(d) Patient laundry facilities with automatic washer and dryer.
(5) All of the following elements shall be provided, but may be either within the
psychiatric unit or immediately accessible to it:
(a) Rooms for examination and treatment with a minimum area of not less than 11.1
square meters (120 square feet). Examination treatment rooms for medical surgical patients
may be shared by the psychiatric unit patients. These rooms may be on a different floor if
conveniently accessible.
(b) Separate consultation rooms with a minimum floor space of 9.3 square meters (100
square feet) each shall be provided at the rate of 1 consultation room for each 30 psychiatric
beds. The rooms shall be designed for acoustical and visual privacy and constructed to
achieve a noise reduction of not less than 45 decibels.
(c) Each psychiatric unit shall contain 1.39 square meters (15 square feet) of separate
space per patient for occupational therapy with a minimum total area of not less than 18.6
square meters (200 square feet), whichever is greater. Space shall be provided for
handwashing, work counters, storage, and displays. Occupational therapy areas may serve
more than 1 nursing unit. When psychiatric units contain less than 16 beds, the
occupational therapy functions may be performed within the noisy
activities area, if not less than an additional 0.9 square meters (10 square feet) per patient
served is included.
(6) Within the psychiatric nursing unit there shall be a seclusion room or rooms for
patients requiring security and protection. The rooms shall be located for direct nursing
staff supervision. Each room shall be for only 1 patient. It shall have an area of not less
than 9.3 square meters (100 square feet) and be constructed to prevent patient hiding,
escape, injury, or suicide. If a facility has more than 1 psychiatric nursing unit, the number
of seclusion rooms shall be a function of the total number of psychiatric beds in the facility.
Seclusion rooms may be grouped together. The seclusion room is intended for short-term
occupancy by a patient who has become violent or suicidal. Therefore, special fixtures
and hardware, including ground fault interrupters (GFI) for electrical circuits and
tamperproof outlets, shall be used. Doors shall open out and shall permit staff observation
of the patient while maintaining patient privacy. If the interior of a seclusion room is
padded with combustible materials, the room area, including the floor, walls, ceiling, and
all openings, shall be protected with not less than 1-hour-rated construction.
History: 1990 AACS.
R 330.1243 Construction and equipment of nursing units generally.
Rule 1243. (1) Each patient room in a nursing unit shall meet all of the following
standards:
(a) Maximum room capacity shall be 4 patients.
(b) Patient room areas, exclusive of toilet rooms, closets, lockers, wardrobes, alcoves, or
vestibules, shall be not less than 9.29 square meters (100 square feet) for single-bed rooms
and 7.43 square meters (80 square feet) per bed for multiple-bed rooms. Minor
encroachments, including columns and lavatories, that do not interfere with functions may
be ignored when determining space requirements for patient rooms. In multiple-bed rooms,
a clearance of 1.12 meters (3 feet 8 inches) shall be available at the foot of each bed to
permit the passage of equipment and beds. The areas noted in this subdivision are intended
Page 6