DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS  
DIRECTOR’S OFFICE  
GENERAL INDUSTRY SAFETY AND HEALTH STANDARD  
(By authority conferred on the director of the department of licensing and regulatory affairs  
by sections 16 and 21 of the Michigan occupational safety and health act, 1974 PA 154,  
MCL 408.1016 and 408.1021, and Executive Reorganization Order Nos. 1996-2, 2003-1,  
2008-4, and 2011-4, MCL 445.2001, 445.2011, 445.2025, and 445.2030)  
PART 6. FIRE EXITS  
GENERAL PROVISIONS  
R 408.10601 Scope.  
Rule 601. (1) These rules specify requirements for means of egress for employee use  
required by the advent of hazardous conditions such as fire, explosion, and natural disaster.  
(2) These rules apply to workplaces in general industry except mobile workplaces such  
as vehicles or vessels.  
(3) These rules cover the minimum requirements for exit routes that employers must  
provide in their workplace so that employees may evacuate the workplace safely during an  
emergency. These rules cover the minimum requirements for emergency action plans and  
fire prevention plans.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10602 Applicability.  
Rule 602. (1) This part covers new and existing construction. In various sections of this  
part there are special provisions for existing buildings differing from those for new  
construction. Where there are no specific provisions in this part for existing buildings, the  
requirements for new construction shall apply.  
(2) If a political subdivision of the state has fire safety standards in conflict with this part,  
the more restrictive provisions of either the political subdivision or this standard shall  
apply.  
History: 1979 AC.  
R 408.10603 Definitions; B to F.  
Rule 603. (1) "Breakaway door" means a door that is designed to slide in normal operation  
and which will swing open in any position when a maximum pressure of 50 pounds is  
applied to the latch side of the door in an emergency.  
Page 1  
(2) "Draw bolt" means a metal bar or rod in the mechanism of a lock that is thrown or  
withdrawn by turning the key or retracting a lever.  
(3) “Electroluminescent” means a light-emitting capacitor. Alternating current excites  
phosphor atoms when placed between the electrically conductive surfaces to produce light.  
This light source is typically contained inside the device.  
(4) "Fire area of a building" means that space contained within component structural parts  
that has a fire resistance sufficient to prevent the further spread of fire that originates  
therein.  
(5) "Fire door" means a fire-resistive door assembly, including the frame and hardware.  
(6) "Fire resistance" means the property of a material or assembly to withstand fire or give  
protection from it.  
(7) "Flammable" means subject to easy ignition and rapid flaming combustion.  
(8) "Floor area" or "gross area" means the floor area within the perimeter of the outside  
walls of a building, with no deductions for any of the following:  
(a) Hallways.  
(b) Stairs.  
(c) Closets.  
(d) Thickness of walls.  
(e) Columns.  
(f) Other features.  
(9) "Flush bolt" means a door bolt that is designed so that when applied it is flush with  
the face or edge of the door.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10604 Definitions; H to M.  
Rule 604. (1) "Hasp and staple" means a fastening device that consists of a slotted hinge  
plate and a loop (staple).  
(2) "Hazardous area" means an area of a building, or portion thereof, used for purposes  
that involve highly combustible, highly flammable, or explosive products or materials  
which are likely to burn with extreme rapidity or which may produce poisonous fumes or  
gases, including highly toxic or noxious acids, alkalines, or irritant hazards; which cause  
the division of material into fine particles or dust subject to explosion or spontaneous  
combustion; or which constitute a high fire hazard because of the form, character, or  
volume of the material used.  
(3) "Hazard of contents" means the relative danger of the start and spread of fire, the  
danger of smoke or gases generated, and the danger of explosion or other occurrence  
potentially endangering the lives and safety of employees in a building. Where certain  
features of a building are such as to involve a hazard greater than the hazard of the contents,  
the greater degree of hazard shall govern.  
(4) “High hazard area” means an area inside a workplace in which operations include high  
hazard materials, processes, or contents.  
(5) "High hazard contents" means combustibles of a character or quantity that burn with  
extreme rapidity or from which extremely poisonous fumes or explosions are to be  
expected in the case of fire.  
Page 2  
(6) "Horizontal exit" means a way of passage from a building to an area of refuge in  
another building on approximately the same level or a way of passage through or around a  
fire-resistant wall or fire-resistant partition to an area of refuge on approximately the same  
level in the same building which affords safety from fire or smoke in the area of escape  
and areas communicating therewith.  
(7) "Listed” means equipment that is listed if it is of a kind mentioned in a list that is  
published by a nationally recognized testing laboratory that makes periodic inspections of  
the production of such equipment and that states that such equipment meets nationally  
recognized standards or has been tested and found safe for use in a specified manner.  
(8) "Low hazard contents" means combustibles of such low combustibility that self-  
propagating fire cannot occur and that consequently the only probable danger will be from  
panic, fumes, smoke, or fire from some external source.  
(9) "Means of egress” also known as an “exit route” means a continuous and unobstructed  
path of exit travel from any point within a workplace to a place of safety, including refuge  
areas. A means of egress includes both vertical and horizontal areas along the route of  
travel. A means of egress or an exit route consists of 3 separate parts and are defined as  
follows:  
(a) "Exit access" means that portion of a means of egress or an exit route which leads to  
an exit. An example of an exit access is a corridor on the 5th floor of an office building that  
leads to a 2-hour fire resistance-rated enclosed stairway.  
(b) "Exit" means that portion of a means of egress or an exit route that is separated from  
the area of a building from which escape is to be made by a wall, floor, door, or other  
means which provides the protected path necessary to proceed with reasonable safety to  
the exterior of the building. An example of an exit is a 2-hour fire resistance-rated enclosed  
stairway that leads from the 5th floor of an office building to the outside of the building.  
(c) "Exit discharge" means that portion of an exit route that leads directly outside or to a  
street, walkway, refuge area, public way, or open space with access to the outside. An  
example of an exit discharge is a door at the bottom of a 2-hour fire resistance-rated  
enclosed stairway that discharges to a place of safety outside the building.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10605 Definitions; N to S.  
Rule 605. (1) “Nationally recognized testing laboratory." See 29 C.F.R. §1910.7  
“Definition and requirements for a nationally recognized testing laboratory,” as adopted in  
R 408.10606, for the definition.  
(2) "Noncombustible building" means a building that is constructed of materials that do  
not support fire.  
(3) “Occupant load” means the total number of persons that may occupy a workplace or  
portion of a workplace at any one time. The occupant load of a workplace is calculated by  
dividing the gross floor area of the workplace or portion of the workplace by the occupant  
load factor for that particular type of workplace occupancy. Information regarding the  
"Occupant load" is located in NFPA 101 “Life Safety Code,” 2009 edition and in the  
“International Fire Code” 2009 edition, as adopted in R 408.10606.  
