Rule 66. Sections 7-6 to 7-6.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-6 Emergency shutoff devices.  
7-6.1 H2 dispensing systems shall be provided with 1 or more clearly identified emergency  
shutoff devices or electrical disconnects at the dispensing area. Such devices or disconnects  
shall be installed in approved locations but not less than 10 feet (3.1 meters) and not more  
than 100 feet (30.5 meters) away from the dispensing area and which is along the means  
of egress. Emergency shutoff devices or electrical disconnects shall disconnect power and  
gas supply to all dispensing devices, to all remote pumps serving  
the dispensing devices, and to all associated power. When more than 1 emergency shutoff  
device or electrical disconnect is provided, all devices shall be interconnected. Resetting  
from an emergency shutoff shall require manual intervention and the manner of resetting  
shall be approved by the department.  
History: 2008 AACS.  
R 29.7067 Refueling from transport vehicles.  
Rule 67. Sections 7-7 to 7-7.11 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-7 Refueling from transport vehicles. The dispensing of H2 in the open from a transport  
vehicle to a motor vehicle located at commercial, industrial, governmental, or  
manufacturing establishments and intended for fueling vehicles used in connection with  
their businesses shall be permitted if all of the requirements of sections 7-7.1 to 7-7.11 have  
been met.  
7-7.1 The department shall be notified before commencing operations under section 7-7.  
7-7.2 The transport vehicle shall comply with U.S. DOT requirements for the transportation  
of H2.  
7-7.3 Nighttime deliveries shall only be made in an area considered to be adequately  
lighted.  
7-7.4 The transport vehicle flasher lights shall be in operation while dispensing operations  
are in progress.  
7-7.5 Smoking materials, including matches, lighters, and other sources of ignition,  
including torches, shall not be used within 20 feet (6.1 meters) of the dispensing of H2 in  
the open from a transport vehicle to a motor vehicle.  
7-7.6 Each area where dispensing of H2 in the open from a transport vehicle to a motor  
vehicle shall be provided with 1 or more listed fire extinguishers that have a minimum  
capability of 40-B:C. The fire extinguishers shall be readily accessible to the dispensing  
Page 45  
operation. Fire extinguishers shall be inspected and maintained under NFPA 10, "Standard  
for Portable Fire Extinguishers," adopted by reference in section 8-1.  
7-7.7 Mobile fueling shall take place aboveground, shall not be beneath electric power lines  
or where exposed by their failure, and shall be a minimum of 10 feet (3.1 meters) from the  
nearest important building, property line, or combustible storage.  
7-7.8 Transport vehicle brakes shall be set and chock blocks shall be in place.  
7-7.9 Persons performing dispensing operations shall be qualified to deliver and dispense  
H2 fuels. Operations of transport vehicles used for mobile fueling operations shall have  
access on-site or be in possession of an emergency communications device to notify the  
proper authorities if there is an emergency.  
7-7.10 The transport vehicles shall be positioned with respect to vehicles being fueled to  
prevent traffic from driving over the delivery hose and between the transport vehicle and  
motor vehicle being fueled. The dispensing hose shall be properly placed on an approved  
reel or in an approved compartment before moving the transport vehicle.  
7-7.11 Additional requirements. The transfer area must meet the requirements of section  
5-5.  
History: 2008 AACS.  
Chapter 8 Referenced publications  
R 29.7068 Referenced publications.  
Rule 68. Sections 8-1 to 8-1.2.10 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
8-1 The following documents or portions thereof are referenced within this standard as  
mandatory requirements and shall be considered part of the requirements of this standard.  
The edition indicated for each referenced mandatory document is the current edition, and  
cost as of the date of issuance of these rules. Copies of the adopted publications are  
available for inspection at the office of the Department of Environmental Quality, Waste  
and Hazardous Materials Division, Storage Tank Unit, P.O. Box 30241, Lansing, Michigan  
48909-7741.  
8-1.1 NFPA publications. National Fire Protection Association. 1 Batterymarch Park, P.O.  
Box 9101, Quincy, Massachusetts 02269-9101.  
NFPA 10, "Standard for Portable Fire Extinguishers," 2002 edition, $36.50.  
NFPA 13, "Standard for the Installation of Sprinkler Systems," 2002 edition, $70.00.  
NFPA 51, "Standard for the Design and Installation of Oxygen-Fuel Gas Systems for  
Welding, Cutting, and Allied Processes," 2002 edition, $28.00.  
NFPA 52, "Vehicle Fuel Systems Code," 2006 edition, $36.00.  
NFPA 55, "Standard for the Storage, Use, and Handling of Compressed Gases and  
Cryogenic Fluids in Portable and Stationary Containers, Cylinders, and Tanks," 2005  
edition, $36.50.  
NFPA 69, "Standard on Explosion Prevention Systems," 2002 edition, $33.50.  
NFPA 70, "National Electrical Code," 2005 edition, $75.00.  
NFPA 101, "Life Safety Code," 2006 edition, $75.00.  
NFPA 220, "Standard on Types of Building Construction," 1999 edition, $28.00.  
Page 46  
NFPA 496, "Standard for Purged and Pressurized Enclosures for Electrical Equipment,"  
2003 edition, $33.50.  
NFPA 704, "Standard System for the Identification of the Hazards of Materials for  
Emergency Response," 2001 edition, $33.50.  
8-1.2 Other publications.  
8-1.2.1 ASME publications. American Society of Mechanical Engineers, Three Park  
Avenue, New York, New York 10016-5990.  
ANSI/ASME B31.3, "Process Piping," 2002 edition, $240.00.  
ASME International, "Boiler and Pressure Vessel Code, Section VIII," 2004 edition,  
$525.00.  
8-1.2.2 ASTM publication. American Society for Testing and Materials, 100 Barr Harbor  
Drive, West Conshohocken, Pennsylvania 19428-2959.  
ASTM E136-04, "Standard Test Method for Behavior of Materials in a Vertical Tube  
Furnace at 750 Degrees C," 2004 edition, $35.00.  
8-1.2.3 CGA publications. Compressed Gas Association, 1725 Jefferson Davis Highway,  
Arlington Virginia 22202-4100.  
CGA S-1.1, "Pressure Relief Device Standards - Part 1 - Cylinders for Compressed Gases,"  
2002 edition, $196.00.  
CGA S-1.2, "Pressure Relief Device Standards - Part 2 - Cargo and Portable Tanks for  
Compressed Gases," 1995 edition, $145.00.  
CGA S-1.3, "Pressure Relief Device Standards - Part 3 - Stationary Storage Containers for  
Compressed Gases," 2003 edition, $145.00.  
ANSI/CGA C-4, "Method of Marking Portable Compressed Gas Containers to Identify the  
Material Contained," 2003 edition, $252.00.  
CGA C-7, "Guide to the Preparation of Precautionary Labeling and Marking of  
Compressed Gas Containers," 2000 edition, $268.00.  
CGA G-5.5, "Hydrogen Vent Systems," 2004 edition, $39.00.  
8-1.2.4 IAS publications. International Approval Services, 8501 East Pleasant Valley  
Road, Cleveland, Ohio 44131.  
ANSI/IAS NGV 4.4, "Breakaway Devices for Dispensing Systems," 1999 edition, $57.00.  
8-1.2.5 NACE publications. National Association of Corrosion Engineers International,  
1440 South Creek Drive, Houston, Texas 77084.  
NACE RP0169, "Control of External Corrosion of Underground or Submerged Metallic  
Piping Systems," 2002 edition, $42.00.  
NACE RP0285, "Corrosion Control of Underground Storage Tank Systems by Cathodic  
Protection," 2002 edition, $37.00.  
8-1.2.6 SAE publications. Society of Automotive Engineers, 400 Commonwealth Drive,  
Warrendale, Pennsylvania 15096.  
SAE J2600, "Compressed Hydrogen Surface Vehicle Fueling Connection Devices," 2002  
edition, $59.00.  
8-1.2.7 International codes council. 4051 West Flossmore Road, Country Club Hills,  
Illinois 60478-5795.  
"International Fire Code," 2006 edition, section 2209.3.2.6, $61.50.  
8-1.2.8 U.S. Government publications. U.S. Government Printing Office, Washington, DC  
20402.  
Page 47  
Title 49, Code of Federal Regulations, "Transportation," Parts 171-190, U.S. Department  
of Transportation "Specifications and Regulations."  
8-1.2.9 ECS publications. European Committee for Standardization, Central Secretariat:  
rue de Stassart 36, B-1050, Brussels.  
EN 1081, "Resilient Floor Coverings, Determination of the Electrical Resistance," 1998  
edition, $32.00.  
8-1.2.10 API publications. American Petroleum Institute, 1220 L Street, Northwest,  
Washington, DC, 20005-5-4070.  
API Recommended Practice 2003, "Protection Against Ignitions Arising Out of Static,  
Lightning, and Stray Currents," 7th edition, $111.00.  
History: 2008 AACS.  
PART 3. STORAGE AND HANDLING OF LIQUEFIED HYDROGEN NFPA 50B  
Chapter 1 General information  
R 29.7070 Scope.  
Rule 70. Sections 1-1 to 1-1.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-1 Scope.  
1-1.1 Application. This standard covers the requirements for the design, siting,  
construction, installation, spill containment, operation, maintenance, and dispensing from  
a liquefied H2 system.  
1-1.2 Nothing in this H2 code shall be intended to prevent the use of systems, methods, or  
devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability,  
environmental protection capability, or safety over those prescribed by this H2 code, if  
technical documentation is submitted to the department to demonstrate equivalency and  
the system, method, or device is approved for the intended purpose.  
1-1.3 This code shall apply to the design and installation of liquefied H2 dispensing  
systems.  
Exception: Dispensing into rail and aircraft.  
History: 2008 AACS.  
R 29.7071 Retroactivity.  
Rule 71. Sections 1-2 and 1-2.1of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-2 Retroactivity.  
1-2.1 The provisions of this H2 code are necessary to provide a reasonable level of  
protection from loss of life and property from fire and explosion. The provisions shall  
reflect situations and the state of the art prevalent when the H2 code was issued. Unless  
otherwise noted, it shall not be intended that the provisions of this H2 code be applied to  
Page 48  
facilities, equipment, structures, or installations that were existing or approved for  
construction or installation before the effective date of this H2 code, except in those cases  
where it is determined by the department that the existing situation involves a distinct  
hazard to public health, safety, and welfare, and the environment.  
History: 2008 AACS.  
R 29.7072 Definitions.  
Rule 72. Section 1-3 of the storage and handling of gaseous and Liquefied H2 code is  
added and section 1-3.1 is reproduced from NFPA 50B as follows:  
1-3 Definitions.  
(a) "ANSI" means the american national standards institute.  
(b) "Approved" means acceptable to the department.  
(c) "ASME" means the american society of mechanical engineers.  
(d) "Authority having jurisdiction" means the department.  
(e) "Automatic emergency shutoff valve" means a designated fail-safe automatic closing  
valve designed to shut off the flow of gases or liquids that is initiated by a control system  
where the control system is activated by either manual or automatic means.  
(f) "Bulk storage" means a single container or containers, where all containers draw down  
at the same time.  
(g) "Cargo transport container" means a mobile unit designed to transport gaseous or  
liquefied H2.  
(h) "Cascade storage system" means storage in containers or cylinders arranged in banks  
where each bank acts as 1 large container. The banks are separated by switching valves to  
provide sequential drawdown of the banks.The bank may consist of 1 or more containers  
or cylinders.  
(i) "Cathodic protection" means a technique to prevent the corrosion of a metal surface  
by making the surface the cathode of an electrochemical cell.This protection renders a  
metallic container or piping component negatively charged with respect to its environment.  
This protection shall be designed by a corrosion expert as defined by these rules.  
(j) "Cathodic protection tester" means a person who can demonstrate an understanding of  
the principles and measurements of all common types of cathodic protection systems  
applicable to metal piping and container systems and who has education and experience in  
soil resistivity, stray current, structure-to-soil potential, and component electrical isolation  
measurements of metal piping and container systems. The person shall be certified as being  
qualified by the national association of corrosion engineers (NACE) international.  
(k) "Composite container" means a container fabricated of 2 or more materials that  
interact to facilitate the container design criteria.  
(l) "Compression discharge pressure" means the varying pressure at the point of discharge  
from the compressor.  
(m) "CGA" means the compressed gas association.  
(n) "Container" means a pressure vessel or cylinder used to store H2.  
(o) "Container appurtenances" means devices connected to container openings for safety,  
control, or operating purposes.  
(p) "Container system" means a container or combination of containers and all attached  
appurtenances, valves, and piping.  
Page 49  
(q) "Container valve" means a valve connected directly to the container outlet.  
(r) "Continuous gas detection system" means a gas detection system in which the  
instrument is maintained in continuous operation.  
(s) "Corrosion expert" means a person who, by reason of thorough knowledge of the  
physical sciences and the principals of engineering and mathematics acquired by a  
professional education and related practical experience, is qualified to engage in the  
practice of corrosion control of container systems. The person shall be certificated as being  
qualified by NACE, as a senior corrosion technologist, a cathodic protection specialist, or  
a corrosion specialist or be a registered engineer who has certification and licensing that  
includes education and experience in corrosion control.  
(t) "Corrosion protection" means protecting a container system to prevent the degradation  
of the metal through oxidation or reactivity with its environment.  
(u) "Cryogenic fluid" means a fluid with a boiling point lower than -130 degrees  
Fahrenheit (-90 degrees Celsius) at an absolute pressure of 101.325 kPa (14.7 psia).  
(v) "Cylinder" means a container constructed in accordance with the United States  
Department of Transportation specifications, Title 49, code of federal regulations (CFR),  
parts 171-190.  
(w) "Department" means the department of environmental quality.  
(x) "Director" means the director of the department of environmental quality.  
(y) "Dispensing station" means an H2 installation that dispenses H2 from storage  
containers into fuel supply containers or into portable cylinders by means of a compressor,  
reformer, vaporizer, or pressure booster.  
(z) "Emergency shutdown device (ESD)" means a device that closes all fueling operations  
within the fueling facility from either local or remote locations.  
(aa) "Excess flow control" means to limit or stop the flow of H2 gas from a source of  
supply, when there is a rupture, break, or 'open valve to atmosphere' condition that may  
present a hazard to personnel or the environment.  
(bb) "Fail-safe" means a design feature that provides for the maintenance of safe operating  
conditions in the event of a malfunction of control devices or an interruption of an energy  
source.  
(cc) "Fixed liquid level device" means a device that indicates when the container is filled  
to its maximum permitted liquid filling volume.  
(dd) "Flow-through process container" means a container that forms an integral part of a  
production process through which there is a steady, variable, recurring, or intermittent flow  
of materials during the operation of the process and the container is utilized to carry out or  
control the heating, cooling, mixing, blending, separating, metering, or chemical reaction  
of materials. The processing is done on a regular basis and it is the primary function of the  
container. A flow-through process container does not include a container that is used for  
the storage of materials before its introduction into the production process or for the storage  
of finished products or by-products from the production process or a container that is only  
used to recirculate materials.  
