placed in the same tunnel, trench, or duct with fuel gas pipe lines if natural or forced
ventilation is provided.
(2) Low points in piping carrying moist gas shall be drained into drip pots constructed so
as to permit pumping or draining out the condensate at necessary intervals. A drain valve
shall be installed for this purpose, having an outlet normally closed with screw caps or
plugs. Open end valves or petcocks shall not be used, except that, in drips located out of
doors, underground, and not readily accessible, a valve may be used at such points if it is
equipped with means to secure it in the closed position. A pipe leading to the surface of the
ground shall be cased or jacketed where necessary to prevent loosening or breaking.
(3) A gas shutoff valve shall be provided at the pipe entrance to a building. There shall
also be provided a shutoff valve in the discharge line from the generator, gas holder,
manifold, or other source of supply.A shutoff valve shall not be installed in a manner that
renders a safety relief device ineffective.
(4) Before assembly, piping and fittings shall be freed of scale and dirt. An oxygen line
shall be washed out with a solution such as caustic soda or trisodium phosphate. After
assembly, piping shall be blown out with oil-free air or oil-free inert gas.
(5) Loose dirt that may have been trapped in the pipe shall be blown out with oil-free air
or oil-free inert gas.
(6) Pressure testing of a pipeline shall be done in a manner to protect an employee from
injury due to blowing out of closures and other pressure restraining devices.
(7) A piping system shall be tested and proved gastight at 1 1/2 times the maximum
operating pressure and shall be purged of air before being placed in service. The material
used for testing oxygen lines shall be oil-free and noncombustible. A flame shall not be
used to detect leaks.
(8) Repairs on ferrous piping for other than inert gas lines shall be preceded by purging
the lines, unless only nonsparking tools are used.When gas lines and other parts of a
manifold system are being purged, a source of ignition shall not be permitted near the
uncapped opening.
(9) Outdoor ferrous and all underground piping and fittings shall be covered or painted to
protect against corrosion.
(10) A steel or wrought iron pipe joint shall be welded, threaded, or flanged.
(11) A brass or copper pipe joint shall be welded, brazed, threaded, or flanged. A seamless
copper, brass, or stainless steel tubing joint shall be brazed or gas tubing fittings used.
Where a socket-type joint is used, it shall be brazed with silver brazing alloy or similar
filler metal having a melting point not less than 800 degrees Fahrenheit.
History: 1979 AC; 1981 AACS.
R 408.11243 Installation and identification of piping.
Rule 1243. (1) Above ground piping, station outlet, and section valves shall be identified
as to contents by color or name, or both, as prescribed in ASME A13.1 “Identification of
Piping Systems,” 1956 edition, as adopted in R 408.11202.
(2) A cylinder manifold shall be installed under the supervision of an individual
experienced in the proper practices with reference to its installation and use.
History: 1979 AC; 2013 AACS.