Page 3  
(4) "Ordinary hazard contents" means combustibles that are liable to burn with moderate  
rapidity and to give off a considerable volume of smoke, but from which neither extremely  
poisonous fumes nor explosions are to be expected in case of fire.  
(5) “Refuge area” means either of the following:  
(a) A space along an exit route that is protected from the effects of fire by separation from  
other spaces within the building by a barrier with at least a 1-hour fire resistance-rating.  
(b) A floor with at least 2 spaces, separated from each other by smoke-resistant partitions,  
in a building protected throughout by an automatic sprinkler system that complies with  
General Industry Safety Standard Part 9 “Fixed Fire Equipment,” as referenced in  
R 408.10606.  
(6) "Self-closing" means equipped with an approved device which will ensure closing  
without manual assistance after having been opened.  
(7) "Sprinklered" means equipped with an approved automatic sprinkler system that is  
properly maintained.  
(8) "Street" means a public thoroughfare that is 30 or more feet in width, that has been  
dedicated or deeded to the public for public use, and that is accessible for use by a fire  
department in fighting fires. An enclosed space or tunnel, even though used for vehicular  
and pedestrian traffic, is not considered a street.  
(9) “Self-luminous” means a light source that is illuminated by a self-contained power  
source, like tritium, and that operates independently from external power sources. Batteries  
are not acceptable self-contained power sources. The light source is typically contained  
inside the device.  
(10) "Surface bolt" means a locking bolt that is installed on the surface of a door.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10606 Adoption of standards by reference; access to MIOSHA rules.  
Rule 606. (1) The National Fire Protection Association NFPA 101 “Life Safety Code,”  
2009 edition, is adopted by reference in these rules and is available from IHS Global, 15  
Inverness Way East, Englewood, Colorado, 80112, USA, telephone number:  
1-800-854-7179 or via the internet at the following website: http://global.ihs.com, at a cost  
as of the time of adoption of these rules of $93.00.  
(2) The “International Fire Code” 2009 edition, is adopted by reference in these rules and  
is available from International Code Council, 500 New Jersey Avenue, NW, 6th floor,  
Washington, DC 20001, USA, telephone number: 1-800-786-4452, or via the internet at  
the following website: www.iccsafe.org, at a cost as of the time of adoption of these rules  
of $113.00.  
(3) The following federal Occupational Safety and Health Administration (OSHA)  
regulations are adopted by reference in these rules:  
(a) 29 CFR 1910.7 “Definition and requirements for a nationally recognized testing  
laboratory,” as amended February 25, 2011.  
(b) 29 CFR 1910.165 “Employee alarm systems,” as amended September 12, 1980.  
(4) The federal regulations adopted by reference in these rules are available from the  
United States Department of Labor, Occupational Safety and Health Administration  
website: www.osha.gov, at no charge, as of the time of adoption of these rules.  
Page 4  
(5) The standards adopted in these rules are available for inspection at the Department of  
Licensing and Regulatory Affairs, MIOSHA Regulatory Services Section, 530 West  
Allegan Street, P.O. Box 30643, Lansing, Michigan, 48909-8143.  
(6) Copies of the standards adopted in these rules may be obtained from the publisher or  
may be obtained from the Department of Licensing and Regulatory Affairs, MIOSHA  
Regulatory Services Section, 530 West Allegan Street, P.O. Box 30643, Lansing,  
Michigan, 48909-8143, at the cost charged in this rule, plus $20.00 for shipping and  
handling.  
(7) The following Michigan Occupational Safety and Health Administration (MIOSHA)  
Standards are referenced in these rules. Up to 5 copies of these standards may be obtained  
at no charge from the Michigan Department of Licensing and Regulatory Affairs,  
MIOSHA Regulatory Services Section, 530 West Allegan Street, P.O. Box 30643,  
Lansing, Michigan, 48909-8143 or via the internet at the following website:  
www.michigan.gov/mioshastandards. For quantities greater than 5, the cost, at the time of  
adoption of these rules, is 4 cents per page.  
(a) General Industry Safety and Health Standard Part 2. “Walking-Working Surfaces,”  
R 408.10201 to R 408.10241.  
(b) General Industry Safety Standard Part 9. “Fixed Fire Equipment,” R 408.10901 to  
R 408. 10999.  
History: 1979 AC; 1990 AACS; 2015 AACS; 2019 AACS.  
R 408.10607 Rescinded.  
History: 1954 ACS 62, Eff. May 18, 1970; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10608 Notification of emergency escape procedures and routes; designation of  
evacuation assistants.  
Rule 608. (1) An employer shall assure that employees are informed of emergency escape  
procedures and emergency routes to approved means of egress.  
(2) An employer shall designate a sufficient number of persons to assist in the safe and  
orderly emergency evacuation of employees.  
History: 1990 AACS.  
R 408.10610 Rescinded.  
History: 1954 ACS 69, Eff. Nov. 15, 1971; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10611 Design of buildings and structures.  
Rule 611. (1) The danger to employees must be minimized.  
(2) A building or structure designed for human occupancy shall be provided with exits,  
as prescribed in this part, that permit prompt escape in case of fire or other emergency.  
Page 5  
(3) Exits and other safeguards shall be designed so that an employee's safety or  
preservation of life in case of fire or other emergency is not dependent solely on a single  
safeguard. Additional safeguards shall be provided for life safety in case any single  
safeguard is ineffective due to human or mechanical failure.  
(4) Exit routes shall be kept free of explosive or highly flammable furnishings or other  
decorations.  
(5) A building or structure shall be constructed, arranged, equipped, maintained, and  
operated to avoid undue danger to the lives and safety of the employees from fire, smoke,  
fumes, or panic during the period of time necessary for escape from the building or  
structure.  
(6) An employee alarm system must be operable. Employers shall install and maintain an  
operable employee alarm system that has a distinctive signal to warn employees of fire or  
other emergencies, unless employees can promptly see or smell a fire or other hazard in  
time to provide adequate warning to them. The employee alarm system must comply with  
General Industry Safety Standard Part 9 “Fixed Fire Equipment,” and 29 C.F.R. 1910.165  
“Employee alarm systems” as adopted in R 408.10606.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10612 Occupancy of new buildings.  
Rule 612. During new construction, employees shall not occupy a workplace until the exit  
routes required by these rules are completed and ready for employee use for the portion of  
the workplace they occupy.  
History: 1979 AC; 2015 AACS.  
R 408.10613 Occupancy and use during repairs and alterations.  
Rule 613. (1) During repairs or alterations, employees shall not occupy a workplace unless  
the exit routes required by these rules are available and existing fire protections are  
maintained, or until alternate fire protection is furnished that provides an equivalent level  
of safety.  
(2) Employees shall not be exposed to hazards of flammable or explosive substances or  
equipment used during construction, repairs, or alterations, that are beyond the normal  
permissible conditions in the workplace, or that would impede exiting the workplace.  