(ee) "Fuel dispenser system" means all the pumps, meters, piping, hose, and controls used  
for the delivery of fuel.  
(ff) "Fueling connector" means a mating device at the refueling station, including shutoff  
valves that connect the fueling dispenser hose to the vehicle fuel filling system receptacle  
for the transfer of liquid or vapor.  
Page 50  
(gg) "Gallon water capacity (wc)" means the amount of water in gallons at 60 degrees  
Fahrenheit (15.6 degrees Celsius) required to fill a container.  
(hh) "Gas detection system" means a grouping of 1 or more sensors capable of detecting  
an H2 leak at specified concentrations and activating alarms and safety systems.  
(ii) "Gaseous H2 system" means a system in which the H2 is delivered, stored, and  
discharged in the gaseous form including the piping system. The gaseous H2 system  
terminates at the point where the H2 is dispensed.  
(jj) "Hydrogen (H2)" means the simplest and lightest element in the known universe,  
which exists as a gas except at low cryogenic temperatures. H2 gas is a colorless, odorless  
and highly flammable gas when mixed with oxygen over a wide range of concentrations.  
H2 forms water when combusted, or when otherwise joined with oxygen, as within a fuel  
cell.  
(kk) "Hydrogen code" means the storage and handling of gaseous and liquefied H2 rules  
as promulgated by the department.  
(ll) "Hydrogen gas vehicle (HGV) or vehicle" means a self-propelled device on land; in,  
on, or by which any person or property is or may be transported or drawn upon, except for  
a device exclusively moved by human power; and which has the capability to use H2 gas  
as an engine fuel.  
(mm) "Ignition source" means any item or substance capable of an energy release of type  
and magnitude sufficient to ignite any flammable mixture of gases or vapors that could  
occur at the site.  
(nn) "kPa" means absolute pressure in kilo-Pascals.  
(oo) "kPag" means gauge pressure in kilo-Pascals.  
(pp) "Labeled" means equipment or materials to which has been attached a label, symbol,  
or other identifying mark of an organization that is acceptable to the department and  
concerned with product evaluation, that maintains periodic inspection of production of  
labeled equipment or materials, and by whose labeling the manufacturer indicates  
compliance with accepted or approved standards of construction and or performance.  
(qq) "Liquefied hydrogen system" means a system into which liquefied H2 is delivered  
and stored and from which it is discharged in the liquid or gaseous form including the  
piping system. The liquid or gaseous H2 system terminates at the point where the H2 is  
dispensed.  
(rr) "Listed" means equipment, materials, or services included in a list published by an  
organization that is acceptable to the department and concerned with evaluation of products  
or services, that maintains periodic inspection of production listed equipment or materials  
or periodic evaluation of services, and whose listing states that either the equipment,  
material, or service meets appropriate designated standards or has been tested and found  
suitable for a specified purpose.  
(ss) "Manifolded storage system" means storage in containers arranged in banks where  
each bank acts as 1 large container. The banks are separated by switching valves to provide  
sequential drawdown of the banks. The bank may consist of 1 or more containers.  
(tt) "Manual emergency shutoff valve" means a designated valve designed to shut off flow  
due to arupture in pressurized piping system.  
(uu) "Maximum allowable working pressure (MAWP)" means the maximum pressure to  
which any component or portion of the pressure system can be subjected.  
Page 51  
(vv) "Maximum operating pressure (MOP)" means the steady-state gauge pressure at  
which a part or system normally operates.  
(ww) "Metal hydride storage system" means a system for the storage of H2 gas absorbed  
in solid material.  
(xx) "Motor fuel dispensing facility" means that portion of the property where H2 is stored  
and dispensed from fixed equipment into the fuel tanks of motor vehicles or marine craft  
or into approved containers, including all equipment used in connection therewith.  
(yy) "NACE" means the national association of corrosion engineers, international.  
(zz) "Original equipment manufacturer (OEM)" means an original equipment motor  
vehicle manufacturer that certifies that the motor vehicle complies with applicable federal  
motor vehicle safety codes.  
(aaa) "Partially buried container" means a container that has part of, but less than 100%,  
of the container surface covered with earth.  
(bbb) "Point of transfer" means the point where the transfer connection is made.  
(ccc) "Portable container" means a container designed to be moved readily, as  
distinguished from containers designed for stationary installations.Portable containers,  
designed for transportation with H2 filled to their maximum filling limit, include  
"cylinders," "cargo tanks," and "portable tanks," all 3 of which are defined separately.  
Containers designed to be readily moved from 1 usage location to another, but substantially  
empty of product, are "portable storage containers" and are defined separately.  
(ddd) "Portable storage container" means a container similar to those designed and  
constructed for stationary installation, designed so that it can be moved readily over the  
highways, substantially empty of liquefied H2, from 1 usage location to another. Such  
containers either have legs or other supports attached, or are mounted on running gear, such  
as trailer or semitrailer chassis, with suitable supports that can be of the fold-down type,  
allowing them to be placed or parked in a stable position on a reasonably firm and level  
surface. For large-volume, limited-duration product usage, such as at construction sites and  
normally for 6 months or less, portable storage containers function in lieu of permanently  
installed stationary containers.  
(eee) "Portable tank, or skid tank" means a container of more than 1,000 pounds (454  
kilograms) water capacity used to transport H2 handled as a package, that is, filled to its  
maximum permitted filling limit. Such containers are mounted on skids or runners and  
have all container appurtenances protected in such a manner that they can be safely handled  
as a package.  
(fff) "Pressure relief device" means a pressure or temperature activated device used to  
prevent pressure from rising above a specified value and thereby prevent the rupture of a  
normally charged pressure vessel or a cylinder due to emergency or abnormal conditions.  
(ggg) "Pressure vessel" means a container or other component designed in accordance  
with the ASME code.  
(hhh) "psi" means pounds per square inch.  
(iii) "psia" means pounds per square inch, absolute.  
(jjj) "psig" means pounds per square inch gauge.  
(kkk) "Rated pressure" means the pressure to which a component is rated provided that  
the MAWPis observed for temperature extremes.  
(lll) "Release" means an unexpected discharge of H2.  
Page 52  
(mmm) "Remotely located manually activated shutdown control" means a control system  
that is designed to initiate shut down of the flow of gas or liquid that is manually activated  
from a point located some distance from the delivery system.  
(nnn) "Service pressure" means the nominal gas pressure at a uniform gas temperature of  
70 degrees Fahrenheit (15.6 degrees Celsius) when the equipment is properly and  
completely charged with gas; the nominal design pressure for which the equipment has  
been constructed.  
(ooo) "Set pressure" means the start-to-discharge pressure for which a relief valve is set  
and marked.  
(ppp) "Standard cubic foot (scf)" means 1 cubic foot of gas at 70 degrees Fahrenheit (21  
degrees Celsius) and 14.7 psia (101 kPa).  
(qqq) "Standard cubic foot per minute (scfm)" means the amount of gas flow in standard  
cubic feet per minute compensated for pressure and temperature.  
(rrr) "Substantially empty" means a gas container of H2 when the residual gas pressure is  
less than 10% of the maximum allowable working pressure of the vessel. A liquefied H2  
container is substantially empty when the liquid level within the container is less than 10%  
of its normal operating volume.  
(sss) "Vaporizer" means a device other than a container that receives H2 in liquid form  
and adds sufficient heat to convert the liquid to a gaseous state.  
(ttt) "Vehicle-fueling appliance" means a self-contained listed assembly used for the  
compression and delivery of H2 into vehicles including associated equipment and piping of  
the appliance.  
1-3.1 NFPA official definitions.Combustible liquid. A liquid having a closed-cup flash  
point at or above 100°F (37.8°C) and are subdivided as follows:  
(a) Class II liquids include those having a flash point at or above 100°F (37.8°C) and  
below 140°F (60°C).  
(b) Class IIIA liquids include those having a flash point at or above 140°F (60°C) and  
below 200°F (93.4°C).  
(c) Class IIIB liquids include those having a flash point at or above 200°F (93.4°C).  
Flammable liquid (Class I). Any liquid having a closed-cup flash point below 100°F  
(37.8°C) and having a vapor pressure not exceeding 40 psia (276 kPa) at 100°F (37.8°C).  
Gallon. A standard U.S. gallon.  
Limited-Combustible Material. A material, as defined in NFPA 220, Standard on Types of  
Building Construction, not complying with the definition of noncombustible material that,  
in the form in which it is used, has a potential heat value not exceeding 3500 Btu/lb (8141  
kJ/kg) and complies with one of the following paragraphs (a) or (b). Materials subject to  
an increase in combustibility or flame spread rating, beyond the limits herein established,  
through the effects of age, moisture, or other atmospheric condition are considered  
combustible.  
(a) Materials having a structural base of noncombustible material, with a surfacing not  
exceeding a thickness of 1/8 in. (3.2 mm) that has a flame spread rating not greater than  
50.  
(b) Materials, in the form and thickness used, other than as described in (a), having neither  
a flame spread rating greater than 25 nor evidence of continued progressive combustion  
and of such composition that surfaces that would be exposed by cutting through the  
material on any plane would have neither a flame spread rating greater than 25 nor evidence  
Page 53  
of continued progressive combustion. Noncombustible material. A material, as defined in  
NFPA 220, Standard on Types of Building Construction, that, in the form in which it is  
used and under the conditions anticipated, will not ignite, burn, support combustion, or  
release flammable vapors when subjected to fire or heat. Materials reported as  
noncombustible, when tested in accordance with ASTM E 136, Standard Method of Test  
for Behavior of Materials in a Vertical Tube Furnace at 750°C, are considered  
noncombustible materials.  
Outdoors. Location outside of any building or structure or locations under a roof, weather  
shelter, or canopy provided this area is not enclosed on more than two sides.  
Separate building. A detached, noncommunicating building used exclusively to house a  
hydrogen system. Shall. Indicates a mandatory requirement.  
Special room. A separate enclosed area that is part of or attached to another building and  
is used exclusively for a hydrogen system.  
Standard. A document, the main text of which contains only mandatory provisions using  
the word "shall" to indicate requirements and which is in a form generally suitable for  
mandatory reference by another standard or code or for adoption into law. Nonmandatory  
provisions shall be located in an appendix, footnote, or fine-print note and are not to be  
considered a part of the requirements of a standard.  
History: 2008 AACS.  
R 29.7073 Prohibitions.  
Rule 73. Sections 1-4 to 1-4.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-4 Prohibitions.  
1-4.1 Any liquefied H2 storage container system or practice that is not in compliance with  
these rules shall be considered to be in violation of these rules.  
1-4.2 Upon notification by the department, a person shall not deliver liquefied H2 to a  
storage container system under any circumstances that are prohibited by these rules or if a  
container is not in compliance with these rules. Such notification may include a verbal or  
written communication or an affixed written notification on the H2 system.  
1-4.3 A person shall not tamper with, remove, or disregard written notification affixed to  
the storage container system.  
1-4.4 An owner or operator shall not continue to use a storage container system that is  
causing a release and shall expeditiously empty the system or the component that is causing  
the release until the system is repaired or replaced.  
History: 2008 AACS.  
R 29.7074 Installation application.  
Rule 74. Sections 1-5 to 1-5.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-5 Installation application.  
Page 54  
1-5.1 An application for plan review shall be submitted, on a form provided by the  
department, by the owner or owner's designee on behalf of the owner to the department not  
less than 30 days before the installation of an H2 storage container system.  
1-5.1.1 The installation application shall include all of the following information:  
(a) A plot map showing all of the following within 100 feet (30.5 meters) of any portion  
from the container system:  
(i) The location of the following:  
(A) Buildings.  
(B) Public roadways.  
(C) Railroad mainlines.  
(D) Public sidewalks.  
(E) Overhead power lines.  
(ii) The proposed location of the dispensing station.  
(iii) The location of property lines.  
(iv) The locations of existing aboveground and underground tanks storing flammable and  
combustible liquids, and flammable, compressed or liquefied gases.  
(v) The location of the point of transfer in relationship to all of the following:  
(A) The container.  
(B) Buildings.  
(C) Public ways.  
(D) Outdoor places of public assembly.  
(E) Driveways.  
(F) Main line railroad track center lines.  
(G) The line of adjoining property that may be built upon.  
(H) Aboveground and underground tanks storing flammable and combustible liquids  
and/or flammable, compressed, or liquefied gases.  
(b) The construction material, the dimensions and the capacity of each container.  
(c) The type of container venting and pressure relief.  
(d) The compressor(s) size (psig and scfm).  
(e) Container appurtenances.  
(f) A piping diagram showing sizes, valves, pressure relief and fittings, and control  
devices.  
1-5.2 Upon acknowledged receipt of the plans, the department shall issue a plan review  
report within 30 days. If the plan review report is not issued within 30 days, the installation  
may be constructed according to the submitted plans and shall be in compliance with these  
rules.  
1-5.3 An applicant shall notify the department upon completion of the installation before  
the installation is placed into service. The department shall inspect the installation after  
receiving notification and shall certify the installation, if the requirements of the rules are  
met. If the inspection is not made within 2 working days, then the applicant may place the  
installation into service, or if intended to be underground, mounded, or partially  
underground, may cover the installation from sight, and shall  
notify the department, and shall submit a notarized affidavit to the department attesting to  
the fact that the installation complies with the installation application submitted and the  
applicable rules.  
Page 55  
1-5.4 Upon the owner's request, all plans and specifications that are submitted to the  
department for review shall be returned after the department has certified the installation  
or within 30 working days after notification to the department of the completion of the  
installation. Plans and specifications may be marked "Confidential-Do Not Copy" at the  
time they are submitted.  
History: 2008 AACS.  
R 29.7075 Installation application fees and annual certification.  
Rule 75. Sections 1-6 to 1-6.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-6 Installation application fees and annual certification.  
1-6.1 Only an owner of an H2 container system for which an installation application is  
required to be submitted under section 1-5 of the H2 code shall be required to pay fees as  
specified in 1941 PA 207, MCL 29.5.  
1-6.2 For the purpose of assessing fees, each liquefied H2 permanent installation, or any  
container filling location, shall be considered a container, as defined in section 5 of 1941  
PA 207, MCL 29.5.  
History: 2008 AACS.  
R 29.7076 Equivalency.  
Rule 76. Sections 1-7 to 1-7.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-7 Equivalency.  
1-7.1 Nothing in this H2 code shall be intended to prevent the use of systems, methods, or  
devices having equivalent or superior quality, strength, fire resistance, effectiveness,  
durability, environmental protection capability, or safety over those prescribed by the H2  
code, if technical documentation is submitted to the department to demonstrate equivalency  
and the system, method, or device is approved for the intended purpose.  
1-7.2 An owner or operator may make an application for a variance of rules by applying to  
the department with a satisfactory explanation of why compliance is not possible. The  
department may approve the variance request upon finding that the variance is based upon  
the best interest of public health, safety, and welfare, and the environment.  
