Rule 633. (1) Approved exits for all occupancies regulated by this part shall be restricted
to the following permissible types: doors, inside or outside stairs, horizontal exits, ramps,
escalators, and fire escapes for existing occupancies.
(2) An exit shall consist only of approved components. An exit shall be constructed as an
integral part of the building or permanently affixed thereto.
(3) Stairs, landings, and other exit components shall be guarded against falls over open
edges, and guards and handrails shall continue the full length of the guarded exit
component.
(4) An exit protected by separation from other parts of the building shall have the
separating construction meet the following:
(a) The separation shall have not less than a 1-hour fire-resistance rating when the exit
connects 3 stories or less. This applies whether the stories connected are above or below
the story at which the exit discharge is located.
(b) The separation shall have not less than a 2-hour fire-resistance rating when the exit
connects 4 or more stories, whether above or below the floor of discharge.
(c) An opening into an exit must be protected by a self-closing fire door that remains
closed or automatically closes in an emergency upon the sounding of a fire alarm or
employee alarm system.
(d) An opening in an exit enclosure shall be confined to that which is necessary for access
to the enclosure from a normally occupied space and for egress from the enclosure.
(5) Each exit route shall be a permanent part of the workplace.
(6) Each fire door, including its frame and hardware, shall be listed or approved by a
nationally recognized testing laboratory. For the definition of a "nationally recognized
testing laboratory, see 29 C.F.R. §1910.7 “Definition and requirements for a nationally
recognized testing laboratory,” as adopted in R 408.10606.
History: 1979 AC; 2015 AACS.
R 408.10634 Number of exits.
Rule 634. (1) An employer shall ensure that there are an adequate number of exit routes.
(2) Where the contents of a building are classified as high hazard, there shall be not less
than 2 exits which are accessible in different directions. All doors shall swing in the
direction of exit travel. Where floor areas are divided into rooms, there shall be not less
than 2 ways of escape from every room, however small, except for toilet rooms that are not
located in areas of high hazard classification.
(3) The exit routes shall be located as far away as practical from each other so that if 1
exit route is blocked by fire or smoke, employees can evacuate using the second exit route.
(4) At least 2 exit routes shall be available in a workplace to permit prompt evacuation of
employees and other building occupants during an emergency, except as allowed in subrule
(6) of this rule.
(5) More than 2 exit routes shall be available in a workplace if the number of employees,
the size of the building, its occupancy, or the arrangement of the workplace is such that all
employees would not be able to evacuate safely during an emergency.
(6) A single exit route is permitted where the number of employees, the size of the
building, its occupancy, or the arrangement of the workplace is such that all employees
would be able to evacuate safely during an emergency.
Page 12