History: 1979 AC; 2015 AACS.  
R 408.10614 Operating condition of protective equipment.  
Rule 614. A required exit, exit lighting, automatic sprinkler system, fire detection and  
alarm system, fire door, and other required items of fire protection shall be maintained in  
proper operating condition.  
History: 1979 AC.  
Page 6  
R 408.10615 Rescinded.  
History: 1954 ACS 62, Eff. May 18, 1970; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10616 Rescinded.  
History: 1954 ACS 69, Eff. Nov. 15, 1971; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10617 Rescinded.  
History: 1954 ACS 62, Eff. May 18, 1970; rescinded 1954 ACS 79, Eff. May 16, 1974.  
CLASSES OF OCCUPANCY AND HAZARD OF CONTENTS  
R 408.10621 Classes of occupancy.  
Rule 621. A building or part thereof shall be classified as follows:  
(a) A hotel, which includes a building, portion of a building, or group of buildings which  
is under the same management and in which there are more than 16 sleeping  
accommodations for hire that are primarily used by transients, whether designated as a  
hotel, apartment hotel, inn, club, or motel or by any other name.  
(b) Mercantile occupancy, which includes a store, market, and other room or building for  
the display and sale of merchandise. Examples of this occupancy are as follows:  
(i) Supermarkets.  
(ii) Department stores.  
(iii) Shopping centers.  
(iv) Drugstores.  
(v) Auction rooms.  
(c) Business occupancy, which means a place used for the transaction of business, other  
than that covered under mercantile occupancy, for the keeping of accounts and records and  
for similar purposes. Examples of this occupancy are as follows:  
(i) Doctors' and dentists' offices.  
(ii) City and township halls.  
(iii) Courthouses.  
(iv) Libraries.  
(v) Schools.  
(d) An industrial occupancy, which includes a factory that makes products of all kinds  
and a property devoted to operations such as processing, assembling, mixing, packaging,  
finishing or decorating, repairing, and similar operations. Examples of this group are as  
follows:  
(i) Laboratories.  
(ii) Dry cleaning plants.  
(iii) Power plants.  
Page 7  
(iv) Pumping stations.  
(v) Smokehouses.  
(vi) Laundries.  
(vii) Creameries.  
(viii) Gas plants.  
(ix) Refineries.  
(x) Sawmills.  
(e) A storage occupancy, which includes a building that is used primarily for the storage  
or sheltering of goods, merchandise, products, vehicles, or animals. Examples of this group  
are as follows:  
(i) Warehouses.  
(ii) Cold storage operations.  
(iii) Freight terminals.  
(iv) Truck and marine terminals.  
(v) Bulk oil storage.  
(vi) Parking garages.  
(vii) Hangars.  
(viii) Grain elevators.  
(ix) Barns.  
(x) Stables.  
(f) Miscellaneous occupancies, which means those buildings covered in the provisions of  
R 408.10691 to R 408.10697.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10622 Multiple and partial occupancies.  
Rule 622. (1) If 2 or more classes of occupancy occur in the same building so intermingled  
that separate safeguards are impracticable, the safeguard facilities shall be sufficient to  
meet the requirements for each individual area or section, as well as for the entire building.  
(2) If a minor portion of a building is used for any purpose incidental to the major  
occupancy and the minor occupancy does not incur any hazard to the remainder of the  
building, it shall be classified as part of the major occupancy.  
History: 1979 AC.  
R 408.10623 Employee emergency action plans.  
Rule 623. (1) An employer shall have an emergency action plan whenever required by a  
particular Michigan occupational safety and health act standard. The requirements in these  
rules apply to each such emergency action plan.  
(2) An emergency action plan shall be in writing, kept in the workplace, and available to  
employees for review. However, an employer with 10 or fewer employees may  
communicate the plan orally to employees.  
(3) An emergency action plan shall include at a minimum all of the following:  
(a) Procedures for reporting a fire or other emergency.  
Page 8  
(b) Procedures for emergency evacuation, including type of evacuation and exit route  
assignments.  
(c) Procedures to be followed by employees who remain to operate critical plant  
operations before they evacuate.  
(d) Procedures to account for all employees after evacuation.  
(e) Procedures to be followed by employees performing rescue or medical duties.  
(f) The name or job title of every employee who may be contacted by employees who  
need more information about the plan or an explanation of their duties under the plan.  
(4) An employer shall establish an employee alarm system that is in compliance with the  
provisions of General Industry Safety Standard Part 9 “Fixed Fire Equipment,” and 29  
C.F.R. 1910.165 “Employee alarm systems” as adopted in R 408.10606. If the employee  
alarm system is used for alerting fire brigade members or for other purposes, a distinctive  
signal for each purpose shall be used.  
(5) An employer shall establish in the emergency action plan the types of evacuation to  
be used in emergency circumstances.  
(6) Before implementing the emergency action plan, an employer shall designate and train  
a sufficient number of persons to assist in the safe and orderly emergency evacuation of  
employees.  
(7) The employer shall review the plan, at the following times, with each employee to  
whom the plan applies:  
(a) When the plan is developed.  
(b) If an employee's responsibilities or designated actions under the plan change.  
(c) If the plan is changed.  
(8) An employer shall review, with each employee, upon initial assignment, those parts  
of the plan that the employee must know to protect the employee in an emergency.  
History: 1993 AACS; 2015 AACS.  
R 408.10624 Fire prevention plans.  
Rule 624. (1) An employer shall have a fire prevention plan whenever they are required  
by a particular Michigan occupational safety and health act standard. The requirements in  
these rules apply to each such fire prevention plan.  
(2) A fire prevention plan must be in writing, be kept in the workplace, and be made  
available to employees for review. However, an employer with 10 or fewer employees may  
communicate the plan orally to employees.  
(3) An employer shall control the accumulations of flammable and combustible waste  
materials and residues so that they do not contribute to a fire emergency. The control  
procedures shall be included in the written fire prevention plan.  
(4) An employer shall inform employees of the fire hazards of the materials and processes  
to which they are exposed.  
(5) An employer shall review, with each employee, upon initial assignment, those parts  
of the fire prevention plan that the employee must know to protect the employee in an  
emergency.  
(6) An employer shall regularly and properly maintain, according to established  
procedures, equipment and systems that are installed on heat-producing equipment to  
Page 9  
prevent the accidental ignition of combustible materials. The maintenance procedures shall  
be included in the written fire prevention plan.  
(7) Minimum elements of a fire prevention plan shall include all of the following  
information:  
(a) A list of all major fire hazards, proper handling and storage procedures for hazardous  
materials, potential ignition sources and their control, and the type of fire protection  
equipment necessary to control each major hazard.  
(b) Procedures to control accumulations of flammable and combustible waste materials.  
(c) Procedures for regular maintenance of safeguards installed on heat-producing  
equipment to prevent the accidental ignition of combustible materials.  