1-7.3 A person aggrieved by a final decision of the department on a request for variance or  
an equivalency determination may appeal to the circuit court within 21 days of receiving  
the decision.  
History: 2008 AACS.  
R 29.7077 Personnel.  
Rule 77. Sections 1-8 and 1-8.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-8 Personnel.  
Page 56  
1-8.1 In the interest of safety, all persons involved in handling H2 shall be trained in the  
proper handling and operating procedures. This training shall be acceptable to the  
department.  
Exception: This training is not required for a person dispensing H2 into a vehicle at an  
attended self-service facility.  
History: 2008 AACS.  
R 29.7078 Application.  
Rule 78. Sections 1-9 to 1-9.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
1-9 Application.  
1-9.1 The application of this standard at places of public assembly shall meet the  
requirements of section 3-2.2(a) and the approval of the department.  
1-9.2 This standard does not apply to flow-through process containers.  
1-9.3 When required by the department, H2 introduced into any system covered by this  
code shall have a leak detection system acceptable to the department and based on the best  
interest of public health, safety, and welfare, and the environment.  
1-9.4 Liquefied H2 in fuel containers on vehicles and mobile equipment shall not be  
included in determining the maximum allowable quantities.  
History: 2008 AACS.  
Chapter 2 Design of liquefied hydrogen systems  
R 29.7079 Containers.  
Rule 79. Sections 2-1 to 2-1.10.1.3 and figure 2-1.2 of the storage and handling of gaseous  
and Liquefied H2 code are added as follows:  
2-1 Containers.  
2-1.1 H2 containers shall comply with the following.  
(a) Storage containers shall be designed, constructed, and tested in accordance with  
appropriate requirements of the ASME "Boiler and Pressure Vessel Code," section VIII,  
"Rules for the Construction of Pressure Vessels," adopted by reference in section 8-1.  
(b) Portable containers shall be designed, constructed, and tested in accordance with title  
49 CFR.  
(c) Welding or brazing for the repair or alteration of an ASME pressure vessel shall  
comply with the standard adopted in section 8-1.2.1.  
(d) Other welding or brazing shall be permitted only on saddle plates, lugs, or brackets  
which are attached to the pressure vessel by the pressure vessel manufacturer.  
(e) The exchange or interchange of pressure vessel appurtenances intended for the same  
purpose shall not be considered a repair or alteration but must comply with these rules.  
2-1.2 Permanently installed containers shall be provided with substantial supports of  
noncombustible material securely anchored on firm foundations of noncombustible  
material, and shall comply with the following subsections as applicable:  
Page 57  
(a) Steel supports in excess of 18 inches (46 centimeters) in height shall be protected with  
a protective coating having a 2-hour fire resistance rating, see figure 2-1.2.  
(b) If a permanently installed aboveground container is in an area that is subject to buoyant  
forces, provision shall be made to prevent the container, either full or empty, from floating  
during a rise in water level, including up to the established maximum flood stage.  
(c) Horizontally installed containers shall have not more than 2 points of support  
longitudinally or other methods approved by the department based on the best interest of  
public health, safety, and welfare and the environment.  
(d) Horizontally installed containers shall not be in direct contact with each other.  
(e) Aboveground containers shall be protected by painting or other equivalent means  
where necessary to inhibit corrosion.  
(f) Temperature effects. Foundations or supports that could come in contact with the  
cryogenic fluid in the event of a spillage, such as at fill connections, and flanges, shall be  
constructed of materials that are capable of withstanding the cryogenic temperature effects,  
such as concrete and stainless steel.  
(g) Excessive loads. Stationary containers shall be supported to prevent the concentration  
of excessive loads causing differential settlement of the support system.  
(h) Expansion and contraction. Foundations for horizontal containers shall be constructed  
to accommodate expansion and contraction of the container.  
(i) Support of ancillary equipment. Foundations shall be provided to support the weight  
of ancillary equipment such as vaporizers and/or heat exchangers.  
2-1.3 Marking. Liquefied H2 containers and systems shall be marked in accordance with  
this section.  
2-1.3.1 Portable containers. Portable containers shall be marked in accordance with CGA  
C-7, "Guide to the Preparation of Precautionary Labeling and Marking of Compressed Gas  
Containers," adopted by reference in section 8.  
Page 58  
2-1.3.2 Stationary containers. Stationary containers shall be marked in accordance with  
NFPA 704, "Standard Systems for the Identification of the Hazards of Materials for  
Emergency Response," adopted by reference in section 8.  
2-1.3.3 Identification of contents. Each container shall be marked as follows:  
LIQUEFIED HYDROGEN - FLAMMABLE GAS in letters that are not less than 3 inches  
(7.62 centimeters) in height.  
2-1.3.4 Container specification. Stationary containers shall be marked with the  
manufacturing specification and maximum allowable working pressure on a permanent  
nameplate in accordance with the standard to which the container was manufactured.  
2-1.4 An owner or operator that has had a container subjected to heat exposure due to an  
engulfing fire, a fire in which at least 25% of the container surface is exposed, shall remove  
the container from service, and shall not return the container to service, unless the owner  
or operator provides documentation to substantiate mechanical and performance integrity  
of the container in accordance with section 2-1.1 to the department. Such documentation  
shall be issued by a qualified engineer.  
2-1.5 Guard posts or other approved means shall be provided to protect a  
container system subject to vehicular damage. When guard posts are  
installed, all of the following design specifications shall be met:  
(a) Guard posts shall be constructed of steel not less than 4 inches (10.16 centimeters) in  
diameter and shall be filled with concrete.  
(b) Guard posts shall be spaced not more than 4 feet (1.2 meters) on center.  
(c) Guard posts shall be set not less than 4 feet (1.2 meters) deep in a concrete footing that  
is not less than 15 inches (38.1 centimeters) in diameter.  
(d) Guard posts shall be not less than 4 feet (1.2 meters) in height above grade.  
(e) Other means as approved by the department based on the best interests of public health,  
safety, and welfare, and the environment.  
2-1.6 Physical protection. Containers, piping, valves, pressure-relief devices, regulating  
equipment, and other appurtenances shall be protected against physical damage and  
tampering.  
2-1.7 Portable containers subject to shifting or upset shall be secured. Nesting shall be  
permitted as a means of securing portable containers.  
2-1.8 Overfill protection and prevention systems. An approved means or method shall be  
provided to prevent the overfilling of storage containers.  
2-1.9 Vacuum level monitoring. An approved monitoring method shall be provided to  
indicate vacuum degradation within the vacuum jacket(s).  
2-1.10 Underground containers. Underground containers for the storage of liquefied H2  
shall be in accordance with this subsection.  
2-1.10.1 Construction. Storage containers for liquefied H2 shall be designed and  
constructed in accordance with section VIII of ASME "Boiler and Pressure Vessel Code,"  
adopted by reference in section 8, and shall be vacuum-jacketed in accordance with section  
2-1.10.1.1.  
2-1.10.1.1 Vacuum jacket construction. The vacuum jacket shall be designed and  
constructed in accordance with section VIII of ASME "Boiler and Pressure Vessel Code,"  
and shall be designed to withstand the anticipated loading, including loading from  
vehicular traffic, where applicable. Portions of the vacuum jacket installed below grade  
shall be designed to withstand anticipated soil, hydrostatic, and seismic loading.  
Page 59  
2-1.10.1.2 Material. The vacuum jacket shall be constructed of stainless steel or other  
approved corrosion-resistant material.  
2-1.10.1.3 Corrosion protection. The underground container shall be protected by an  
engineered corrosion protection system designed by a corrosion expert. If cathodic  
protection is used the maintenance schedule shall meet the requirements of section 5-3.  
History: 2008 AACS.  
R 29.7080 Pressure relief devices.  
Rule 80. Sections 2-2.1 to 2-2.5 are reproduced from NFPA 50B, and sections 2-2.6 to 2-  
2.16 of the storage and handling of gaseous and Liquefied H2 code are added as follows:  
2-2 Pressure relief devices.  
2-2.1 Stationary liquefied hydrogen containers shall be equipped with pressure relief  
devices sized in accordance with CGA S-1.3, Pressure Relief Device Standards - Part 3 -  
Compressed Gas Storage Containers.  
2-2.2 Portable liquefied hydrogen containers complying with DOT Specifications and  
Regulations shall be equipped with pressure relief devices as required in DOT  
Specifications and Regulations. Pressure relief devices shall be sized in accordance with  
the requirements of CGA S-1.1, Pressure Relief Device Standards - Part 1 - Cylinders for  
Compressed Gases, and CGA S-1.2, Pressure Relief Device Standards - Part 2 - Cargo and  
Portable Containers for Compressed Gases.  
2-2.3 Pressure relief devices shall be arranged to discharge unobstructed to the outdoors  
and in such a manner as to prevent impingement of escaping liquid or gas upon the  
container, adjacent structures, or personnel. (See 3-1.5 for venting of pressure relief devices  
in special locations.)  
2-2.4 Pressure relief devices or vent piping shall be designed or located so that moisture  
cannot collect and freeze in a manner that would interfere with proper operation of the  
device.  
2-2.5 Pressure relief devices shall be provided in piping wherever liquefied hydrogen could  
be trapped between closures.  
2-2.6 Stationary containers shall be provided with a sign, in letters not less than 1 inch  
(2.54 centimeters) in height, placed in proximity to the primary container pressure relief  
valve vent stack that warns against spraying water on or into the vent opening.  
2-2.7 The pressure-relief device shall have the capacity to prevent the pressure inside the  
container from exceeding 110% of the maximum design pressure.  
2-2.8 H2 venting systems discharging to the atmosphere shall be in accordance with CGA  
G-5.5, adopted by reference in section 8.  
2-2.9 Components which come in contact with cryogenic H2 under normal operating  
conditions shall be suitable for operation at a temperature of -430 degrees Fahrenheit (-236  
degrees Celsius).  
2-2.10 Individual discharge lines and adapters shall be sized, located, and secured so as to  
permit the maximum required relief discharge capacity to minimize the possibility of  
physical damage. The discharge lines shall be able to withstand the pressure of the relief  
vapor discharge when the relief is in the full-open position.  
2-2.11 Secondary relief devices, designed to provide additional relief in emergencies, shall  
be piped away from the container independently.  
Page 60  
2-2.12 Shutoffs between pressure-relief devices and containers. Shutoff valves shall not be  
installed between pressure-relief devices and containers unless the valves or their use meets  
the requirements of this section.  
2-2.12.1 Security. Shutoff valves shall be of a locking type and their use shall be limited to  
service-related work performed by the supplier under the requirements of ASME "Boiler  
and Pressure Vessel Code," adopted by reference in section 8.  
2-2.12.2 Multiple pressure-relief devices. Shutoff valves controlling multiple pressure-  
relief devices on a container shall be installed so that either the type of valve installed or  
the arrangement provides the full required flow through the minimum number of required  
relief devices at all times.  
2-2.13 Safety and relief valves. Pressure relief valves for liquefied H2 systems, if externally  
adjustable, shall be provided with a means for sealing the adjustment to prevent tampering.  
2-2.13.1 If at any time it is necessary to break such a seal, the valve shall be removed from  
service until it has been reset and sealed.  
2-2.13.2 Adjustments shall be made only by the manufacturer or other organizations having  
competent personnel and facilities for the repair, adjustment, and testing of such valves.  
2-2.13.3 The organization making such adjustment shall attach a permanent tag with the  
setting, capacity, and date.  
2-2.14 The thermal expansion relief valve shall be installed as required to prevent  
overpressure in any section of a liquid or cold vapor pipeline that can be isolated by valves.  
2-2.14.1 Thermal expansion relief valves shall be set to discharge above the maximum  
pressure normally expected in the line but less than the rated test pressure of the line it  
protects.  
2-2.14.2 Discharge from thermal expansion relief valves shall be directed so as to minimize  
hazard to personnel and other equipment.  
2-2.15 Pressure relief valves shall be tested at least every 5 years.  
Exception: Thermal relief valves will not be tested.  
2-2.16 Heat exchangers, vaporizers, insulation casing surrounding containers, vessels, and  
coaxial piping systems in which liquefied or cold vapor H2 could be trapped shall be  
provided with a pressure-relief device.  
History: 2008 AACS.  
R 29.7081 Piping, tubing, and fittings.  
Rule 81. Sections 2-3.1, and 2-3.4 are reproduced from NFPA 50B, and sections 2-3.2, 2-  
3.2.1, 2-3.3, 2-3.5, 2-3.5.1, 2-3.6 to 2-3.17 of the storage and handling of gaseous and  
Liquefied H2 code are added as follows:  
2-3 Piping, tubing, and fittings.  
2-3.1 Piping, tubing, and fittings, and gasket and thread sealants shall be suitable for  
hydrogen service at the pressures and temperatures involved. Consideration shall be given  
to the thermal expansion and contraction of piping systems when exposed to temperature  
fluctuations of ambient to liquefied hydrogen temperatures.  
2-3.2 Material specifications and thickness requirements for piping and tubing shall  
conform to ASME B31.3, "Process Piping." Piping or tubing for operating temperatures  
below -20 degrees Fahrenheit (-29 degrees Celsius) shall be fabricated from materials  
Page 61  
meeting the impact test requirements of Chapter III of ASME B31.3 when tested at the  
minimum operating temperature to which the piping can be subjected in service.  
2-3.2.1 Aluminum shall not be used with liquefied H2 piping except for ambient air  
vaporizers.  
2-3.3 Joints in piping and tubing shall be made by welding, brazing, or flanged. Brazing  
materials shall have a melting point above 1,000 degrees Fahrenheit (538 degrees Celsius).  
Flanged connection shall use a gasket that is suitable for H2.  
2-3.4 Means shall be provided to minimize exposure of personnel to piping operating at  
low temperatures and to prevent air condensate from contacting piping, structural  
members, and surfaces not suitable for cryogenic temperatures. Insulation shall be of  
noncombustible material and shall be designed to have a vaportight seal in the outer  
covering to prevent the condensation of air and subsequent oxygen enrichment within the  
insulation. The insulation material and outside shield also shall be of adequate design to  
prevent attrition of the insulation due to normal operating conditions.  
2-3.5 Uninsulated piping and equipment that operate at liquid hydrogen temperatures shall  
not be installed above asphalt surfaces or other combustible materials to prevent contact of  
oxygen enriched liquefied air with such materials. Drip pans may be installed under  
uninsulated piping and equipment to control drips and vaporize condensed liquefied air.  
2-3.5.1 Where insulation materials are used, the insulation shall be compatible with the  
equipment with which the insulation is in contact.  
2-3.6 A piping system shall be substantially supported and protected against physical  
damage and excessive stresses arising from settlement, vibration, expansion, or  
contraction. Supports for aboveground piping shall be constructed of noncombustible  
material.  
2-3.7 Aboveground piping systems shall be protected from corrosion in compliance with  
recognized standards. Underground piping system shall be in compliance with section 5-3.  
2-3.8 Aboveground piping systems shall be marked in accordance with the following:  
(a) Marking shall include the name of the gas and direction of flow arrow.  
