or the employee is working with, or under the supervision of, a licensed electrician. A
qualified employee is not required to be licensed when working on utility installation or
maintenance such as, but not limited to, substations, switch yards, and street or highway
lighting.
(2) The employer shall insure that all live parts of electrical equipment operating at 50
volts or more are properly guarded against accidental contact.
(3) The employer shall do all of the following:
(a) Limit access to energized electrical equipment such as, but not limited to, switch gear,
transformers, and service panels, to qualified employees.
(b) Provide, and insure the proper use of, an accident prevention sign on electric
apparatus, equipment, and enclosures. The voltage shall be indicated.
(c) Provide a conductor of an ampacity of not less than the rating of the circuit breaker or
fuses protecting that circuit.
(d) Insure that a bare conductor or earth return is not used for any temporary circuit.
(e) Insure that all electrical wiring is protected from physical damage.
History: 1979 AC.
R 408.41724 Electrical installations.
Rule 1724. (1) Electrical apparatus and equipment used for construction operations shall
bear an approved label or marking.
(2) Before work begins, a competent person shall ascertain by inquiry, observation, or
instruments whether any part of an electric power circuit, exposed or concealed, is so
located that, in performance of the work, contact by an employee, tool, or equipment can
be made with the circuit.
(3) Any employee shall not be permitted to be in proximity to any part of an electric
power circuit that he may contact unless the employee is protected against electric shock
by de-energizing the circuit and locking out and tagging it, or unless the employee working
on an energized circuit is guarded by insulation, insulated tools, or insulating matting or
blankets sufficient to protect against the voltage involved.
(4) Where an electrical power circuit exists that can be contacted by an employee, the
employer shall do both of the following:
(a) Post and maintain accident prevention signs prescribed in Part 22. Signals, Signs,
Tags, and Barricades, being R 408.42201 et seq. of the Michigan Administrative Code.
(b) Advise the employee of the location of the lines, hazard involved, and protective
measures taken or to be taken.
(5) When an employee is using a jack hammer, bar, or other tool which could come in
contact with an underground line, the energy source shall be de-energized.
(6) A work space of not less than 3 feet wide and 6 1/2 feet high, in addition to space
necessary to open equipment doors not less than 90 degrees, shall be provided and
maintained in the area of electrical equipment.
(7) Barriers or other means shall be provided to ensure that the work space for electrical
equipment is not used as a passageway during periods when energized parts of electrical
equipment are exposed.
History: 1979 AC.