(d) The name or job title of employees responsible for maintaining equipment to prevent  
or control sources of ignition or fires.  
(e) The name or job title of employees responsible for the control of fuel source hazards.  
History: 1993 AACS; 2015 AACS.  
R 408.10625 Rescinded.  
History: 1954 ACS 62, Eff. May 18, 1970; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10626 Rescinded.  
History: 1954 ACS 62, Eff. May 18, 1970; rescinded 1954 ACS 79, Eff. May 16, 1974.  
R 408.10627 Compliance with alternate exit-route codes.  
Rule 627. MIOSHA shall deem an employer demonstrating compliance with the exit-  
route provisions of the NFPA 101 “Life Safety Code,” 2009 edition or the exit-route  
provisions of the “International Fire Code” 2009 edition, as adopted in R 408.10606, to be  
in compliance with the corresponding requirements in these rules.  
History: 2015 AACS.  
MEANS OF EGRESS  
R 408.10631 Construction, maintenance, and changes.  
Rule 631. (1) The components of a means of egress including doors, stairs, ramps,  
passages, and signs shall be of substantial construction and shall be maintained in an  
operable condition.  
(2) An exit shall be not less than 28 inches (71.1 cm) wide at all points, except where  
specifically permitted elsewhere in this part. Where there is only 1 exit access leading to  
an exit or exit discharge, the width of the exit and exit discharge shall be at least equal to  
the width of the exit access.  
Page 10  
(3) The ceiling of an exit route shall be at least 7 feet 6 inches (2.3 m) high. Any projection  
from the ceiling shall not reach a point less than 6 feet 8 inches (2.0 m) from the floor.  
(4) The width of an exit route shall be sufficient to accommodate the maximum permitted  
occupant load of each floor served by the exit route.  
(5) Objects that project into the exit route shall not reduce the width of the exit route to  
less than the minimum width requirements for exit routes.  
(6) Exit routes must be kept free of explosive or highly flammable furnishings or other  
decorations.  
(7) A space formed with movable or folding partitions and occupied by more than 20  
persons shall have an approved means of egress.  
(8) An alteration, addition, or change of occupancy that would reduce means of egress  
below the requirements for a new building is prohibited.  
(9) Furnishings and decorations of an explosive or highly flammable character shall not  
be used in any occupancy.  
(10) Where fire retardant paints or solutions are used, they shall be renewed, as necessary  
to maintain their fire retardant properties.  
History: 1979 AC; 2015 AACS.  
R 408.10632 Obstructions.  
Rule 632. (1) An employer shall ensure that exit routes are free and unobstructed. No  
materials or equipment may be placed, either permanently or temporarily, within the exit  
route. The exit access must not go through a room that can be locked, such as a bathroom,  
to reach an exit or exit discharge, nor may it lead into a dead-end corridor. Stairs or a ramp  
must be provided where the exit route is not substantially level.  
(2) A lock, fastening device, or barrier must not be installed or used on a means of egress  
in a manner that will prevent or hinder free escape from the inside of a building.  
(3) Exit route doors must be free of any device or alarm that could restrict emergency use  
of the exit route if the device or alarm fails.  
(4) Devices such as turnstiles and gates must not be placed so as to obstruct a means of  
egress.  
(5) Combustible or flammable debris, waste, or other material, the burning of which  
would render hazardous egress from the building must not be placed, stored, or kept on,  
under, at the bottom of, or adjacent to a means of egress or elevator. Where a means of  
egress is being obstructed by the placement of movable objects, aisles must be marked, and  
railings or permanent barriers provided to protect the means of egress against  
encroachment.  
(6) Each exit route door must be free of decorations or signs that obscure the visibility of  
the exit route door. A mirror must not be placed on an exit door or be placed in or adjacent  
to an exit in a manner to confuse the direction of exit.  
History: 1979 AC; 2015 AACS; 2019 AACS.  
R 408.10633 Permissible exits and exit components.  
Page 11  
Rule 633. (1) Approved exits for all occupancies regulated by this part shall be restricted  
to the following permissible types: doors, inside or outside stairs, horizontal exits, ramps,  
escalators, and fire escapes for existing occupancies.  
(2) An exit shall consist only of approved components. An exit shall be constructed as an  
integral part of the building or permanently affixed thereto.  
(3) Stairs, landings, and other exit components shall be guarded against falls over open  
edges, and guards and handrails shall continue the full length of the guarded exit  
component.  
(4) An exit protected by separation from other parts of the building shall have the  
separating construction meet the following:  
(a) The separation shall have not less than a 1-hour fire-resistance rating when the exit  
connects 3 stories or less. This applies whether the stories connected are above or below  
the story at which the exit discharge is located.  
(b) The separation shall have not less than a 2-hour fire-resistance rating when the exit  
connects 4 or more stories, whether above or below the floor of discharge.  
(c) An opening into an exit must be protected by a self-closing fire door that remains  
closed or automatically closes in an emergency upon the sounding of a fire alarm or  
employee alarm system.  
(d) An opening in an exit enclosure shall be confined to that which is necessary for access  
to the enclosure from a normally occupied space and for egress from the enclosure.  
(5) Each exit route shall be a permanent part of the workplace.  
(6) Each fire door, including its frame and hardware, shall be listed or approved by a  
nationally recognized testing laboratory. For the definition of a "nationally recognized  
testing laboratory, see 29 C.F.R. §1910.7 “Definition and requirements for a nationally  
recognized testing laboratory,” as adopted in R 408.10606.  
History: 1979 AC; 2015 AACS.  
R 408.10634 Number of exits.  
Rule 634. (1) An employer shall ensure that there are an adequate number of exit routes.  
(2) Where the contents of a building are classified as high hazard, there shall be not less  
than 2 exits which are accessible in different directions. All doors shall swing in the  
direction of exit travel. Where floor areas are divided into rooms, there shall be not less  
than 2 ways of escape from every room, however small, except for toilet rooms that are not  
located in areas of high hazard classification.  
(3) The exit routes shall be located as far away as practical from each other so that if 1  
exit route is blocked by fire or smoke, employees can evacuate using the second exit route.  
(4) At least 2 exit routes shall be available in a workplace to permit prompt evacuation of  
employees and other building occupants during an emergency, except as allowed in subrule  
(6) of this rule.  
(5) More than 2 exit routes shall be available in a workplace if the number of employees,  
the size of the building, its occupancy, or the arrangement of the workplace is such that all  
employees would not be able to evacuate safely during an emergency.  
(6) A single exit route is permitted where the number of employees, the size of the  
building, its occupancy, or the arrangement of the workplace is such that all employees  
would be able to evacuate safely during an emergency.  
Page 12  
Note: For assistance in determining the number of exit routes necessary for your  
workplace, consult NFPA 101 “Life Safety Code,” 2009 edition or “International Fire  
Code” 2009 edition, as adopted in R 408.10606.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10635 Travel distance to exits.  