(b) Marking for piping systems shall be provided at the following locations:  
(i) At each critical process control valve.  
(ii) At wall, floor, or ceiling penetrations.  
(iii) At each change in direction.  
(iv) At a minimum of every 20 feet (6.1 meters) or fraction thereof throughout the piping  
run.  
2-3.9 Underground piping shall be installed on a bedding of at least 6 inches (15.24  
centimeters) of well-compacted backfill material.  
2-3.10 In areas subject to vehicle traffic, the pipe trench shall be of sufficient depth to  
permit a cover of not less than 18 inches (45.72 centimeters) of well compacted backfill  
material and pavement.  
Exception: In paved areas where a minimum of 8 inches (20.32 centimeters) of asphalt  
paving is used, the depth of the backfill between the topmost tier of piping and the paving  
can be reduced to not less than 8 inches (20.32 centimeters).  
Exception: In paved areas where a minimum of 6 inches (15.24 centimeters) of reinforced  
concrete paving is used, the depth of backfill between the topmost tier of the piping and  
the paving can be reduced to not less than 4 inches (10.2 centimeters).  
Page 62  
2-3.11 In areas not subject to vehicle traffic, the pipe trench shall be of sufficient depth to  
permit 6 inches (15.24 centimeters) each of bedding and cover of well-compacted backfill  
material. A greater burial depth shall be provided when required by the manufacturer's  
instructions.  
2-3.12 Piping within the same trench shall be separated by more than 3 times the diameter  
of the larger adjacent pipe.  
2-3.13 Piping to equipment shall be provided with an accessible, manual shutoff valve.  
2-3.14 Pipe, tubing, fittings, and other piping components shall be capable of withstanding  
a hydrostatic test of at least 3 times the rated pressure without structural failure as  
documented by the manufacturer.  
2-3.15 Underground liquefied H2 piping shall be vacuum-jacketed. Unjacketed piping shall  
not be buried and shall exit the container annular space above grade.  
2-3.16 All natural gas piping shall be installed in accordance with R 29.4601 et seq.  
2-3.17 All liquefied petroleum gas piping shall be installed in accordance with R 29.4001  
et seq.  
History: 2008 AACS.  
R 29.7082 Equipment assembly.  
Rule 82. Sections 2-4.1 and 2-4.2 are reproduced from NFPA 50B, and sections 2-4.3 to  
2-4.8 of the storage and handling of gaseous and Liquefied H2 code are added as follows:  
2-4 Equipment assembly.  
2-4.1 Valves, gauges, regulators, and other accessories shall be suitable for liquefied  
hydrogen service and for the pressures and temperatures involved.  
2-4.2 Installation of liquefied hydrogen systems shall be supervised by personnel familiar  
with proper installation practices and with their construction and use.  
2-4.3 Aboveground containers, piping, valves, regulating equipment, and other accessories  
shall be readily accessible and shall be protected against physical damage and against  
tampering.  
2-4.4 An automatic emergency shutoff valve shall be located in liquid product withdrawal  
lines as close to the container as practical.  
2-4.5 The automatic shutoff valve shall be provided with a remotely located, manually  
activated, shutdown control.  
2-4.6 The shutoff valve shall be connected to the storage container by means of welded  
connections without the use of flanges, or other appurtenances except that a manual shutoff  
valve equipped with welded connections is allowed to be installed immediately upstream  
of the automatic shutoff valve to allow for maintenance of the automatic valve.  
2-4.7 Connections downstream of the shutoff valve shall be in accordance with ASME  
B31.3, "Process Piping," adopted by reference in section 8.  
2-4.8 Cabinets or enclosures containing H2 control equipment shall be ventilated to prevent  
any accumulations of H2 gas.  
History: 2008 AACS.  
R 29.7083 Testing.  
Page 63  
Rule 83. Sections 2-5 and 2-5.1 are reproduced from NFPA 50B, and section 2-5.2 of the  
storage and handling of gaseous and Liquefied H2 code is added as follows:  
2-5 Testing.  
2-5.1 After installation, all field-erected piping shall be tested and proved hydrogen gas-  
tight at operating pressure and temperature.  
2-5.2 Containers, if out-of-service in excess of 1 year, shall be inspected and tested as  
outlined in 2-5.1. The pressure relief devices shall be checked to determine if they are  
operable, properly set, and within test service dates as per section 2-2.15.  
History: 2008 AACS.  
R 29.7084 Liquefied H2 vaporizers.  
Rule 84. Sections 2-6.1 to 2-6.4 are reproduced from NFPA 50B, and sections 2-6.5 to 2-  
6.13 of the storage and handling of gaseous and Liquefied H2 code are added as follows:  
2-6 Liquefied H2 vaporizers.  
2-6.1 The vaporizer shall be anchored and its connecting piping shall be sufficiently  
flexible to provide for the effect of expansion and contraction due to temperature changes.  
2-6.2 The vaporizer and its piping shall be protected on the hydrogen and heating media  
sections with pressure relief devices.  
2-6.3 Heat used in a liquefied hydrogen vaporizer shall be indirectly supplied utilizing  
media such as air, steam, water, or water solutions.  
2-6.4 A low-temperature shutoff switch or valve shall be provided in the vaporizer  
discharge piping to prevent flow of liquefied hydrogen in the event of the loss of the heat  
source.  
2-6.5 Vaporizers shall be designed for a working pressure at least equal to the maximum  
discharge pressure of the pump or the pressurized system that supplies them, whichever is  
greater.  
2-6.6 The discharge valve of each vaporizer, if provided, its piping components, the relief  
valves installed upstream of the discharge valve, the vaporizer piping, and related  
components shall be suitable for operation at a liquefied H2 temperature of -423 degrees  
Fahrenheit (217.2 degrees Celsius).  
2-6.7 Multiple vaporizers shall be manifolded such that both inlet and discharge block  
valves are installed on each vaporizer.  
2-6.8 A low temperature switch or other accepted means shall be installed on the vaporizer  
discharge to eliminate the possibility of cryogenic H2 entering gaseous H2 containers and  
other equipment not designed for cryogenic H2 temperatures.  
2-6.9 Relief valves on heated vaporizers shall be located so that they are not subjected to  
temperatures exceeding 140 degrees Fahrenheit (60 degrees Celsius) during normal  
operation unless they are designed to withstand higher temperatures.  
2-6.10 The combustion air required for the operation of integral heated vaporizers or the  
primary heat source for remote heated vaporizers shall be taken from outside an enclosed  
structure or building.  
2-6.11 Installation of internal combustion engines or gas turbines shall conform to R  
29.5101 et seq.  
Page 64  
2-6.12 Securing of vaporizers. Vaporizers, heat exchangers, and similar equipment shall  
be secured to foundations, and their connecting piping shall be flexible to provide for the  
effects of expansion and contraction due to temperature changes.  
2-6.13 Vaporizers and heaters shall be provided with instrumentation to monitor outlet  
temperatures.  
Exception: Ambient pressure-building coil vaporizers that are fed with liquid from, and  
return vapor to, a container.  
History: 2008 AACS.  
R 29.7085 Electrical systems.  
Rule 85. Sections 2-7 to 2-7.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-7 Electrical systems.  
2-7.1 Electrical equipment and wiring shall be specified and installed in accordance with  
NFPA 70, "National Electrical Code," adopted by reference in section 8.  
2-7.2 Static protection shall be required when liquefied H2 cargo transport vehicles are  
loaded or unloaded. This can be achieved when cargo transport vehicles or marine  
equipment are loaded or unloaded by grounding cable, conductive hose, flexible metallic  
tubing, or pipe connections where both halves of metallic couplings are in contact.  
History: 2008 AACS.  
R 29.7086 Bonding and grounding.  
Rule 86. Section 2-8 is reproduced from NFPA 50B as follows:  
2-8 Bonding and grounding. The liquefied hydrogen container and associated piping shall  
be electrically bonded and grounded.  
History: 2008 AACS.  
R 29.7087 Approval.  
Rule 87. Sections 2-9 and 2-9.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-9 Approval.  
2-9.1 Systems and all system components shall be listed or approved, including, but not  
limited to all of the following:  
(a) A container.  
(b) A pressure relief device, including a pressure relief valve.  
(c) A pressure gauge.  
(d) A pressure regulator.  
(e) A valve.  
(f) A vaporizer.  
(g) A hose and hose connection.  
(h) A vehicle fueling connection.  
Page 65  
(i) Electrical equipment related to the H2 system.  
(j) A dispenser.  
(k) Emergency shutoff valves.  
(l) Metal hydride storage.  
(m) Gas detection equipment and alarms.  
(n) H2 generators.  
(o) Pumps or compressors.  
(p) Stationary engine fuel system.  
History: 2008 AACS.  
R 29.7088 Pressure gauges.  
Rule 88. Sections 2-10 to 2-10.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-10 Pressure gauges.  
2-10.1 A pressure gauge, if provided, shall be capable of reading at least 1.2 times the  
system MAWP.  
2-10.2 Pressure gauges shall be installed on each pump and compressor discharge.  
History: 2008 AACS.  
R 29.7089 Pressure regulators.  
Rule 89. Sections 2-11 to 2-11.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-11 Pressure regulators.  
2-11.1 A pressure regulator inlet and each chamber shall be designed for its service  
pressure with a safety factor of at least 3.  
2-11.2 Pressure chambers shall provide for overpressure relief, if required.  
2-11.3 Regulators shall be designed, installed, or protected so that their operation is not  
affected by freezing rain, sleet, snow, ice, mud, insects, or debris. Regulator protection  
shall be permitted to be integral with the regulator.  
History: 2008 AACS.  
R 29.7090 Valves.  
Rule 90. Sections 2-12 to 2-12.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-12 Valves.  
2-12.1 Shutoff valves shall have a rated service pressure not less than the rated service  
pressure of the entire system and shall be capable of withstanding a hydrostatic test of at  
least 3 times the rated service pressure without rupture.  
2-12.1.1 Leakage shall not occur when tested at least 1.1 times the rated service pressure,  
using an inert gas compatible with industry practices.  
Page 66  
2-12.2 Valves of a design that allows the valve stem to be removed without removal of the  
complete valve bonnet or without disassembly of the valve body shall not be used.  
History: 2008 AACS.  
R 29.7091 Hose and hose connections.  
Rule 91. Sections 2-13 to 2-13.6 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-13 Hose and hose connections.  
2-13.1 Hose shall be constructed of or lined with materials that are resistant to corrosion  
and compatible with H2.  
2-13.2 Hose, metallic hose, flexible metal hose, tubing, and their connections shall be  
designed for the most severe pressures and temperatures expected under normal operating  
conditions with a burst pressure of at least 3 times the service pressure.  
2-13.3 Prior to use, hose assemblies shall be tested by the manufacturer or its designated  
representative at a pressure at least 1.1 times the service pressure.  
2-13.4 Hose and metallic hose shall be distinctly marked by the manufacturer either by the  
manufacturer's permanently attached tag or by distinct markings indicating the  
manufacturer's name or trademark, applicable service identifier and design pressure.  
2-13.5 The use of hose in an installation shall be limited to the following:  
(a) Vehicle fueling hose.  
(b) Inlet connection to compression equipment.  
(c) Section of metallic hose not exceeding 36 inches (1 meter) in length in the pipeline to  
provide flexibility where necessary.  
(d) Transfer hoses for connecting the mobile supply equipment to a local storage system.  
2-13.6 Each section shall be so installed that it is protected against mechanical damage and  
is readily visible for inspection.  
History: 2008 AACS.  
R 29.7092 Vehicle fueling connection.  
Rule 92. Sections 2-14 to 2-14.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-14 Vehicle fueling connection.  
2-14.1 Fueling receptacles and nozzles for liquefied H2 service shall be in accordance with  
a standard acceptable to the department based on the best interest of public health, safety,  
and welfare, and the environment.  
2-14.2 The use of adapters shall be prohibited.  
History: 2008 AACS.  
R 29.7093 Stationary pumps and compressors.  
Rule 93. Sections 2-15 to 2-15.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
Page 67  
2-15 Stationary pumps and compressors.  
2-15.1 Valves shall be installed such that each pump or compressor can be isolated for  
maintenance. Where pumps or centrifugal compressors are installed for operation in  
parallel, each discharge line shall be equipped with a check valve to prevent the backflow  
of liquid from 1 system to the other.  
2-15.2 Foundations for cryogenic pumps or compressors shall be designed and constructed  
to prevent frost heaving.  
2-15.3 Operation of all pumps and compressors shall cease when the facility's emergency  
shutdown device (ESD) system is initiated.  
2-15.4 Each pump shall be provided with an adequate vent or relief valve that will prevent  
over pressurizing of the pump case under normal conditions including the maximum  
possible rate of cool down.  
2-15.5 Vents shall be piped outside of buildings to a point of safe discharge.  
History: 2008 AACS.  
R 29.7094 Liquefied H2 to gaseous H2 systems.  
Rule 94. Sections 2-16 to 2-16.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
2-16 Liquefied H2 to gaseous H2 systems.  
2-16.1 Section 2-16 shall apply to the design, construction, installation, and operation of  
equipment used to produce gaseous H2 from liquefied H2.  
2-16.2 Gaseous H2 storage containers and equipment located downstream of liquefied H2  
containers are not regulated by section 2-16. Gaseous H2 storage containers and equipment  
shall comply with part 2 of these rules.  
2-16.3 In addition to the emergency shutdown systems described in section 7-6, the  
emergency shutdown system shall also shut off the liquid supply and power to the liquefied  
H2 transfer equipment necessary for producing gaseous H2 from liquefied H2.  
2-16.4 Transfer piping, pumps, and compressors shall be protected from vehicle collision  
damage and shall comply with section 2-1.5.  
History: 2008 AACS.  
R 29.7095 Temporary installations.  
Rule 95. Sections 2-17 and 2-17.1 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
2-17 Temporary installations.  
2-17.1 ASME or U.S. DOT containers that are used as portable storage containers, see  
definition of portable container in section 1-5, for temporary, less than 6 months at any  
given location, stationary service shall comply with the following:  
(a) If mounted on legs or supports, then such supports shall be of steel and either shall be  
welded to the container by the manufacturer at the time of fabrication or shall be attached  
to lugs that have been so welded to the container. The legs or supports or the lugs for the  
attachment of these legs or supports shall be secured to the container in accordance with  
Page 68  
the code or rule under which the container was designed and built, to withstand loading in  
any direction equal to twice the weight of the empty container and attachments.  
(b) If the container is mounted on a trailer or semitrailer running gear so that the unit can  
be moved by a conventional over-the-road tractor, then attachment to the vehicle, or  
attachments to the container to make it a vehicle, shall comply with the appropriate U.S.  
DOT requirements for cargo tank service. The unit also shall comply with applicable state  
and U.S. DOT motor carrier regulations and shall be approved by the department.  
History: 2008 AACS.  
R 29.7096 Indoor fueling.  
Rule 96. Section 2-18 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
2-18 Indoor fueling. Indoor fueling of liquefied H2 is not permitted unless department  
approved.  
