(2) An employer shall provide a mechanical air supply system if its absence will result in
building negative pressures sufficient to cause back-drafting of vents from fuel-fired
equipment or ineffective control.
(3) Mechanical air supply volumes shall be heated to maintain a minimum air temperature
of 65 degrees Fahrenheit measured at the point of air discharge to the space. Exceptions to
this requirement are refrigerated storage rooms, special process rooms, and similar
locations where low air temperatures are essential to the preservation of the product or
service, or, if in the opinion of the director, a lower air temperature will not be harmful to
the health of the persons affected.
(4) Make-up air for spray-finishing operations shall be as prescribed in General Industry
Safety Standard Part 76 “Spray Finishing Using Flammable and Combustible Materials,”
as referenced in R 325.52002.
(5) Make-up air for open surface tanks shall be as prescribed in Occupational Health
Standard Part 526 “Dipping and Coating Operations,” as referenced in R 325.52002.
History: 2005 AACS; 2016 AACS.
R 325.52006 Direct-fired air heaters.
Rule 6. (1) A direct-fired air heater, wherein combustion products are released in the
supply air stream, may be installed in buildings of industrial occupancy, garages, laundries,
and commercial kitchens. They shall not be installed in offices, schools, hospitals, and
places of public assembly.
(2) A direct-fired air heater shall have an inlet duct connected directly to the out-of-doors.
Room air shall not be circulated across the burner.
(3) A direct-fired air heater shall deliver air which contains not more than 10 ppm of
carbon monoxide and is free from odors of combustion products. Permissible
concentrations of other contaminants in the delivered air may be established by the director
pursuant to their permissible exposure limits and the degree of exposure to a person.
(4) The air volume supplied to the building by a direct-fired air heater shall not exceed
110% of the total air volume exhausted. The director may require interlocking of a heater
control system with an
exhaust ventilation system if necessary to ensure that the exhaust systems are operating.
(5) A direct-fired air heater shall have both of the following:
(a) A pre-ignition purge of fresh air.
(b) A positive fuel supply closure in the event of fuel supply failure, ignition failure, flame
failure, power failure or interruption, or air flow reduction below 50% of its rated capacity.
History: 2005 AACS.
R 325.52007 Exhaust ventilation systems.
Rule 7. The minimum rate of exhaust ventilation for places of manufacturing, processing,
assembling, maintenance and repair, or storage of material shall be 1 cubic foot of air per
minute per square foot of floor area. This amount of exhaust ventilation may be provided
by local exhaust, general exhaust, or both. The director may permit a variance if
contaminant control is accomplished at a lesser rate of ventilation.