Rule 635. (1) The total number of exits in a building shall be sufficient so that the  
maximum travel distance from any occupied space to at least 1 exit shall not exceed the  
limits specified in R 408.10636.  
(2) The distance to an exit shall be measured along the center line of the natural and  
unobstructed path of travel.  
(3) In case of an open area, the distance to an exit shall be measured from the most remote  
point subject to occupancy. In case of an individual room subject to occupancy by not more  
than 6 persons, distance to an exit shall be measured from the doors of such room if the  
path of travel from any point in the room to the door does not exceed 50 feet.  
(4) Where an open stairway is part of a path of travel to a required exit, the distance shall  
include the travel on the stairway, and the travel from the end of the stairway to reach an  
outside door or other exit, in addition to the distance to reach the stairway.  
(5) Where any part of an outside stair or other outside exit is within 15 feet horizontal  
distance of an unprotected building opening, the distance to an exit shall include the length  
of travel, to ground level, on the exit itself.  
(6) Exits and exit access shall be so arranged that there are no dead-end pockets or  
hallways whose depths exceed the limits specified for the individual occupancies in table  
1.  
History: 1979 AC.  
R 408.10636 Maximum travel distance to exits.  
Rule. 636. Table 1 reads as follows:  
Page 13  
TABLE 1  
Maximum travel distance to exits  
(in feet)  
Dead-end limits  
(in feet)  
Type of occupancy  
Unsprinklered  
Sprinklered  
Mercantile, ordinary hazard  
Mercantile, high hazard  
Business  
150  
75  
250  
75  
50  
0
200  
200  
0
300  
250  
75  
50  
50  
0
Industrial  
Industrial, high hazard  
Storage, low and ordinary  
hazard  
200  
400  
100  
Storage, high hazard  
Hotels  
75  
100  
200  
0
100  
50  
Note: For miscellaneous structures, See R 408.10691 to R 408.10697  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10637 Rescinded.  
History: 1979 AC; 2015 AACS.  
R 408.10638 Rescinded.  
History: 1979 AC; 2015 AACS.  
R 408.10639 Capacity as affected by population.  
Rule 639. (1) The capacity of a means of egress from a building, floor, balcony, tier, or  
other occupied space shall be sufficient for the population thereof. The population for  
industrial and storage occupancies shall be based on the maximum number of employees  
or persons that may be in the space at any time as determined by actual count. All other  
types of occupancies shall be not less than the number computed in accordance with the  
provisions of table 2.  
(2) Mercantile occupancy in a single-story, noncombustible building with an approved,  
fully equipped automatic sprinkler system that is in compliance with General Industry  
Safety Standard Part 9 “Fixed Fire Equipment,” as referenced in R 408.10606, may  
increase the square footage requirement in table 2 by 100%.  
(3) The population of an occupancy shall be limited to the existing exit capacity of a  
building or space.  
Page 14  
(4) Where an exit serves more than 1 floor, only the population of each floor considered  
individually need be used in computing the capacity of the exit at that level, if the exit  
capacity is not decreased in the direction of exit travel. Where a means of egress from  
floors above and below converge at an intermediate level, the capacity of the exit from the  
point of convergency shall be not less than the combined capacity of the converging exits.  
(5) Table 2 reads as follows:  
TABLE 2  
Type of occupancy  
Mercantile, street floor or sales basement  
Mercantile, other floors  
Mercantile, office  
Mercantile, storage  
Business  
Square feet per person  
30  
60  
100  
300  
100  
200  
100  
Hotel  
Industrial  
Note: The computed population of an occupancy is obtained by dividing the total floor  
area of a building, floor, or fire area by the indicated square feet per person. Total floor  
area means the floor area within the perimeter of the outside walls of a building, with no  
deductions for any of the following:  
(a) Hallways.  
(b) Stairs.  
(c) Closets.  
(d) Thickness of walls.  
(e) Columns.  
(f) Other features.  
(6) The capacity of an exit route shall be adequate. Information regarding the "Occupant  
load" is located in NFPA 101 “Life Safety Code,” 2009 edition and in the “International  
Fire Code” 2009 edition, as adopted in R 408.10606.  
(7) Exit routes shall support the maximum permitted occupant load for each floor served.  
(8) The capacity of an exit route shall not decrease in the direction of exit route travel to  
the exit discharge.  
History: 1979 AC; 2015 AACS.  
R 408.10641 Exit access and discharge.  
Rule 641. (1) An exit access must not be through a room subject to locking.  
(2) An exit access must be so arranged that it will not be necessary to travel through any  
area of high hazard occupancy to reach the nearest exit.  
Page 15  
(3) The minimum width of an exit access must be at least equal to the required width of  
the exit to which it leads, but not less than 34 inches. The headroom clearance must be not  
less than 6 feet 8 inches from the floor.  
(4) An exit discharge must discharge directly outside or to a street, walkway, refuge area,  
public way, or to a yard, court, or other open space with access to the outside.  
(5) Stairs and other exits must be arranged to make clear the direction of egress to the  
street. Where an exit stairs continues beyond the floor of discharge, it must be interrupted  
at the floor of discharge by a partition, door, or other effective means.  
(6) Exit access by the way of an exterior balcony, porch, gallery, or roof must be in  
compliance with all of the following:  
(a) Be kept free from accumulations of snow and ice.  
(b) Be a permanent direct route without obstructions, such as railings, gates, barriers, or  
other objects, that might divide the space into sections or rooms. Furniture or other movable  
objects must not block the path of travel.  
(c) Have no dead ends in excess of 20 feet.  
(d) Comply with this standard as to requirements for width and arrangement.  
(7) The street, walkway, refuge area, public way, or open space to which an exit discharge  
leads must be large enough to accommodate the building occupants likely to use the exit  
route.  
(8) An exit door must be unlocked.  
(9) An outdoor exit route is permitted.  
(10) The outdoor exit route must have all of the following:  
(a) Guardrails to protect unenclosed sides if a fall hazard exists.  
(b) Be covered if snow or ice is likely to accumulate along the route, unless the employer  
can demonstrate that any snow or ice accumulation will be removed before it presents a  
slipping hazard.  
(c) Be reasonably straight and have smooth, solid, substantially level walkways.  
(d) Not have a dead-end that is longer than 20 feet (6.2 m).  
(11) An exit access must be so arranged that employees will not have to travel toward a  
high hazard area, unless the path of travel is effectively shielded from the high hazard area  
by suitable partitions or other physical barriers.  
History: 1979 AC; 2015 AACS; 2019 AACS.  
DOORS AND STAIRS  
R 408.10643 Doors; general provisions.  
Rule 643. (1) A door assembly, including the doorway, frame, door, and necessary  
hardware, may be used as a component in a means of egress when it conforms to the  
requirements of this part. As such, the assembly is designated as an exit door.  