History: 2008 AACS.  
Chapter 3 Location of liquefied hydrogen systems  
R 29.7097 General requirements.  
Rule 97. Sections 3-1.1 and 3-1.3 to 3-1.5 are reproduced from NFPA 50B, and sections  
3-1.2, 3-1.6 to 3-1.13 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
3-1 General requirements.  
3-1.1 The storage containers shall be located so that they are readily accessible to mobile  
supply equipment at ground level and to authorized personnel. Roadways or other means  
of access for emergency equipment, such as fire department apparatus, shall be provided.  
3-1.2 Systems shall not be located beneath or where exposed by failure of the following:  
(a) Electric power lines as follows:  
(i) Not less than 50 feet (15.2 meters) horizontally from the vertical plane below the  
nearest overhead wire of an electric trolley, train, or bus line.  
(ii) Not less than 5 feet (1.5 meters) horizontally from the vertical plane below the nearest  
overhead electrical wire.  
(b) Piping containing all classes of flammable and combustible liquids  
(c) Piping containing oxidizing materials  
3-1.3 Where a liquefied hydrogen container is installed on ground that is level with or lower  
than the adjacent storage of all classes of flammable and combustible liquid or liquid  
oxygen, suitable protective means shall be taken to prevent accumulation of liquids within  
50 ft (15.2 m) of the liquefied hydrogen container. Protective means shall include diking,  
diversion curbs, or grading of the flammable and combustible liquid storage or liquid  
oxygen storage.  
3-1.4 Storage sites shall be fenced and posted to prevent entrance by unauthorized  
personnel. Sites also shall be placarded as follows:  
Page 69  
LIQUEFIED HYDROGEN FLAMMABLE GAS NO SMOKING - NO OPEN FLAMES  
3-1.5 If liquefied hydrogen is located (as specified in table 3-2.1) in a separate building, in  
a special room, or inside buildings where not in a special room or exposed to other  
occupancies, containers shall have the pressure relief devices vented unobstructed to the  
outdoors at a minimum elevation of 25 ft (7.6 m) above grade to a safe location as required  
in 2-2.3.  
3-1.6 Underground systems shall be located underground, mounded, or partially buried and  
outside of any buildings. Buildings shall not be constructed over any underground,  
mounded, or partially buried container. Sides of adjacent containers shall be separated by  
not less than 3 feet (1 meter).  
(a) Excavation for underground, mounded, or partially buried containers shall be made  
with due care to avoid damage to an existing structure or its foundation. Containers shall  
not be installed where loads from adjacent structures may be transmitted to the container.  
A structure or foundation of a structure on the same property shall not be erected or  
constructed within 10 feet (3.1 meters) of any point on the container surface, unless the  
footings extend to the bottom of the container. A container shall not be installed less than  
10 feet (3.1 meters) from the nearest wall of any basement, pit, or property line.  
3-1.7 All underground containers shall be set on firm foundation and surrounded with 6  
inches (15.24 centimeters) minimum of noncorrosive inert material such as clean sand or  
pea gravel.  
3-1.8 Underground or mounded containers shall be covered with not less than 2 feet (60.96  
centimeters) of earth or with not less than 1 foot (30.48 centimeters) of earth on top of  
which shall be placed a reinforced concrete slab not less than 4 inches (10.16 centimeters)  
thick. If containers are likely to be subjected to traffic, they shall be protected against  
damage from vehicles passing over them by at least 3 feet (1 meter) of earth cover plus 6  
inches (15.24 centimeters) of reinforced concrete. When reinforced concrete paving is used  
as part of the protection, it shall extend at least 1 foot (30.48 centimeters) horizontally  
beyond the outline of the container in all directions.  
(a) The vertical extension of the vacuum jacket required for service connections shall be  
allowed to extend above grade.  
3-1.9 Containers installed in an area subject to flooding, high water table, or other buoyant  
forces shall be safeguarded from movement by anchoring or other means acceptable to the  
department based on the best interests of public health, safety, and welfare and the  
environment.  
3-1.10 Where a liquefied H2 container is installed on ground that is level with or lower than  
the adjacent storage of all classes of flammable and combustible liquid or liquid oxygen,  
suitable protective means shall be taken to prevent accumulation of liquids within 50 feet  
(15.2 meters) of the liquefied H2 container. Protective means shall include diking, diversion  
curbs, or grading of the flammable and combustible liquid storage or liquid oxygen storage.  
3-1.11 Aboveground liquefied H2 systems shall be fenced and posted to prevent entrance  
by unauthorized personnel.  
Exception: Liquefied H2 dispensers may be located outside the fence.  
3-1.12 Underground installations shall be deemed to provide engineered protection from  
overhead power lines.  
3-1.13 Venting of underground containers. Venting systems for underground storage  
containers shall be in accordance with CGA G-5.5, adopted by reference in section 8.  
Page 70  
History: 2008 AACS.  
R 29.7098 Specific requirements.  
Rule 98. Sections 3-2.1, 3-2.4 and table 3-2.1 are reproduced from NFPA 50B, and  
sections 3-2.2, 3-2.2.1, 3-2.3, 3-2.5 to 3-2.8 and table 3-2.2 of the storage and handling of  
gaseous and Liquefied H2 code are added as follows:  
3-2 Specific requirements.  
3-2.1 The location of liquefied hydrogen storage, as determined by the maximum total  
quantity of liquefied hydrogen, shall be in the order of preference indicated by the Roman  
numerals in table 3-2.1.  
Table 3-2.1 Preferred Locations of Liquefied Hydrogen Systems  
Size of Hydrogen Storage  
39.63 gal to 50 gal 51 gal to 300 gal 301 gal to  
In excess of  
600 gal  
(150 L to 189.25 L)  
600 gal  
Nature of Location  
(193.03 L to  
1135.5 L)  
(1139.29 L to  
(2271 L)  
2271 L)  
Outdoors  
I
I
I
I
In a separate building  
In a special room  
Inside buildings  
II  
III  
II  
III  
II  
Not permitted  
Not permitted  
Not permitted  
IV  
Not permitted  
Not permitted  
Not permitted  
Not in a special room or  
exposed to other occupancies  
3-2.2 The minimum distance in feet from liquefied H2 systems of indicated storage capacity  
located either outdoors, in a separate building, or in a special room to any specified  
exposure shall be in accordance with table 3-2.2.  
Exception: The distances in numbers 1, 4, 6, 7, 8, and 11 in table 3-2.2 may be reduced by  
2/3, but not to less than 5 feet (1.5 meters), for insulated portions of the systems. For  
uninsulated portions of the system, the distances may be reduced by the use of protective  
structures having a minimum fire resistance rating of 2 hours. The protective structure or  
the insulated liquefied H2 container shall interrupt the line of sight between uninsulated  
portions of the liquefied H2 storage system and the exposure.  
(a) An aboveground H2 storage container system shall be erected per table 3-2.2 but not  
less than 75 feet (22.9 meters) from any of the following:  
(i) A school.  
(ii) A church.  
(iii) A hospital.  
(iv) A theater.  
(v) Assembly occupancy for 50 or more persons.  
Exception: The restrictions in section 3-2.2(a) shall not apply to an aboveground H2 system  
used exclusively for stationary power generation.  
Page 71  
3-2.2.1 Loose or piled combustible materials and weeds and long dried grass shall not be  
permitted within 10 feet (3.1 meters) of any system.  
Table 3-2.2 Minimum Distance from Liquefied Hydrogen Systems to Exposures  
Total Liquefied H2 Storage  
39.63 gal to  
3,500 gal (ft)  
3,501 gal to  
15,000 gal (ft)  
15,001 gal to  
75,000 gal (ft)  
Type of Exposure  
1. Building or structure  
(a) Wall(s) adjacent to system constructed of  
non-combustible or limited-combustible materials  
(1) Sprinklered building or structure or unsprinklered  
building or structure having noncombustible contents  
(2) Unsprinklered building or structure with  
combustible contents.  
5a  
5a  
5a  
25  
5
50  
5
75  
5
Adjacent wall(s) with fire resistance rating less than 3  
hoursb  
Adjacent wall(s) with fire resistance rating of 3 hours or  
greaterb  
(b) Wall(s) adjacent to system constructed of  
combustible materials  
50  
50  
50  
75  
50  
(1) Sprinklered building or structure  
(2) Unsprinklered building or structure  
2. Wall openings  
100  
(a) Openable  
(b) Unopenable  
75  
25  
75  
50  
75  
50  
3. Air compressor intakes or inlets for air-conditioning  
or ventilating equipment  
75  
75  
75  
4. All classes of flammable and combustible liquid  
containers (above ground, and vent or fill openings if  
below ground) (see 3-1.3)c  
50  
75  
100  
5. Between stationary liquefied H2 containers  
6. Flammable gas storage other than H2  
7. Liquid oxygen storage and other oxidizers (see 3-1.3)  
8. Combustible solids  
5
5
5
50  
75  
50  
50  
75  
25  
10  
25  
75  
75  
75  
50  
75  
50  
10  
50  
75  
75  
100  
50  
75  
75  
10  
50  
9. Open flames and welding  
10. Places of public assembly for 50 or more persons  
11. Public ways, railroads, and property lines  
12. Inlet to underground sewers  
13. Places of public assembly less than 50 people  
14. Flammable/Combustible liquid dispenser other than  
H2  
10  
10  
10  
For SI units: 1 ft = 0.305 m; 1 gal = 3.785 L.  
Page 72  
a Portions of wall less than 10 ft (3 m) (measured horizontally) from any part of a system shall have a fire  
resistance rating of at least 1/2 hour.  
b Exclusive of windows and doors.  
c Distances can be reduced to 15 ft (4.6 m) for class IIIB combustible liquids.  
3-2.3 Cargo transport unloading. Unloading connections on delivery equipment shall not  
be positioned closer to any of the exposures cited in table 3-2.2 than the distances given  
for the storage system. The following shall apply:  
(a) For stationary container system installations or stationary multiple container systems  
utilizing a common or manifolded transfer line, or railroad tank car transfer systems to fill  
trucks with no stationary storage involved shall comply with all of the following:  
(i) Owners and operators shall ensure that fixed piping is used between the container and  
master shutoff and check valves. The piping and manifolds shall be secured to the container  
frame. Flexible hoses are permitted between the check valve and the cargo vehicle  
unloading connection.  
Exception: Bulkheads will be located at a minimum of 1.5 feet (45.72 centimeters) when  
crash protection is provided at 10 feet (3.1 meters) from storage container.  
(ii) Emergency shutoff valves required in this section shall be tested annually for proper  
operation. The results of the tests shall be documented.  
(iii) All installations shall have at least 1 clearly identified and easily accessible manually  
operated remote emergency shutoff device. Within 1 year after the effective date of these  
rules, existing installations shall have at least 1 clearly identified and easily accessible  
manually operated remote emergency shutoff device. The emergency shutoff device shall  
be located not less than 20 feet (6.1 meters) nor more than 100 feet (30.5 meters) in the  
path of egress from the emergency shutoff valve and not less than 20 feet (6.1 meters) from  
the container system.  
(iv) During transfer of H2 to and from cargo vehicles, the hand or emergency brake of the  
vehicle shall be set, and chock blocks shall be used to prevent rolling of the vehicle.  
(v) Transfer systems shall be capable of depressurizing to facilitate disconnection. Bleed  
connections shall lead to a safe point of discharge.  
(vi) Cargo vehicle shall be equipped with air-brake interlock in front of the unloading  
connection to protect against drive-away.  
(b) The delivery vehicle shall be located so that all parts of the vehicle are on the premises  
when delivery is made, and shall comply with all of the following:  
(i) Vent connections shall be provided so that loading arms and hoses can be  
depressurized and vented prior to disconnection if necessary. The connections for liquefied  
H2 shall be piped to a vent stack in accordance with part 2, section 2-2.2.  
(ii) When transfers are made into fueling facility containers, the liquefied H2 shall be  
transferred at a pressure that shall not over-pressurize the receiving container.  
(iii) The transfer piping shall be equipped with a check valve to prevent backflow from  
the container being filled to the transport vehicle. Check valve shall be located as close as  
practicable to the container.  
(iv) If the fueling facility container or transfer equipment is located in a remote area  
relative to the delivery vehicle operating status indicators, that is those that indicate  
container level, these container status indicators shall be provided in the unloading area.  
Page 73  
(v) At least 1 qualified person shall be in continuous attendance and shall have an  
unobstructed view of the transfer point while unloading is in progress.  
(vi) Sources of ignition shall not be permitted in the unloading area while transfer is in  
progress.  
(vii) The cargo transport vehicle's engine shall be shut off while the transfer hose or piping  
is being connected or disconnected. If required for liquefied H2 trailer pumping transfer,  
the engine pump drive motor may be started and used during the liquid transfer operations.  
3-2.4 The minimum distance of container fill connections from parked vehicles shall be 25  
ft (7.6 m).  
3-2.5 An owner and operator shall ensure that a container systems are properly designed  
and constructed in accordance with the ASME and that any portion, which is underground,  
mounded, or partially underground, is protected from corrosion by either of the following:  
(a) The ASME approved container system is cathodically protected by all the following  
requirements:  
(i) The ASME approved container system is coated with a suitable dielectric material  
approved by the department.  
(ii) Factory-installed or field-installed cathodic protection systems are designed by a  
corrosion expert or in accordance with the NACE recommended practice RP0285 entitled  
"Corrosion Control of Underground Storage Tank Systems by Cathodic Protection" or  
impressed current systems are designed to allow a determination of current operating status  
as required in section 5.4-1 of the H2 code.  
(iii) Cathodic protection systems are operated and maintained in accordance with the  
provisions of section 5.4-1 of the H2 code.  
(b) Other methods as approved by the department and in the best interest of public health,  
safety, and welfare, and the environment.  
3-2.6 Out-of-service aboveground containers.  
3-2.6.1 Containers that are no longer in service for a period of 12 months shall be closed.  
To close the aboveground container, the owner or operator shall empty the container, purge  
it with an inert gas and safeguard it against tampering. Piping that is removed from service  
shall be purged with an inert gas and capped or removed.  
3-2.6.2 Each container that is to be reused at the original location or a new location shall  
be purged with an inert gas and be in compliance with all the requirements for the  
installation of a new container, and shall be recertified by the manufacturer, or authorized  
representative, and tested in accordance with the container's design specifications or be  
pressure tested with an inert gas or H2 at 1.1 times the MOP for not less than 10 minutes.  
Piping that is to be reused shall be in compliance with all the requirements for the  
installation of new piping and shall be tested in compliance with section 3-2.8 of this code  
prior to being brought back into service.  
3-2.7 Out-of-service underground, mounded, and partially buried containers.  
3-2.7.1 Containers that are no longer used to store H2 and are not intended to be brought  
back into service shall be permanently closed. To permanently close the container, the  
container shall be emptied and purged with an inert gas to render the container free of H2,  
and then the container shall be removed from the ground. When a structure above or near  
the container prevents removal, the container shall be emptied and purged with an inert gas  
to render the container free of H2, then the container shall be filled with an inert solid  
Page 74  
material. Piping that is permanently removed from service shall be purged with an inert  
gas and capped or removed.  
3-2.7.2 Containers may be rendered temporarily out-of-service only when it is intended  
they be brought back into service at a later date. To temporarily close a container, all of the  
following requirements shall be met:  
(a) The container shall be emptied and purged with an inert gas.  
(b) Corrosion protection for the container and all underground piping shall be maintained  
in compliance with section 5-4.1 of this code.  
(c) The vent line shall remain functional.  
(d) The container shall be secured against tampering.  
(e) Piping that is temporarily removed from service shall be purged with an inert gas and  
capped.  
3-2.7.2.1 Each container that is temporarily out-of-service greater than 12 months shall be  
pressure tested with an inert gas at 1.1 times the MOP for not less than 10 minutes prior to  
being brought back into service. Temporarily out-of-service piping shall be tested in  
compliance with section  
3-2.8 of this code prior to being brought back into service.  
3-2.8 Testing. After installation, prior to being placed into service, all container  
connections, piping, tubing, hose, and hose assemblies shall be tested by an approved  
method as outlined in ASME B31.3 "Process Piping," adopted by reference in section 8,  
or by a method acceptable to the department based on the best interest of public health,  
safety, and welfare, and the environment.  
History: 2008 AACS.  
R 29.7099 Handling of liquefied H2 inside buildings other than separate buildings and  
special rooms.  
Rule 99. Sections 3-3 and 3-3.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-3 Handling of liquefied H2 inside buildings other than separate buildings and special  
rooms.  
3-3.1 Portable liquefied H2 containers of 50-gallons (189-Liters) or less capacity as  
permitted in Table 3-2.1 and in compliance with section 3-1.5 where housed inside  
buildings not located in a special room and exposed to other occupancies shall comply with  
the following minimum requirements.  
(a) Containers shall be located 20 feet (6.1 meters) from all classes of flammable and  
combustible liquids and readily combustible materials such as excelsior or paper.  
(b) Containers shall be located 15 feet (4.6 meters) from ordinary electrical equipment,  
and 25 feet (7.6 meters) from open flames, welding or other sources on ignition.  
(c) Containers shall be located 50 feet (15 meters) from storage of oxidizing gases.  
(d) Containers shall be protected against damage or injury due to falling objects or work  
activity in the area.  
(e) Containers shall be firmly secured and stored in an upright position and protected  
against damage in accordance with the provisions of section 2-1.7.  
(f) Pressure relief devices on the containers shall be vented directly outdoors or to a hood  
that is suitable for flammable and combustible vapors.  
Page 75  
History: 2008 AACS.  
R 29.7100 Location of dispensing operations and equipment.  
Rule 100. Sections 3-4 to 3-4.4 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-4 Location of dispensing operations and equipment.  
3-4.1 Dispensing equipment located outdoors shall be in accordance with the following:  
(a) Dispensing equipment shall be allowed under weather protection in accordance with  
the requirements of section 4-5 and constructed in a manner that prevents the accumulation  
of H2 gas.  
3-4.2 Dispensing equipment shall not be beneath electric power lines or where exposed by  
their failure, and shall be a minimum of 10 feet (3.1 meters) from the nearest important  
building or property line or 20 feet (6.2 meters) from any activity that involves a fixed  
source of ignition.  
3-4.3 Dispensing equipment shall be located so that all parts of the vehicle being served  
are on the premises of the motor fuel dispensing facility.  
3-4.4 Dispensing equipment shall be protected against collision damage by means  
acceptable to the department. Dispensing devices shall be securely bolted in place.  
Dispensing devices shall be installed in accordance with manufacturer's instructions.  
History: 2008 AACS.  
R 29.7101 Installation of emergency shutdown equipment.  
Rule 101. Sections 3-5 to 3-5.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
3-5 Installation of emergency shutdown equipment.  
3-5.1 Breakaway protection shall be provided in a manner such that, if a pullaway event  
occurs, liquefied H2 will cease to flow at any separation.  
3-5.2 A breakaway device shall be installed at every dispensing point. Such a device shall  
be arranged to separate by a force not greater than 150 pounds (75 kilograms), when applied  
in any direction that the vehicle would move. Breakaway devices shall be compatible with  
a standard acceptable to the department.  
History: 2008 AACS.  
Chapter 4 Design considerations at specific locations  
R 29.7102 Outdoor locations.  
Rule 102. Sections 4-1 to 4-1.4 are reproduced from NFPA 50B as follows:  
4-1 Outdoor locations.  
4-1.1 Roadways and yard surfaces located below liquefied hydrogen piping as well as areas  
under the fill connections and delivery vehicle's uninsulated hydrogen piping from which  
Page 76  
liquid air can drip shall be constructed of noncombustible materials. For the purposes of  
this standard, asphaltic and bitumastic paving shall be considered combustible. If  
expansion joints are used, fillers also shall be of noncombustible materials.  
4-1.2 If walls, roofs, weather shelters, or canopies are provided, they shall be constructed  
of noncombustible or limited-combustible materials.  
4-1.3 Electrical wiring and equipment shall comply with section 2-7.  
4-1.4 Lighting shall be provided for nighttime transfer operation.  
History: 2008 AACS.  
R 29.7103 Specific requirements.  
Rule 103. Sections 4-2 to 4-2.2.3 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
4-2 Specific requirements.  
4-2.1 The location of liquefied H2 storage, as determined by the maximum total quantity  
of liquefied H2, shall be in accordance with table 3-2.1.  
4-2.2 Installation of liquefied H2 inside buildings other than detached buildings and gas  
rooms.  
4-2.2.1 More than 1 system of 50 gallons (189.5 liters) or less capacity may be installed in  
the same room or area outside of special rooms located as allowed in table 3-2.1 and in  
compliance with section 4-2.1, provided the systems are separated by at least 50 feet (50.2  
meters) or by a full height fire-resistive partition having a minimum fire resistance rating  
of 2 hours is located between the systems.  
4-2.2.2 The separation distance between multiple systems of 50 gallons (189.5 liters) or  
less may be reduced to 25 feet (7.6 meters) in buildings where the space between storage  
areas is free of combustible materials and protected with a sprinkler system.  
4-2.2.3 When sprinkler protection is provided, the area in which the H2 is stored or used  
shall be protected with a sprinkler system designed to be not less than that required by  
NFPA 13 for extra hazard group 1 with a minimum design area of 2,500 square feet (762  
square meters).  
History: 2008 AACS.  
R 29.7104 Separate buildings.  
Rule 104. Sections 4-3 to 4-3.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-3 Separate buildings.  
4-3.1 Separate buildings containing more than 300 gallons (1137 liters) of liquefied H2  
shall be constructed of noncombustible or limited-combustible materials on a substantial  
frame. Walls and roofs shall be lightly fastened. All venting elements shall be designed to  
relieve at a maximum pressure of  
25 pounds/square foot. Doors shall be located in such a manner that they are readily  
accessible to personnel in an emergency. Exception: Window glazing may be of plastic.  
Exception: Explosion venting shall be in accordance with section 4-4.3.  
Page 77  
4-3.2 Ventilation to the outdoors shall be provided. Inlet openings shall be located within  
18 inches (45.72 centimeters) of the floor in exterior walls only. Outlet openings shall be  
located at the high point of the room in exterior walls or roof. Both the inlet and outlet vent  
openings shall have a minimum total area of 1 square foot/1000 cubic foot (0.3 square  
meters/305 cubic meters) of room volume. Discharge from outlet openings shall be directed  
or conducted to a location that allows for dissipation of the exhaust air in the ambient  
surroundings away from air intakes and occupied spaces.  
4-3.3 There shall be no sources of ignition within the room or area where the H2 system is  
installed.  
4-3.4 Electrical wiring and equipment shall comply with section 2-7.  
Exception: All electrical wiring and equipment in the separate building shall be class I,  
division 2, group B.  
4-3.5 Heating, if provided, shall be by indirect means such as steam or hot water.  
Exception: Electrical heating shall be in accordance with section 4-3.4.  
History: 2008 AACS.  
R 29.7105 Special rooms.  
Rule 105. Sections 4-4 to 4-4.9.1, and table 4-4.9 of the storage and handling of gaseous  
and Liquefied H2 code are added as follows:  
4-4 Special rooms.  
4-4.1 Floors, walls, and ceiling shall be constructed of noncombustible or limited-  
combustible materials. Interior walls or partitions shall have a fire resistance rating of at  
least 2 hours, shall be continuous from floor to ceiling, and shall be securely anchored. At  
least 1 wall shall be an exterior wall. Windows and doors shall be located so as to be readily  
accessible in case of emergency.  
Exception: Window glazing may be of plastic.  
4-4.1.1 Access from within the primary structure shall be made through 1 vapor-sealing, 2  
hour, self-closing fire door.  
4-4.2 Ventilation shall be provided as in section 4-4.3.  
4-4.3 Deflagration venting shall be provided in exterior walls or roof only.  
4-4.3.1 Vents shall be any 1 or any combination of the following:  
(a) Walls of light material.  
(b) Lightly fastened hatch covers.  
(c) Lightly fastened, outward opening doors in exterior walls.  
(d) Lightly fastened walls or roof.  
(e) Other methods in accordance with NFPA 69, adopted by reference in section 8.  
4-4.3.2 Where applicable, snow loads shall be considered.  
4-4.3.3 The venting area shall be equal to not less than 1 cubic foot/30 cubic feet (1 cubic  
meter/9 cubic meters) of room volume.  
4-4.4 There shall be no sources of ignition.  
4-4.5 Electrical wiring and equipment shall comply with section 2-7, except that all  
electrical wiring and equipment in the special room shall be class I, division 2, group B.  
4-4.6 Heating, if provided, shall be by steam, hot water, or other indirect means.  
Exception: Electrical heating shall be in accordance with section 4-4.5.  
4-4.7 Room ventilation.  
Page 78  
4-4.7.1 The ventilation shall be at least 1 cubic foot/minute/square foot of room area, but  
not less than 1 cubic foot/minute/12 cubic feet of room volume and shall be designed such  
that an accumulation of H2 at a concentration equal to or greater than 25% of the lower  
flammable limit shall not occur in any part of the room.  
4-4.7.2 Ventilation shall be by a continuous mechanical ventilation system or by a  
mechanical ventilation system activated by a continuously monitoring H2 detection system  
where a gas concentration of not more than 25% of the lower flammable limit is present.  
4-4.7.3 Where installed, a gas detection system shall be equipped to sound an alarm and  
visually indicate when a maximum of 25% of the lower flammable limit is reached.  
4-4.7.4 Any failure of the ventilation system shall immediately shut down the fueling  
system and provide notification to the system operator. Reactivation of the fueling system  
shall be by manual restart and shall be conducted by trained personnel.  
4-4.7.5 The gas detection system shall function during ventilation system maintenance  
operations.  
4-4.7.6 A ventilation system for a room within or attached to another building shall be  
designed to ensure that all areas serviced by the ventilation system meeting performance  
requirements in accordance with section 4-4.7 during the normal operating conditions and  
during alarm conditions.  
4-4.8 Warning signs.  
4-4.8.1 Access doors shall have warning signs with the words "WARNING - NO  
SMOKING - NONORDORIZED FLAMMABLE GAS - CRYOGENIC LIQUID - COLD  
GAS - NO OPEN FLAMES." The wording shall be in plainly legible, bright red letters  
not less than 1 inch (2.54 centimeters) high on a white background.  
4-4.9 Indoor attended gaseous H2 fast-fill fueling.  
4-4.9.1 Attended indoor fast-fill fueling system shall be in accordance with subsections (a)  
to (k) of this section.  
(a) Gas storage equipment shall be located outdoors unless approved by the department.  
Gas processing and compression equipment shall be listed or approved for indoor use or  
located outdoors.  
(b) An emergency manual shutdown device shall be located in the dispensing area not  
less than 20 feet (6.1 meters) and not more than 100 feet (30.5 meters) in the path of egress  
from the dispensing area. Actuation of the emergency manual shutdown device shall  
perform in accordance with subsection (h) of this section.  
(c) The dispenser shall be equipped with a gas detection system which shall actuate in  
accordance with subsection (h) of this section when a maximum of 25% of LFL is detected  
(1% H2 in air).  
(d) The dispenser shall be equipped with a leak detection system capable of identifying a  
leak from the dispensing system outside the dispenser housing by conducting a pre-fill  
pressure test. The leak detection must be capable of detecting a minimum leak rate of 1.9  
gallon/minute (7.2 liter/minute) and shall actuate in accordance with subsection (h) of this  
section when a leak is detected.  
(e) Whether the fill is communicated or non-communicated, the dispensing system must  
be listed, labeled or approved to insure that the fills are protective of the safety of the  
temperature, pressure and flow rate limits of the on-board fuel system during fueling.  
(f) The dispensing area shall be equipped with a fire detection system and shall actuate in  
accordance with subsection (i) of this section if a fire is detected.  
Page 79  
(g) A ventilation system shall be installed for the dispensing area. The ventilation system  
shall be capable of delivering ventilation air as provided in section 4.3.7. The ventilation  
system shall operate prior to dispenser operation, during fueling, and for at least 1 minute  
after fueling has been completed. The ventilation flow rate shall be monitored. Failure or  
reduction of the ventilation flow rate below the required flow rate shall shut down the  
dispensing system.  
Exemption: A dispensing area ventilation system is not required when the fuel delivery per  
refueling event is less than those listed in table 4-4.9.  
Table 4-4.9  
Maximum fuel delivery per refueling event  
that does not require room ventilation (kg)  
Room Size (m3)  
1000  
2000  
3000  
4000  
0.8  
1.7  
2.5  
3.3  
4.2  
5000  
(h) The actuation of any 1 of the systems listed in subsections (b) to (g) of this section  
shall shut down the dispenser, stop the flow of gas into the room, and start or continue to  
run the ventilation system, if required, it shall be in accordance with table 4-4.9.  
(1) Reactivation of the dispenser and gas flow into the room shall be by manual restart  
and shall be conducted by trained personnel.  
(i) Interior walls, doors, and window openings within 15 feet (4.6 meters) of the dispenser  
shall be constructed of materials having a fire rating of at least 2 hours. Wall penetrations  
shall require use of listed fire-rated equipment.  
(j) The owner/operator shall not allow hot work/open flames within 15 feet (4.6 meters)  
of the refueling location unless the dispenser is shut down, depressurized, and purged.  
(k) If H2 is to be removed from the vehicle storage system, H2 shall be discharged into a  
closed transfer system or vented outdoors in accordance with CGA G-5.5, "Hydrogen Vent  
Systems," as adopted by reference in section 8.  
History: 2008 AACS.  
R 29.7106 Canopies.  
Rule 106. Sections 4-5 to 4-5.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-5 Canopies.  
4-5.1 A container installation that has a canopy or roof shall have prior approval by the  
department based on the best interests of public health, safety, and welfare and the  
environment. This canopy or roof shall not limit the dissipation of heat or dispersion of  
flammable vapors and cannot restrict firefighting access and control.  