(2) A single leaf of an exit door shall be not less than 28 inches nor more than 48 inches  
in width.  
(3) Where a door or gate opens directly on a stairway, a platform shall be provided, and  
the swing of the door or gate shall not reduce the floor area leading to the stairs to a width  
less than 20 inches.  
Page 16  
History: 1979 AC; 2015 AACS.  
R 408.10644 Door swing.  
Rule 644. (1) A side-hinged exit door shall be used. The force required to fully open any  
door in the means of egress shall not be more than 5 pounds applied to the latch side of the  
door. The door shall swing with exit travel when serving an area of high hazard occupancy  
or a building, floor, or area with a population of more than 50 persons.  
(2) If 1 or more approved exits are provided and the travel distance requires additional  
exits, a mechanically aided sliding door may be used to exit to the outside of a building  
constructed before May 15, 1970, under the following conditions:  
(a) The occupancy shall be classified as a low or ordinary storage hazard or an ordinary  
mercantile hazard.  
(b) The mechanical aid to the door shall allow the door to be opened quickly and easily  
by 1 person.  
(c) The mechanical aid of the door shall not be rendered inoperative by fire or the lack of  
maintenance.  
(3) An exit door that gives access to a stairway shall swing in the direction of exit travel,  
shall not block stairs or landings during its swing, and shall not interfere with the full use  
of the stairway when open.  
(4) An exit door at the foot of stairs from upper floors or at the head of stairs from  
basements shall swing with exit travel.  
(5) A screen door or storm door that is part of a required exit shall not swing against the  
direction of exit travel in any case where doors are required to swing with exit travel.  
(6) A side-hinged door shall be used to connect any room to an exit route.  
(7) The door that connects any room to an exit route shall swing out in the direction of  
exit travel if the room is designed to be occupied by more than 50 people or if the room is  
a high hazard area; for example, it contains contents that are likely to burn with extreme  
rapidity or explode.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10645 Locks, fastening devices, and closing mechanism.  
Rule 645. (1) Employees shall be able to open an exit route door from the inside at all  
times without keys, tools, or special knowledge. A device such as a panic bar that locks  
only from the outside is permitted on exit discharge doors.  
(2) A latch or other fastening device on an exit door shall be provided with a knob, handle,  
panic bar, or other simple type of releasing device. Slide bolts, hasps, hooks and eyes, and  
similar types of locking devices that are difficult to open against door pressure shall not be  
installed or used.  
(3) A fire door to a stair enclosure or horizontal exit shall be provided with a reliable self-  
closing mechanism and shall not, at any time, be secured in the open position.  
(4) An exit route door may be locked from the inside only in mental, penal, or correctional  
facilities and then only if supervisory personnel are continuously on duty and the employer  
has a plan to remove occupants from the facility during an emergency.  
Page 17  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10646 Power operated doors.  
Rule 646. An exit door, wholly or partly power operated, shall be so designed that in case  
of power failure it can be manually operated. A power operated door shall not be counted  
as a required exit unless it swings with the exit travel.  
History: 1979 AC.  
R 408.10647 Revolving doors.  
Rule 647. (1) A revolving door shall be considered an approved exit door only if all of  
the following conditions are satisfied:  
(a) The door shall be installed before the prohibition listed in subrule (2) of this rule.  
(b) The number of revolving doors used as exit doors shall not be more than the number  
of swinging doors used as exit doors within 20 feet thereof.  
(c) A revolving door without an adjacent swinging door may serve as an exit for a street  
floor elevator lobby if no stairway or door from other parts of the building discharges  
through the lobby and the lobby has no occupancy other than as a means of travel between  
elevators and the street.  
(d) A revolving door shall be equipped with means to prevent its rotation at more than 12  
1/2 revolutions per minute.  
(e) A revolving door shall not be used at the foot of stairs from upper floors or at the head  
of stairs from the basement or other lower floors.  
(f) A revolving door credited as an exit door shall have a rated capacity of 1/2 unit of exit  
width.  
(2) A revolving door that is installed after June 15, 1990, shall not be considered an  
approved exit door.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10651 Stairs.  
Rule 651. (1) Stairs serving as a required exit shall comply with the requirements of this  
part as to construction specifications and details, and of table 3.  
TABLE 3  
Minimum width clear of all obstructions  
except handrails which may project  
not more than 3 1/2 inches each side.  
44 inches. 36 inches where total  
occupancy of all floors is served  
by stairway is less than 50  
persons.  
Maximum height of risers:  
Existing construction  
New construction  
9 inches.  
8 inches  
Page 18  
Minimum width of tread exclusive of nosing or  
projection:  
Existing construction  
8 inches.  
New construction  
10 inches.  
Winders:  
Permitted when complying with  
all other requirements of this  
part.  
Existing construction -  
New construction -  
Not permitted.  
Maximum height between landings  
12 feet.  
Minimum dimension of landing in direction of travel  
44 inches  
(2) A variation in the width of tread or height of risers in any flight shall not exceed 3/16  
inch.  
(3) A stair and a platform or landing used in connection therewith, in a building 4 stories  
or more in height, shall be of noncombustible construction throughout, except for handrails.  
(4) A stair, platform, landing, balcony, and stair hallway floor shall be designed to carry  
a load of 100 pounds per square foot, or a concentrated load of 300 pounds so located as to  
produce maximum stress conditions.  
(5) Where the material of stair treads and landings is such as to involve danger of slipping,  
nonslip material shall be provided on the tread surface.  
(6) Stairways and intermediate landings shall continue with no decrease in width along  
the direction of exit travel.  
(7) Monumental stairs, either inside or outside, may be accepted as required exits if all  
requirements for exit stairs are complied with, except that curved stairs may be accepted  
with a radius of 25 feet or more at the inner edges.  
History: 1979 AC.  
HORIZONTAL EXITS, RAMPS, AND ESCALATORS  
R 408.10661 Horizontal exits.  
Rule 661. (1) A fire area or area of refuge with a horizontal exit shall have, in addition to  
the horizontal exit or exits, at least 1 means of egress leading to the outside, or have access  
to an adjacent fire area containing an outside means of egress.  
(2) Where either side of a horizontal exit is occupied, the doors used in connection with  
the horizontal exit shall be unlocked.  
(3) The floor area on either side of a horizontal exit shall be sufficient to hold the  
occupants of both floor areas allowing not less than 3 square feet clear floor area per person.  
(4) Where a horizontal exit serves areas on both sides of a wall, there shall be adjacent  
openings with swinging doors at each, opening in opposite directions, with signs on each  
side of the wall or partition indicating as the exit door which swings with the travel from  
Page 19  
that side; or other approved arrangements providing doors always swinging with any  
possible exit travel.  
History: 1979 AC; 2015 AACS.  
R 408.10664 Ramps.  