4-5.2 A roof or canopy shall meet all of the following conditions:  
(a) The lowest elevation of the roof or canopy shall not be less than 4 feet (1.8 meters)  
from the top of the container.  
(b) All container vent(s) are extended through the roof or canopy.  
Page 80  
(c) The roof or canopy is constructed in such a way that it will not allow for vapors to  
accumulate under the canopy or roof.  
(d) Constructed of non-combustible materials.  
History: 2008 AACS.  
R 29.7107 Outdoor fill station.  
Rule 107. Sections 4-6 to 4-6.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
4-6 Outdoor fill station.  
4-6.1 Each line between a liquid storage facility and a dispenser at a fill station shall have  
a valve that closes when 1 of the following occurs:  
(4) The power supply to the dispenser is cut off.  
(5) Any emergency shutdown device at the refueling station is activated.  
4-6.2 A manual shutoff valve shall be provided at a fill station upstream of the breakaway  
device specified in section 3-5, where it is readily accessible to the person dispensing H2,  
unless 1 of the following occurs:  
(a) The self-closing valve referred to in section 4-6.1 is located immediately upstream of  
the dispenser.  
(b) The dispenser is equipped with a self-closing valve that closes each time the dispenser  
is turned to the off position or when an emergency device is activated.  
4-6.3 The liquid hydrogen dispenser shall provide a means to safely vent all hydrogen that  
may become trapped in sections of the dispenser between closed valves in all shut down  
modes including loss of power.  
History: 2008 AACS.  
Chapter 5 Operation  
R 29.7108 Operation.  
Rule 108. Section 5-1 is reproduced from NFPA 50B, and sections 5-1.1 to 5-1.9 of the  
storage and handling of gaseous and Liquefied H2 code are added as follows:  
5-1 Operation. For installations that require any operation of equipment by the user,  
instructions shall be maintained at operating locations.  
5-1.1 Where an overpressure incident that results in operation of the overpressure  
protection system of the dispenser occurs, the dispenser pressure control system shall be  
examined and certified by a qualified operator prior to being returned to service.  
5-1.2 Liquefied H2 fueling facilities shall be designed so that, in the event of a power  
failure, the system shall go into fail-safe condition.  
5-1.3 The maximum delivery pressure at the vehicle tank inlet shall not exceed the  
maximum allowable pressure of the vehicle fuel tanks.  
5-1.4 Hose and arms shall be equipped with a shutoff valve at the fuel end and a breakaway  
device that meets the requirements of section 3-5 to minimize release of liquid and vapor  
Page 81  
in the event that a vehicle pulls away while the hose remains connected. Such a device shall  
be installed and maintained in accordance with the manufacturer's instructions.  
5-1.5 When not in use, hose shall be secured to protect it from damage.  
5-1.6 Where a hose or arm of nominal 3 inches (7.62 centimeters) diameter or larger is  
used for liquid transfer or where 1 of nominal 4 inches (10.16 centimeters) diameter or  
larger is used for vapor transfer, an emergency shutoff valve shall be installed in the piping  
of the transfer system within 10 feet (3.1 meters) from the nearest end of the hose or arm.  
5-1.6.1 Where either a liquid or vapor line has 2 or more legs, an emergency shutoff valve  
shall be installed either in each leg or in the line before the legs.  
5-1.7 Bleed or vent connections shall be provided so that loading arms and hose can be  
drained and depressurized prior to disconnection, if necessary. These bleed or vent  
connections shall lead to a safe point of discharge.  
5-1.8 A fueling connector and mating vehicle receptacle shall be used for reliable, safe,  
and secure transfer of liquefied or gaseous H2 to or from the vehicle with minimal leakage.  
5-1.8.1 The fueling connector either shall be equipped with an interlock device that  
prevents release while the line is open or shall have self-closing ends that automatically  
close upon disconnection.  
5-1.9 The transfer of liquefied H2 into vehicular onboard fuel supply containers shall be  
performed in accordance with the manufacturer's instructions. The dispenser  
manufacturer's instructions shall be posted at the dispensing device.  
History: 2008 AACS.  
R 29.7109 Maintenance.  
Rule 109. Sections 5-2 to 5-2.11 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-2 Maintenance.  
5-2.1 Hoses, nozzles, and breakaways shall be examined visually to ensure that they are  
safe for use and shall be maintained in accordance with manufacturer's instructions on at  
least a quarterly basis, or if required by the manufacturer.  
5-2.2 Hose shall be tested for leaks per manufacturer's requirements, and any leakage shall  
be a reason for rejection and replacement.  
5-2.3 Testing shall be carried out with helium or with helium/ H2 blend as the test gas or if  
this is not possible, with H2 using suitable precautions.  
5-2.4 The facility operator shall maintain a maintenance log in good condition and  
accessible to department inspection. Records shall be maintained for a minimum of 2 years.  
5-2.5 Controllers on fuel stations shall be designed to verify the integrity of the fuel hose,  
breakaway, nozzle, and receptacle by pressurizing these components to at least the vehicle  
back pressure and checking pressure drop prior to the start of fueling.  
5-2.6 Containers and their appurtenances, piping systems, compression equipment,  
controls, and detection devices shall be maintained in operating condition and according to  
manufacturer's instructions.  
5-2.7 Pressure relief valves shall be maintained in operating condition.  
5-2.8 Maintenance personnel shall be trained in leak detection procedures.  
5-2.9 Area within 10 feet (3.1 meters) of dispenser shall be free from debris, weeds and  
other material that present a fire hazard.  
Page 82  
5-2.10 Safety, gas detection, and fire protection equipment shall be tested or inspected at  
intervals not to exceed 6 months.  
5-2.11 Maintenance activities on fire control equipment shall be scheduled so that a  
minimum of equipment is taken out of service at any 1 time and fire prevention safety is  
not compromised.  
History: 2008 AACS.  
R 29.7110 Cathodic protection maintenance.  
Rule 110. Sections 5-3 and 5-3.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-3 Cathodic protection maintenance.  
5-3.1(a) Owners and operators shall ensure that all metallic container systems that are  
underground, mounded, or partially underground are protected and maintained to minimize  
corrosion as cited in the NACE standard RP0169 entitled "Recommended Practice, Control  
of External Corrosion of Underground or Submerged Metallic Piping Systems" and NACE  
recommended practice RP0285 entitled "Corrosion Control of Underground Storage Tank  
Systems by Cathodic Protection," adopted by reference in section 8.  
(b) All corrosion protection systems shall be operated and maintained to continuously  
provide corrosion protection to the metal components of the portion of the ASME approved  
container system that routinely contains liquid H2 and that is in contact with the ground.  
(c) All container systems equipped with cathodic protection systems shall be inspected  
for proper operation by a NACE certified cathodic protection tester as defined in section  
1-3. The H2 system shall be tested within 6 months of installation and at least once each  
calendar year at intervals not to exceed 15 months.  
(d) Container systems equipped with impressed current cathodic protection systems shall  
be inspected by the owner every 60 days to ensure that the equipment is operating within  
design specifications. The design limits shall be readily available.  
(e) If container systems are equipped with cathodic protection, then the owner or operator  
shall maintain records to demonstrate that the cathodic protection is in compliance with the  
performance standards of this section.  
The records shall provide both of the following:  
(i) The results of the last 3 inspections required in subsection (d) of this section.  
(ii) The results of testing from the last 2 inspections required in subsection (c) of this  
section.  
(f) Within 6 months following the repair of any cathodically protected container system,  
where the repairs may affect the operation of the cathodic protection system, the system  
shall be tested in accordance with subsections (c) and (d) of this section to ensure that it is  
operating properly.  
(g) Repairs or replacement of a cathodic protection system shall be conducted by a NACE  
certified corrosion expert as defined in section 1-3. General system maintenance of the  
cathodic protection system including, but not limited to, replacement of fuses, and splicing  
of cable would not be required to be designed by a corrosion expert and shall be approved  
by the department to not increase the hazard to public health, safety, and welfare and the  
environment.  
Page 83  
History: 2008 AACS.  
R 29.7111 Stray or impressed currents and bonding.  
Rule 111. Sections 5-4 to 5-4.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-4 Stray or impressed currents and bonding.  
5-4.1 Where stray or impressed currents are used or can be present on dispensing systems,  
such as cathodic protection, protective measures to prevent ignition shall be taken.  
5-4.2 Static protection between the fuel dispenser and the vehicle shall not be required  
where H2 is transferred by conductive hose, flexible metallic tubing, or pipe connections  
where both halves of the metallic couplings are in continuous contact.  
5-4.3 The transfer surface shall be concrete or shall have a resistivity not exceeding API  
RP 2003, "Protection Against Ignitions Arising Out of Static, Lightning, and Stray  
Currents," adopted by reference in section 8, performance criteria of 1 megohm as  
measured using a method acceptable to the department, such as EN 1081:1998 "Resilient  
Floor Coverings - Determination of the Electrical Resistance," adopted by reference in  
section 8.  
History: 2008 AACS.  
R 29.7112 Emergency plan.  
Rule 112. Sections 5-5 to 5-5.1.2 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
5-5 Emergency plan.  
5-5.1 Emergency plan requirements.  
5-5.1.1 An emergency plan shall be prepared and updated wherever gaseous or liquefied  
H2 are produced, handled, stored, or used.  
5-5.1.2 The plan shall be available to the department for inspection upon reasonable notice  
and shall include all of the following information:  
(a) The type of emergency equipment available and its location.  
(b) A brief description of any testing or maintenance programs for the available  
emergency equipment.  
(c) An indication that hazard identification labeling is provided for each storage area.  
(d) Location of posted emergency procedures.  
(e) A material safety data sheet (MSDS or equivalent) that is available for the gaseous or  
liquefied H2 stored or used on the site.  
(f) A list of personnel or a site operating authority who are designated and trained to be  
liaison personnel for the fire department and who are responsible for but shall not be limited  
to the following:  
(i) Aiding the emergency responders in pre-emergency planning.  
(ii) Identifying the location of the gaseous and liquefied H2 stored or used.  
(iii) Accessing material safety data sheets.  
(iv) Knowledge of the site emergency procedures.  
(g) A list of types and quantities of gaseous and liquefied H2 found within the facility.  
Page 84  
History: 2008 AACS.  
R 29.7113 Release of H2.  
Rule 113. Sections 5-6 to 5-6.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-6 Release of H2.  
5-6.1 Records of unexpected discharges. Accurate records of the unexpected discharge of  
gaseous or liquefied H2 shall be kept by the facility and made readily available upon  
request. Records shall be kept for a minimum of 2 years.  
5-6.2 Container failure. When an unexpected discharge due to primary container failure is  
discovered the department and the local fire department, shall be immediately notified, and  
the container shall be repaired or be removed from service.  
History: 2008 AACS.  
R 29.7114 Security.  
Rule 114. Sections 5-7 and 5-7.1 of the storage and handling of gaseous  
and Liquefied H2 code are added as follows:  
5-7 Security.  
5-7.1 Liquid H2 and compressed gas cylinders, containers, and systems shall be secured  
against accidental dislodgement and against access by unauthorized personnel.  
History: 2008 AACS.  
R 29.7115 Leaks, damage, or corrosion.  
Rule 115. Sections 5-8 and 5-8.1 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
5-8 Leaks, damage, or corrosion.  
5-8.1 Leaking, damaged, or corroded, liquid or gaseous H2 systems shall be removed from  
service, replaced or repaired.  
History: 2008 AACS.  
Chapter 6 Fire protection  
R 29.7116 Cautionary information.  
Rule 116. Sections 6-1 to 6-1.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
6-1 Cautionary information.  
6-1.1 Hazard identification signs shall be conspicuously placed at all locations where H2 is  
produced, stored, used, or handled.  
Page 85  
6-1.2 Ratings shall be assigned in accordance with NFPA 704, "Standard System for the  
Identification of the Hazards of Materials for Emergency Response," adopted by reference  
in section 8.  
History: 2008 AACS.  
R 29.7117 Signs.  
Rule 117. Sections 6-2 to 6-2.3 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
6-2.1 Signs prohibiting smoking or open flames within 25 feet (7.6 meters) shall be  
provided where H2 is produced, stored, or used.  
6-2.2 A sign with the following legends printed in red capital letters on a white background  
shall be conspicuously posted as follows:"NON-ODORIZED FLAMMABLE GAS -  
CRYOGENIC LIQUID or COLD GAS - NO SMOKING - NO OPEN FLAMES" All  
lettering on signage shall be 3 inches (7.62 centimeters) or more.  
Exception: This does not apply to motor vehicle dispensing per sections  
7.2.13 and 4-4.8.1.  
6-2.3 Identification signs. Visible hazard identification signs shall be provided in  
accordance with NFPA 704, "Standard System for the Identification of the Hazards of  
Materials for Emergency Response", adopted by reference in section 8.1.1, at entrances to  
buildings or areas in which liquefied H2 is stored, handled or used.  
History: 2008 AACS.  
R 29.7118 Fire extinguisher.  
Rule 118. Section 6-3 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:6-3 A portable fire extinguisher(s) having a rating of not less than 40-B:C  
or 2-20-B:C shall be located within 75 feet (22.9 meters) from the pumps, dispensers, and  
container fill openings. Fire extinguishers shall be inspected and maintained according to  
NFPA 10, "Standard for Portable Fire Extinguishers," adopted by reference in section 8-  
1.1.  
History: 2008 AACS.  
R 29.7119 Sprinkler protection.  
Rule 119. Section 6-4 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
6-4 When sprinkler protection is provided, the area in which H2 is stored or used shall be  
protected with an automatic sprinkler system designed to be not less than that required by  
NFPA 13, "Standard for the Installation of Sprinkler Systems," adopted by reference in  
section 8.  
History: 2008 AACS.  
Page 86  
Chapter 7 Liquefied hydrogen dispensing systems  
R 29.7120 System component qualification.  
Rule 120. Section 7-1 of the storage and handling of gaseous and Liquefied H2 code is  
added as follows:  
7-1 System component qualification. System components shall comply with applicable  
provisions of Chapters 2 and 3 of this part.  
History: 2008 AACS.  
R 29.7121 General system requirements.  
Rule 121. Sections 7-2 to 7-2.15 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-2 General system requirements.  
7-2.1 All fuel dispensing facilities shall meet the provisions of this chapter.  
7-2.2 Compression, processing, generation, storage, and dispensing equipment shall be  
protected to prevent damage from vehicles and minimize the possibilities of physical  
damage and vandalism and meet the requirements of section 2-1.5 and section 3-4.4.  
7-2.2.1 Access to liquefied H2 storage, compression, and processing equipment by  
members of the public shall be restricted by a suitable secure area.  
7-2.3 Control devices shall be installed so that internal or external icing does not cause  
vehicle or fueling station malfunction.  
7-2.4 Vehicles shall not be considered a source of ignition with respect to the provisions  
of this chapter.  