Rule 664. (1) A ramp may be a component in a means of egress when it conforms to the  
requirements of this part. A ramp which is constructed after June 15, 1990, and which is  
less than the minimum measurements prescribed in this rule shall not be considered as an  
approved part of a means of egress.  
(2) A ramp and the platforms and landings associated therewith shall be designed for not  
less than 100 pounds per square foot live load.  
(3) The slope of a ramp shall not vary between landings. A landing shall be level and the  
changes in direction of travel, if any, shall be made only at landings.  
(4) A ramp in a building that is more than 3 stories in height shall be made of  
noncombustible construction. A ramp floor and landings shall be solid and without  
perforations.  
(5) A ramp shall have a nonslip surface.  
(6) A ramp shall have a minimum width of 44 inches and a maximum slope of 1 inch in  
12 inches.  
History: 1979 AC; 1990 AACS; 2015 AACS.  
R 408.10667 Escalators.  
Rule 667. An escalator, to be considered a component of means of egress, shall be fully  
enclosed above the ground floor and equipped with fire doors containing fusible links to  
protect the escalator area against the passage of flame, smoke, and gases in the event of  
fire. An escalator being operated in the direction contrary to normal exit travel shall not be  
considered a means of egress.  
History: 1979 AC.  
FIRE ESCAPES  
R 408.10671 Fire escape stairs.  
Rule 671. (1) Fire escape stairs may be used as a required exit only in existing buildings.  
Fire escape stairs shall not constitute more than 50% of the required exit capacity. Fire  
escape stairs shall not constitute any part of the required exits for a new building.  
(2) Fire escape stair dimensions shall be in accordance with table 4.  
Page 20  
TABLE 4  
Minimum Width  
22 inches clear between rails  
22 inches  
Minimum horizontal dimension of a landing or  
platform  
Maximum rise  
9 inches  
Minimum tread, exclusive of nosing  
Spiral winders  
9 inches  
Not permitted  
12 feet  
Maximum height between landings  
(3) Fire escape stairs shall have walls or approved guards, and handrails on both sides.  
History: 1979 AC; 2015 AACS.  
R 408.10672 Stair construction and load.  
Rule 672. (1) Iron, steel, concrete, or other approved noncombustible material shall be  
used for the construction of fire escape stairs, balconies, railings, and other features  
appurtenant thereto.  
(2) Balconies and stairs shall be designed to carry a load of 100 pounds per square foot,  
or a concentrated load of 300 pounds so located as to produce maximum stress conditions.  
History: 1979 AC.  
R 408.10673 Exposure to fire escape stairs.  
Rule 673. Fire escape stairs shall be so arranged that they will be subject to exposure by  
the smallest possible number of window and door openings. Every opening, any portion of  
which is within the following limits, shall be completely protected by approved fire doors  
or metal frame wired glass windows, as follows:  
(a) A horizontal opening if within 15 feet of a balcony, platform or stairway constituting  
a part of the escape proper. This does not apply to a platform or walkway leading from the  
same floor to the escape proper. Protection need not extend around a right angle corner  
(outside angle 270 degrees) of the building.  
(b) An opening below if within 3 stories or 36 feet of a balcony, platform, walkway or  
stairway constituting a part of the escape proper, or within 2 stories or 24 feet of a platform  
or walkway leading from any story to the escape proper.  
(c) An opening above if within 10 feet of a balcony, platform or walkway, as measured  
vertically, or from any stair treads, as measured vertically from the face of the outside riser.  
(d) An opening on a top story. Protection for wall openings is not required where stairs  
do not lead to the roof.  
History: 1979 AC; 2015 AACS.  
Page 21  
R 408.10674 Access to fire escape stairs.  
Rule 674. (1) Access to fire escape stairs shall be by doors or casement windows whose  
minimum dimensions are 24 inches by 6 feet 6 inches, or by double hung windows 30 by  
36 inches clear opening. Double hung windows shall be so counterbalanced and maintained  
that they can be readily opened.  
(2) Insert screens, if any, on any type of opening giving access to fire escape stairs shall  
be of types that may be readily opened or pushed out. Storm sash shall not be used on a  
window providing access to fire escape stairs.  
(3) Access to fire escape stairs through windows with sills more than 12 inches above the  
inside floor level shall be provided with permanent access steps leading to the access  
window. The outside balcony shall not be more than 18 inches below the sill.  
History: 1979 AC.  
R 408.10675 Swinging stairs.  
Rule 675. (1) A swinging stair section shall not be used for a fire escape stairs, except  
where termination is over a sidewalk, alley, or driveway.  
(2) A swinging stair section shall not be located over doors, over the path of travel from  
another exit, nor be in any location where there are obstructions.  
(3) The width of a swinging stair section shall be at least equal to that of the stairs above  
and the pitch shall not be steeper than that of the stairs above.  
(4) A counterweight shall be provided for a swinging stair section and this shall be of the  
type balancing about a pivot, no cables being used. Counter-balancing shall be such that a  
weight of 150 pounds 1 step from pivot will not start swinging section, and a weight of 150  
pounds, 1/4 of the length of the swinging stairs from the pivot, will positively cause the  
stairs to swing down.  
(5) A latch or other device shall not be installed or used to lock a swinging stair section  
in the up position.  
History: 1979 AC; 2015 AACS.  
R 408.10677 Ladders.  
Rule 677. No form of ladder shall be used as a fire escape except that a ladder conforming  
to General Industry Safety and Health Standard Part 2. “Walking-Working Surfaces,” as  
referenced in R 408.10606, may be used to provide a means of escape from a boiler room,  
storage elevator, or tower, as permitted for special miscellaneous occupancies, elevated  
platforms around machinery, or similar spaces subject to routine simultaneous occupancy  
by not more than 3 persons.  
History: 1979 AC; 2015 AACS; 2019 AACS.  
R 408.10679 Rescinded.  
History: 1979 AC; 1998-2000 AACS.  
Page 22  
ILLUMINATION AND MARKING  
R 408.10680 Lighting.  
Rule 680. (1) Lighting and marking shall be adequate and appropriate.  
(2) Each exit route shall be adequately lighted so that an employee with normal vision  
can see along the exit route.  
History: 2015 AACS.  
R 408.10681 Artificial lighting.  
Rule 681. (1) A means of egress shall be illuminated by artificial lighting at places and  
for periods of time required to maintain the illumination to values not less than 1.0  
footcandles measured at the floor. Illumination shall be so arranged that the failure of any  
single lighting unit, such as the burning out of an electric bulb, will not leave the area in  
darkness.  
(2) Artificial lighting shall be from a source of reasonable reliability, such as a public  
utility service. A battery operated electric light or any type of portable lamp or lantern shall  
not be used for primary exit illumination. Luminescent, fluorescent, or reflective material  
shall not be used as a substitute for required illumination.  
History: 1979 AC.  
R 408.10682 Emergency illumination.  
Rule 682. In a building with natural lighting subject to occupancy by more than 300  
persons, and in a building for which no natural lighting is provided and subject to  
occupancy by more than 100 persons, approved emergency lighting facilities shall be  
provided for a means of egress so arranged that required exit illumination will be  
maintained for a period of at least 1/2 hour in the event of failure of normal lighting of the  
building. Emergency lighting facilities shall be automatic, and there shall be no appreciable  
period of interruption during the change-over from the normal lighting of the building.  
History: 1979 AC.  
R 408.10685 Signs.  
Rule 685. (1) A means of egress to an exit not immediately apparent from any point in an  
occupancy shall be marked by directional signs. Additionally, the line-of-sight to an exit  
sign shall be clearly visible at all times.  
(2) A door, passage, or stairway, which is neither an exit nor an exit access, and which is  
so located or arranged as to be likely mistaken for an exit, shall be identified by a sign  
reading "NOT AN EXIT" or similar designation, or be identified by a sign indicating its  
actual use or character.  
Page 23  
(3) A sign shall designate an exit and shall be located and be of such size and color and  
design as to be readily visible and identifiable from the distance of travel for that particular  
occupancy.  
(4) Each exit must be clearly visible and marked by a sign reading "EXIT."  
History: 1979 AC; 2015 AACS.  
R 408.10686 Sign illumination and letter size.  
Rule 686. (1) An exit sign shall be illuminated to a surface value of at least 5 foot-candles  
(54 lux) by a reliable light source and be distinctive in color. Self-luminous or  
electroluminescent signs that have a minimum luminance surface value of at least .06 foot  
lamberts (0.21 cd/m2) are permitted.  
(2) An exit sign shall have the word "EXIT" in plainly legible letters not less than 6 inches  
(15.2 cm) high, with the principal strokes of the letters in the word "EXIT" not less than  
3/4 of an inch (1.9 cm) wide.  
(3) An internally illuminated exit sign shall be provided where the reduction of normal  
illumination is permitted and less than 5 footcandles would appear on the exit sign.  
History: 1979 AC; 2015 AACS.  
MISCELLANEOUS OCCUPANCIES  
R 408.10691 Vehicles.  
Rule 691. A house trailer or similar vehicle, railroad car, street car, truck, or bus from  
which the wheels have been removed and a permanent-type foundation provided, or  
otherwise fixed so that it is no longer mobile, is considered a building and is subject to the  
requirements of this part.  
History: 1979 AC.  
R 408.10692 Vessels.  
Rule 692. A ship, barge, or other vessel permanently moored or aground and occupied for  
purposes other than navigation is subject to the requirements of this part.  
History: 1979 AC.  
R 408.10693 Open buildings.  
Rule 693. An open building includes all operations conducted in the open air where  
equipment is in the open with platforms used for necessary access, sometimes with roofs  
or canopies to provide shelter, but without walls as distinguished from an enclosed  
building. An open building shall have exit facilities providing at least 1 means of escape  
Page 24  
from any point subject to employee occupancy, such means of escape affording safety from  
fire or smoke therefrom, explosion or release of fumes.  
History: 1979 AC.  
R 408.10694 Aircraft hangars.  
Rule 694. (1) An exit from an aircraft storage or servicing area shall be provided at  
intervals of not more than 150 feet on all exterior walls of the aircraft hangar. A minimum  
of 2 exits shall serve each aircraft storage or servicing area. Horizontal exits through  
interior walls shall be provided at intervals of not more than 100 feet. Dwarf or "smash"  
doors in doors accommodating aircraft may be used to comply with these requirements.  
(2) An exit from a mezzanine floor in an aircraft storage or servicing area shall be so  
arranged that the maximum travel to reach the nearest exit from any point on the mezzanine  
shall not exceed 75 feet.  
History: 1979 AC.  
R 408.10695 Storage elevators for combustible commodities.  
Rule 695. (1) In a storage elevator for combustible commodities there must be at least 1  
stairway from the basement to the first floor and from the first floor to the top floor of the  
working house that is enclosed in a dust-tight, non-combustible shaft.  
(2) A non-combustible door of the self-closing type must be provided at each floor  
landing.  
(3) An exterior stair or basket ladder-type fire escape, must be provided from the roof of  
the working house to ground level or to the roof of an adjoining annex with access from all  
floors above the first, in compliance with General Industry Safety and Health Standard Part  
2. “Walking-Working Surfaces,” as referenced in R 408.10606.  
(4) An exterior stair or basket ladder-type fire escape, must be provided from the roof of  
each storage annex to ground level, in compliance with General Industry Safety and Health  
Standard Part 2. “Walking-Working Surfaces,” as referenced in R 408.10606.  
(5) A fire escape ladder must be provided adjacent to a manlift for the up and down sides.  
(6) A storage elevator must have an opening that leads to a fire escape ladder from each  
floor or work level.  
(7) Storage elevators for combustible commodities that exist before April 30, 1974, do  
not need to comply with the provisions of subrules (1) and (2) of this rule.  
History: 1979 AC; 1990 AACS; 2015 AACS; 2019 AACS.  
R 408.10696 Towers.  
Rule 696. (1) A tower occupied for purposes such as observation or signaling, either an  
independent structure or on top of a building, shall be permitted with a single stairway or  
ramp exit if all of the following conditions are met:  
(a) The tower is of such size as not to be subject to occupancy by more than 25 persons  
on any 1 floor level.  
Page 25  
(b) The tower is subject only to occupancy by persons capable of descending the stairway  
and is not used for living or sleeping purposes.  
(c) The construction is fire-resistive, non-combustible, or heavy timber, with no  
quick-burning interior finish. There must be no combustible materials in, under, or in the  
immediate vicinity of the tower, except as necessary to perform the requirements of  
occupancy.  
(2) Stairs must conform to the requirements of this standard, except that for existing  
towers fire escape type stairs may be used in compliance with General Industry Safety and  
Health Standard Part 2. “Walking-Working Surfaces,” as referenced in R 408.10606.  
(3) A tower, such as a forest fire observation tower and a railroad signal tower designed  
for occupancy by not more than 3 persons employed therein, need not be constructed of  
fire-resistive, non-combustible material and may be served by ladders instead of stairs in  
compliance with General Industry Safety and Health Standard Part 2. “Walking-Working  
Surfaces,” as referenced in R 408.10606.  
History: 1979 AC; 2015 AACS; 2019 AACS.  
R 408.10697 Piers and water-surrounded buildings.  
Rule 697. (1) A pier used for any purpose other than for mooring of vessels and handling  
of cargo shall be provided with a means of egress from any building thereon to the pier and  
from the pier to the mainland appropriate to the character of the occupancy of the pier.  
(2) A building, such as a lighthouse, surrounded by water shall have a sufficient area of  
ground, as on an island or fire-resistive platform, to provide an adequate area of refuge  
from a fire in the building.  
History: 1979 AC.  
Page 26  
;