Exception: Vehicles containing fuel-fired equipment, such as recreational vehicles and  
catering trucks, shall be considered a source of ignition unless this equipment is shut off  
completely before entering an area in which ignition sources are not permitted.  
7-2.5 The fueling connection shall prevent the escape of H2 where the connector is not  
properly engaged or becomes separated.  
7-2.6 Fueling nozzles for H2 service shall be in accordance with section 2-14.1.  
7-2.7 Compression and processing equipment shall be designed for use with H2 and for  
maximum pressures and temperatures to which it can be subjected under normal operating  
conditions.  
7-2.8 Compression and processing equipment shall have pressure relief devices that limit  
each stage pressure to the maximum allowable working pressure for the compression  
cylinder and piping associated with that stage of compression and meets the requirements  
of chapter 2.  
7-2.9 H2 compression equipment shall be equipped with appropriate automatic shutdown  
controls.  
7-2.10 Control circuits that shut down, shall remain down until manually activated or reset  
by qualified personnel.  
7-2.11 A hazard analysis shall be conducted on every H2 fueling system installation by a  
qualified engineer(s) with proven expertise in H2 fueling systems and installations.  
Page 87  
7-2.11.1 The hazard analysis shall include the following: fire protection measures, fire  
protection and suppression systems, detection systems, and ventilation.  
7-2.11.2 At a minimum, the hazard analysis shall include consideration of potential failures  
in hoses, nozzles, dispensing equipment, as well as failures for maintenance and service.  
7-2.11.3 Method used for hazard analysis shall be 1 or combination of several of the  
following recognized procedures: hazard and operability studies (HAZOPs), failure mode  
effects and criticality analysis (FMECA), preliminary hazards analysis (PHA), fault tree  
analysis (FTA) and event tree analysis (ETA). Other analysis methods, when used, shall  
ensure same level of system safety as provided by any of the recognized procedures or  
acceptable to the department based on the best interest of public health, safety, and welfare,  
and the environment.  
7-2.11.4 Standard designs that have been analyzed by recognized procedure need not be  
studied each and every time such installation occurs. Site-specific elements that are unique  
to the installation shall be reviewed in concert with the analysis performed on the standard  
system to ensure that the standard design has not been altered in a way that would  
negatively affect the hazard analysis.  
7-2.11.5 These hazard analyses shall be available for review at final inspection, prior to the  
installation being placed into service, shall be maintained on site, and be available to the  
department upon request.  
7-2.12 Dispensing systems shall be equipped with overfill protection.  
7-2.13 Warning signs shall be conspicuously posted in the dispensing area and shall  
incorporate the following or equivalent wording: "Stop Motor, No Smoking, Non-  
Odorized Flammable Gas, Cryogenic Liquid or Cold Gas. Remain in attendance outside of  
the vehicle and in view of the nozzle. No filling of portable containers in or on a motor  
vehicle."  
7-2.14 Each outdoor H2-dispensing device shall be located not less than 10 feet (3.1 meters)  
from property lines, openings to buildings, and buildings of combustible wall construction.  
A dispensing device shall not be less than 20 feet (6.1 meters) from any activity that  
involves a fixed source of ignition. In addition, a dispenser shall not be placed beneath a  
power line.  
7-2.15 Each container filling location that is open to the public shall have an attendant or  
supervisor on duty who meets the requirements of section 1-8 of the rules.  
History: 2008 AACS.  
R 29.7122 Operational requirements for full-service liquefied H2 motor fuel  
dispensing facilities.  
Rule 122. Sections 7-3 to 7-3.2 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-3 Operational requirements for full-service liquefied H2 motor fuel dispensing facilities.  
7-3.1 Each motor fuel dispensing facility shall have an attendant or supervisor on duty  
whenever the facility is open for business. The attendant or supervisor shall dispense  
liquefied H2 into fuel tanks of motor vehicles or into portable containers.  
7-3.2 The provisions of section 2-1 of this part shall not prohibit the temporary use of a  
portable storage container in conjunction with the dispensing of liquefied H2 into a  
container of a motor vehicle or other motorized equipment which is on the premises and  
Page 88  
which is not accessible to the public. A portable storage container installation shall only be  
made with the approval of the department and comply with all the requirements of section  
2-13.  
History: 2008 AACS.  
R 29.7123 Operational requirements for attended self-service motor fuel dispensing  
facilities.  
Rule 123. Sections 7-4 to 7-4.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-4 Operating requirements for attended self-service motor fuel dispensing facilities.  
7-4.1 Self-service motor fuel dispensing facility shall mean that portion of a property where  
liquefied H2 used as motor fuel is stored and dispensed from fixed, approved dispensing  
equipment into the fuel containers of motor vehicles by persons other than the facility  
attendant and shall also include, where provided, facilities for sale of other retail products.  
7-4.2 There shall be not less than 1 attendant on duty while the self-service facility is open  
for business. The attendant's primary function shall be to supervise, observe, and control  
the dispensing of liquefied H2 while the liquefied H2 is actually being dispensed.  
7-4.3 The responsibility of the attendant shall be as follows:  
(a) Prevent the dispensing of liquefied H2 into portable containers in or on a motor vehicle.  
(b) Control sources of ignition.  
(c) Immediately activate emergency controls and notify the fire department of any fire.  
The attendant or supervisor on duty shall be mentally and physically capable of performing  
the functions and assuming the responsibility prescribed in section 7-4.  
7-4.4 Operating instructions shall be conspicuously posted in the dispensing area.  
7-4.5 The dispensing area shall at all times be in clear view of the attendant, and the placing  
or allowing of any obstacle to come between the dispensing area and the attendant control  
area is prohibited. This may be achieved by cameras or mirrors, or both. The attendant shall  
at all times be able to communicate with persons in the dispensing area.  
History: 2008 AACS.  
R 29.7124 Operational requirements for unattended self-service motor fuel  
dispensing facilities.  
Rule 124. Sections 7-5 to 7-5.5 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-5 Operating requirements for unattended self-service motor fuel dispensing facilities.  
7-5.1 Unattended self-service shall be permitted subject to the approval of the department  
based on the best interests of public health, safety, and welfare and the environment. Users  
shall use a key, card, or other method which is unique to each user, and which is provided  
by the facility operator, and shall be properly trained in dispensing operations. The owner  
shall verify such training to the department upon request.  
7-5.2 At least 1 emergency shutoff device specified in section 7-6 shall be provided, and  
shall be reset only by the owner or an owner's authorized agent.  
Page 89  
7-5.3 Operating instructions shall be conspicuously posted in the dispensing area. The  
instructions shall include the location of emergency controls.  
7-5.4 In addition to the warning signs specified in section 6-2, emergency instructions shall  
be conspicuously posted in the dispenser area. The instructions shall incorporate the  
following or equivalent wording: "Emergency Instructions In Case of Fire:  
(1) Use emergency stop button.  
(2) Report accident by calling the local fire number. Report location."  
7-5.5 A telephone or other approved, clearly identified means to notify the fire department  
shall be provided on the site in a location approved by the department.  
History: 2008 AACS.  
R 29.7125 Emergency shutoff devices.  
Rule 125. Sections 7-6 and 7-6.1 of the storage and handling of gaseous  
and Liquefied H2 code are added as follows:  
7-6 Emergency shutoff devices.  
7-6.1 Liquefied H2 dispensing systems shall be provided with 1 or more clearly identified  
emergency shutoff devices or electrical disconnects at the dispensing area. Such devices or  
disconnects shall be installed in approved locations but not less than 10 feet (3.1 meters)  
and not more than 100 feet (30.5 meters) away from the dispensing area and which is along  
the means of egress. Emergency shutoff devices or electrical disconnects shall disconnect  
power and fuel supply to all dispensing devices, to all remote pumps serving the dispensing  
devices, and to all associated power. When more than 1 emergency shutoff device or  
electrical disconnect is provided, all devices shall be interconnected. Resetting an  
emergency shutoff shall require manual intervention and the manner of resetting shall be  
approved by the department.  
History: 2008 AACS.  
R 29.7126 Refueling from transport vehicles.  
Rule 126. Sections 7-7 to 7-7.11 of the storage and handling of gaseous and Liquefied H2  
code are added as follows:  
7-7 Refueling from transport vehicles. The dispensing of liquefied H2 in the open from a  
transport vehicle to a motor vehicle located at commercial, industrial, governmental, or  
manufacturing establishments and intended for fueling vehicles used in connection with  
their businesses shall be permitted if all of the requirements of sections 7-7.1 to 7-7.11 have  
been met.  
7-7.1 The department shall be notified before commencing operations under section 7-7.  
7-7.2 The transport vehicle shall comply with U.S. DOT requirements for the transportation  
of liquefied H2.  
7-7.3 Nighttime deliveries shall only be made in an area considered to be adequately  
lighted.  
7-7.4 The transport vehicle flasher lights shall be in operation while dispensing operations  
are in progress.  
Page 90  
7-7.5 Smoking materials, including matches, lighters, and other sources of ignition,  
including torches, shall not be used within 20 feet (6.1 meters) of the dispensing of  
liquefied H2 in the open from a transport vehicle to a motor vehicle.  
7-7.6 Each area where dispensing of liquefied H2 in the open from a transport vehicle to a  
motor vehicle shall be provided with 1 or more listed fire extinguishers that have a  
minimum capability of 40-B:C. The fire extinguishers shall be readily accessible to the  
dispensing operation. Fire extinguishers shall be inspected and maintained under NFPA  
10, "Standard for Portable Fire Extinguishers," adopted by reference in section 8.  
7-7.7 Mobile fueling shall take place aboveground, shall not be beneath electric power lines  
or where exposed by their failure, and shall be 10 feet (3.1 meters) from the nearest  
important building, property lines or combustible storage.  
7-7.8 Transport vehicle brakes shall be set and chock blocks shall be in place.  
7-7.9 Persons performing dispensing operations shall be qualified to deliver and dispense  
H2 fuels. Operations of transport vehicles used for mobile fueling operations shall have  
access on-site or be in possession of an emergency communications device to notify the  
proper authorities if there is an emergency.  
7-7.10 The transport vehicles shall be positioned with respect to vehicles being fueled to  
prevent traffic from driving over the delivery hose and between the transport vehicle and  
motor vehicle being fueled. The dispensing hose shall be properly placed on an approved  
reel or in an approved compartment before moving the transport vehicle.  
7-7.11 The transfer area shall meet the requirements of section 5-4.  
History: 2008 AACS.  
Chapter 8 Referenced publications  
R 29.7127 Referenced publications.  
Rule 127. Sections 8-1 to 8-1.2.9 of the storage and handling of gaseous and Liquefied  
H2 code are added as follows:  
8-1 The following documents or portions thereof are referenced within this standard as  
mandatory requirements and shall be considered part of the requirements of this standard.  
The edition indicated for each referenced mandatory document is the current edition, and  
cost at time of adoption of these rules. Copies of the adopted publications are available for  
inspection at the office of the Department of Environmental Quality, Waste and Hazardous  
Materials Division, Storage Tank Unit, P.O. Box 30241, Lansing, Michigan 48909-7741.  
8-1.1 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, P.O.  
Box 9101, Quincy, Massachusetts 02269-9101.  
NFPA 10, "Standard for Portable Fire Extinguishers," 2002 edition, $36.50.  
NFPA 13, "Standard for the Installation of Sprinkler Systems," 2002 edition, $70.00.  
NFPA 69, "Standard on Explosion Prevention Systems," 2002 edition, $33.50.  
NFPA 70, "National Electrical Code," 2005 edition, $75.00.  
NFPA 220, "Standard on Types of Building Construction," 1999 edition, $28.00.  
NFPA 704, "Standard System for the Identification of the Hazards of Materials for  
Emergency Response," 2001 edition, $33.50.  
8-1.2 Other Publications.  
Page 91  
8-1.2.1 ASME Publications. American Society of Mechanical Engineers, Three Park  
Avenue, New York, New York 10016-5990.  
ANSI/ASME B31.3, "Process Piping," 2004 edition, $240.00.  
ASME International, "Boiler and Pressure Vessel Code," Section VIII, 2004 edition,  
$525.00.  
8-1.2.2 ASTM Publication. American Society for Testing and Materials, 100 Barr Harbor  
Drive, West Conshohocken, Pennsylvania 19428-2959.  
ASTM E136-04, "Standard Test Methods for Behavior of Materials in a Vertical Tube  
Furnace at 750 Degrees C," 2004 edition, $35.00.  
8-1.2.3 CGA Publications. Compressed Gas Association, 1725 Jefferson Davis Highway,  
Arlington Virginia 22202-4100.  
CGA S-1.1, "Pressure Relief Device Standards - Part 1 - Cylinders for Compressed Gases,"  
2002 edition, $196.00.  
CGA S-1.2, "Pressure Relief Device Standards - Part 2 - Cargo and Portable Tanks for  
Compressed Gases," 1995 edition, $145.00.  
CGA S-1.3, "Pressure Relief Device Standards - Part 3 - Stationary Storage Containers for  
Compressed Gases," 2003 edition, $145.00.  
CGA G-5.5, "Hydrogen Vent Systems," 2004 edition, $39.00.  
ANSI/CGA C-4, "Method of Marking Portable Compressed Gas Containers to Identify the  
Material Contained," 2003 edition, $252.00.  
CGA C-7, "Guide to the Preparation of Precautionary Labeling and Marking of  
Compressed Gas Containers," 2000 edition, $268.00.  
8-1.2.4 IAS Publications. International Approval Services, 8501 East Pleasant Valley  
Road, Cleveland, Ohio 44131.  
ANSI/IAS NGV 4.4, "Breakaway Devices for Dispensing Systems," 1999 edition, $57.00.  
8-1.2.5 NACE Publications. National Association of Corrosion Engineers International,  
1440 South Creek Drive, Houston, Texas 77084.  
NACE RP0169, "Control of External Corrosion of Underground or Submerged Metallic  
Piping Systems," 2002 edition, $42.00.  
NACE RP0285, "Corrosion Control of Underground Storage Tank Systems by Cathodic  
Protection," 2002 edition, $37.00.  
8-1.2.6 International Codes Council. 4051 West Flossmore Road, Country Club Hills,  
Illinois 60478-5795.  
"International Fire Code," 2006 edition, section 2209.3.2.6, $61.50.  
8-1.2.7 U.S. Government Publications. U.S. Government Printing Office,  
Washington, DC 20402.  
Title 49, Code of Federal Regulations, Parts 171-190, U.S. Department of Transportation  
Specifications and Regulations.  
8-1.2.8 ECS Publications. European Committee for Standardization, Central Secretariat:  
rue de Stassart 36, B-1050, Brussels.  
EN 1081, "Resilient Floor Coverings, Determination of the Electrical Resistance," 1998  
edition, $32.00.  
8-1.2.9 API Publications. American Petroleum Institute, 1220 L Street, Northwest,  
Washington, DC, 20005-5-4070.  
API Recommended Practice 2003, "Protection Against Ignitions Arising Out of Static,  
Lightning, and Stray Currents," 7th edition, $111.00.  
Page 92  
History: 2008 AACS.  